| 2017-12-27 14:23:36 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES | | | PERMIT #17120550 | | | 12/27/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE A SCOPE OF WORK FOR MECHANICAL | | | ALTERATIONS (IF APPLICABLE) WITH CORRESPONDING DRAWINGS | | | AND DETAILS- SECTION 1009.1 EXISTING BUILDING CODE. | | | | | | 2) SPACE HEATING SYSTEMS ARE REQUIRED FOR THE SUITES | | | PER SECTION 309.1 FBC -14 MECHANICAL. PLEASE INDICATE | | | HOW COMPLIANCE IS BEING MET. | | | | | | 3) VENTILATION IS REQUIRED FOR THE SUITES- EITHER | | | NATURALLY OR MECHANICALLY- PER SECTION 401.2. PLEASE | | | INDICATE HOW COMPLIANCE IS BEING MET. | | | | | | 4) EXHAUST VENTILATION SYSTEMS ARE REQUIRED FOR BOTH | | | THE KITCHENS AND THE BATHROOMS PER TABLE 403.3. | | | INDICATE HOW COMPLIANCE IS BEING MET. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|