| Date |
Text |
| 2018-02-20 10:40:55 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY HAVE BEEN NOTED AS CORRECTED. ITEMS |
| | REMAINING HAVE FURTHER COMMENTS IN PARENTHESES. |
| | |
| | 1. CORRECTED. |
| | 2. CORRECTED. |
| | 3. RISER DIAGRAM SHOWS THE 600 AMP MAIN PANEL BEING FED |
| | WITH THREE 3/0 CONDUCTORS. CONDUCTOR SIZE 3/0 IS NOT |
| | RATED FOR 600 AMPS. ALSO, THIS IS SHOWN AS A 3 PHASE |
| | SERVICE, WHICH WOULD REQUIRE 4 WIRES FROM POWER |
| | COMPANY. AN EGC (EQUIPMENT GROUNDING CONDUCTOR) WOULD |
| | NOT BE INSTALLED IN THIS CONDUIT. PROVIDE CORRECTIONS |
| | NEC 310.15(B)(16), 250.6; FBC 107.2.1 (RISER NOW SHOWS |
| | (4) 1000 KCMIL WIRES IN A 3" CONDUIT. THIS QUANTITY AND |
| | SIZE OF WIRE WILL NOT FIT IN A 3" CONDUIT PER CODE. |
| | PROVIDE CORRECTION. NEC INFORMATIVE ANNEX C) |
| | 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 (NOT PROVIDED AS STATED IN LETTER) |
| | 5. CORRECTED. |
| | 6. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER |
| | ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE |
| | CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH |
| | CODE. THIS SHOULD BE EXPRESSED IN LIGHT FIXTURE WATTAGE |
| | IN RELATION TO SQUARE FOOT WATTAGE PERMITTED. IT HAS |
| | NOTHING TO DO WITH THE AMPACITY OF THE CIRCUIT FEEDING |
| | THE LIGHTING. FBC EC 405.5.2 (NOT PROVIDED. THIS |
| | CHART/GRAPH SHOULD INDICATE THE AMOUNT OF WATTAGE |
| | ALLOWED FOR THE SPACE AND THE AMOUNT DESIGNED FOR THE |
| | SPACE MEETING CODE REQUIREMENTS.) |
| | 7. PROVIDE LIGHT FIXTURE SCHEDULE. FBC 107.2.1 (NOT |
| | PROVIDED AS STATED IN LETTER) |
| | 8. CORRECTED. |
| | 9. COMPLIED. |
| | 10. CORRECTED. |
| | 11. CORRECTED. |
| | 12. CORRECTED. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |