| Date |
Text |
| 2018-08-20 11:44:56 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. 3 PHASE PANEL ON SINGLE PHASE SERVICE. (THIS HAS NOT |
| | BEEN ADDRESSED IN THE RISER DIAGRAM. RISER DIAGRAM MUST |
| | ACCURATELY REFLECT THE CURRENT ELECTRICAL SERVICE. HOW |
| | COULD A 3 PHASE SERVICE BE FED FROM A SINGLE PHASE |
| | SERVICE? PROVIDE ACCURATE RISER DIAGRAM, SHOWING ALL |
| | DETAILS OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD |
| | SERVICE, WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO |
| | ANY SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW |
| | INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, |
| | 250.50, 250.94, 408.30; WPB FBC 107.2.1 |
| | |
| | NEW COMMENT: |
| | |
| | 2. PLAN HAS A BLOCK NOTE THAT STATES THERE IS NOW WORK |
| | TO BE INTENDED UNDER THIS PERMIT, BUT PLAN SHOWS |
| | EXHAUST FANS BEING INSTALLED. CORRECT DISCREPANCY. WPB |
| | FBC 107.2.1 |
| | 3. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE, |
| | INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF |
| | SERVICE IS ADEQUATE. LOAD CALCULATION SHOULD SHOW LOADS |
| | BASED ON THE WATTAGE DEMAND FOR EACH LOAD, AND THEN |
| | DIVIDED BY THE APPROPRIATE VOLTAGE. LOAD CALCULATION |
| | PROVIDED SWITCHES BETWEEN AMPERAGE OF LOADS AND |
| | WATTAGE, AND THEREFORE IS DIFFICULT TO UNDERSTAND. |
| | BASED ON THE NUMBERS PROVIDED, THE SERVICE TO SOUTH |
| | BUILDING IS OVERLOADED AS IS, AND NOW THERE WILL BE |
| | ADDITIONAL LOAD FOR EXHAUST FANS. THERE IS ALSO NO LOAD |
| | SHOWN FOR SMALL APPLIANCE CIRCUITS, WATER HEATERS, AND |
| | EXHAUST HOODS. NEC 215.2, 220, 408.30 |
| | 4. PROVIDE PANEL SCHEDULE(S) INDICATING ANY NEW OR |
| | ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE |
| | CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE |
| | TO COMPLY WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, |
| | 215.5, 408.4; WPB FBC 107.3.5 |
| | 5. EACH OCCUPANT SHALL HAVE READY ACCESS TO ALL |
| | OVERCURRENT DEVICES PROTECTING THE CONDUCTORS SUPPLYING |
| | THAT OCCUPANCY. LOCATION OF ELECTRICAL PANELS NOT SHOWN |
| | ON PLAN, THEREFORE IT IS IMPOSSIBLE TO DETERMINE |
| | COMPLIANCE WITH THIS REQUIREMENT. PROVIDE CORRECTION. |
| | NEC 240.24(B) |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |