| Plan Review Notes For Permit 17120517 |
| Permit Number |
17120517 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2018-06-25 14:18:52 | 3RD REVIEW FBC-2014 MECHANICAL | | | PERMIT #17120517 | | | 6/25/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) M-1: PROVIDE AN ENERGY COMPLIANCE REPORT FOR THE | | | CHANGE OF OCCUPANCY FROM FACTORY TO MERCANTILE, AND FOR | | | THE NEW ADDITIONS (THE CONVERTED LOADING DOCKS TO | | | CONDITIONED MERCANTILE SPACE ON THE EAST SIDE OF THE | | | BUILDING)- SEE SECTIONS C101.4.3 AND C101.4.4 FBC- 2014 | | | ENERGY CONSERVATION. | | | | | | 2) M-1: THE OUTDOOR AIR FAN INLET FOR THE NORTH | | | MERCANTILE SPACE ADDITION SHALL BE A MINIMUM 10 ' FROM | | | THE TRUCK PARKING AREA- SECTION 401.4(2) FBC-2014 | | | MECHANICAL. | | | | | | 3) M-1: THE 2326 CFMS OF TOTAL O/A IN THE SCHEDULE IS | | | INCORRECT. THE TOTAL SHOULD BE 2502 CFMS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|