| 2018-01-10 08:28:57 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHT.A-4 AND A-5 PLEASE SHOW GRAB BARS TO BE MEASURED |
| | TO THE TOP OF THE GRIPPING SURFACE. PER FBC PL 609.4 |
| | |
| | 2. SHOW DIMENSIONS FOR FBC ACC 604.7 DISPENSERS. |
| | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 |
| | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| | THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE |
| | DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48 |
| | INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND |
| | SHALL NOT BE LOCATED BEHIND GRAB BARS |
| | |
| | 3. PLEASE SHOW HOT AND COLD AND LABEL PIPING ON WATER |
| | RISER. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 4. BECAUSE OF THE AGE OF THE BUILDING AND THIS BEING A |
| | CHANGE OF OCCUPANCY THE SAFETY PIPING ON THE WATER |
| | HEATER WILL NEED TO BE BROUGHT UP TO CODE, THE T+P |
| | RELIEF VALVE AND DRAIN LINE AND THERMAL EXPANSION. PER |
| | FBC PL CH 504 AND 607.3 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |