| 2018-04-24 12:42:59 | 2ND REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES |
| | PERMIT #17120551 |
| | 4/24/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) COMMENTS #2, 3, & 4 FROM THE 1ST REVIEW STILL EXIST. |
| | I HAVE PRINTED THEM BELOW WITH SOME ADDITIONAL NOTES- |
| | PLEASE COMPLY. |
| | |
| | 2) SPACE HEATING SYSTEMS ARE REQUIRED FOR THE SUITES |
| | PER SECTION 309.1 FBC -14 MECHANICAL. PLEASE INDICATE |
| | HOW COMPLIANCE IS BEING MET. (THE NEW AC EQUIPMENT |
| | SCHEDULE ON THE M1 PLAN DOESN'T INDICATE IF THE SYSTEMS |
| | PROVIDE HEAT, AND NO CUT SHEETS FOR THE SYSTEMS HAVE |
| | BEEN PROVIDED FOR CLARIFICATION). |
| | |
| | 3) VENTILATION IS REQUIRED FOR THE SUITES- EITHER |
| | NATURALLY OR MECHANICALLY- PER SECTION 401.2. PLEASE |
| | INDICATE HOW COMPLIANCE IS BEING MET. (THE PLAN APPEARS |
| | TO SHOW NATURAL VENTILATION. PLEASE SEE SECTION 402.2 |
| | AN PROVIDE CALCULATIONS TO INDICATE COMPLIANCE). |
| | |
| | 4) EXHAUST VENTILATION SYSTEMS ARE REQUIRED FOR BOTH |
| | THE KITCHENS AND THE BATHROOMS PER TABLE 403.3. |
| | INDICATE HOW COMPLIANCE IS BEING MET. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |