| Plan Review Notes For Permit 17120550 |
| Permit Number |
17120550 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2018-06-26 14:01:12 | 3RD REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES | | | PERMIT #17120550 | | | 6/26/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M1: AS NOTED IN THE PREVIOUS REVIEW, | | | MECHANICAL VENTILATION IS REQUIRED FOR THE BATHROOMS IN | | | ACCORDANCE WITH TABLE 403.3 FBC-14 MECHANICAL. THIS IS | | | A COMMERCIAL R2 OCCUPANCY, NOT A SINGLE FAMILY R3 | | | OCCUPANCY WHERE NATURAL VENTILATION OF BATHROOMS IS | | | ALLOWED PER THE FBC-14 RESIDENTIAL. PLEASE REVIEW THE | | | FOLLOWING CODES THAT ARE ALSO APPLICABLE TO THE | | | PROPOSED PROJECT: | | | | | | A) SECTION 1011.1 FBC-14 EXISTING BUILDING WHICH STATES | | | A CHANGE OF OCCUPANCY SHALL HAVE LIGHT AND VENTILATION | | | IN COMPLIANCE WITH THE FLORIDA BUILDING CODE. | | | | | | B) SECTION 1203.4.2.1 FBC-14 BUILDING WHICH STATES | | | BATHROOMS SHALL BE "MECHANICALLY VENTILATED". | | | | | | 2) M1: THE MODEL NUMBER AEE12DT LISTED IN SCHEDULE IS | | | NOT A FRIDGIDAIRE MODEL NUMBER. IT IS A GE NUMBER- | | | PLEASE CORRECT. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|