| 2017-12-19 12:38:52 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) THE APPLCATIONSTATES THE PROPOSED WORK IS TO REPLACE |
| | THE KITCHEN CABINETS. SHEET A 1 - STATES THAT THE |
| | PROPOSED WORK IS A CHANGE OF OCCUPANCY FROM MOTEL TO |
| | MULTI- RESIDENTIAL. |
| | |
| | PER THE FLORIDA FIRE PREVENTION CODE IT IS FROM |
| | EXISTING HOTEL TO NEW APARTMENT OCCUPANCY |
| | |
| | PLEASE CLARIFY. |
| | |
| | |
| | |
| | 2) THERE IS A REFERENCE INDICATING A FIRE ALARM IS NOT |
| | REQUIRED PER THE FBC; HOWEVER, A FIRE ALARM IS REQUIRED |
| | PER THE FLORIDA FIRE PREVENTION CODE, NFPA 101, CHPATER |
| | 30, NEW APARTMENT BUILDINGS. YOUR PROJECT INDICATES 14 |
| | UNITS. |
| | |
| | 30.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| | 30.3.4.1 GENERAL. |
| | 30.3.4.1.1 APARTMENT BUILDINGS FOUR OR MORE STORIES IN |
| | HEIGHT OR WITH MORE THAN 11 DWELLING UNITS, OTHER THAN |
| | THOSE MEETING THE REQUIREMENTS OF 30.3.4.1.2, SHALL BE |
| | PROVIDED WITH A FIRE ALARM SYSTEM IN ACCORDANCE WITH |
| | SECTION 9.6, EXCEPT AS MODIFIED BY 30.3.4.2 THROUGH |
| | 30.3.4.5. |
| | |
| | HOWEVER, |
| | |
| | 30.3.4.1.2 A FIRE ALARM SYSTEM SHALL NOT BE REQUIRED IN |
| | BUILDINGS WHERE EACH DWELLING UNIT IS SEPARATED FROM |
| | OTHER CONTIGUOUS DWELLING UNITS BY FIRE BARRIERS (SEE |
| | SECTION 8.3) HAVING A MINIMUM 1-HOUR FIRE RESISTANCE |
| | RATING, AND WHERE EACH DWELLING UNIT HAS EITHER ITS OWN |
| | INDEPENDENT EXIT OR ITS OWN INDEPENDENT STAIRWAY OR |
| | RAMP DISCHARGING AT THE FINISHED GROUND LEVEL. |
| | |
| | PLEASE REVIEW, CORRECT OR JUSTIFY WITH DETAILS AND/OR A |
| | SIGNED AND SEALED ENGINEEER REVIEW OF THE CONSTRUCTION, |
| | THAT THE CODE REQUIREMENTS ARE PROVIDED FOR. |
| | |
| | |
| | |
| | |
| | 3) THERE IS A REFERENCE INDICATING A FIRE SPRINKLER |
| | SYSTEM IS NOT REQUIRED PER THE FBC; HOWEVER, A FIRE |
| | SPRINKLER SYSTEM IS REQUIRED PER THE FLORIDA FIRE |
| | PREVENTION CODE, NFPA 101, CHPATER 30, NEW APARTMENT |
| | BUILDINGS. |
| | |
| | 30.3.5 EXTINGUISHMENT REQUIREMENTS. |
| | 30.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY |
| | AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM |
| | INSTALLED IN ACCORDANCE WITH 30.3.5.2. |
| | |
| | 30.3.5.2 WHERE AN AUTOMATIC SPRINKLER SYSTEM IS |
| | INSTALLED, EITHER FOR TOTAL OR PARTIAL BUILDING |
| | COVERAGE, THE SYSTEM SHALL BE INSTALLED IN ACCORDANCE |
| | WITH SECTION 9.7, AS MODIFIED BY 30.3.5.3 AND 30.3.5.4. |
| | IN BUILDINGS FOUR OR FEWER STORIES ABOVE GRADE PLANE, |
| | SYSTEMS IN ACCORDANCE WITH NFPA 13R, STANDARD FOR THE |
| | INSTALLATION OF SPRINKLER SYSTEMS IN LOW-RISE |
| | RESIDENTIAL OCCUPANCIES, SHALL BE PERMITTED. |
| | |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH ALL |
| | APPLICABLE FIRE CODE REFERENCES. |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | |