2018-06-25 14:18:523RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17120517
 6/25/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) M-1: PROVIDE AN ENERGY COMPLIANCE REPORT FOR THE
 CHANGE OF OCCUPANCY FROM FACTORY TO MERCANTILE, AND FOR
 THE NEW ADDITIONS (THE CONVERTED LOADING DOCKS TO
 CONDITIONED MERCANTILE SPACE ON THE EAST SIDE OF THE
 BUILDING)- SEE SECTIONS C101.4.3 AND C101.4.4 FBC- 2014
 ENERGY CONSERVATION.
  
 2) M-1: THE OUTDOOR AIR FAN INLET FOR THE NORTH
 MERCANTILE SPACE ADDITION SHALL BE A MINIMUM 10 ' FROM
 THE TRUCK PARKING AREA- SECTION 401.4(2) FBC-2014
 MECHANICAL.
  
 3) M-1: THE 2326 CFMS OF TOTAL O/A IN THE SCHEDULE IS
 INCORRECT. THE TOTAL SHOULD BE 2502 CFMS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  