| 2018-01-02 13:38:39 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. LOAD CALCULATION PROVIDED USES DEMAND FACTORS FOR A |
| | RESTAURANT, WHICH IS NOT PERMITTED FOR THIS PROJECT. |
| | PROVIDE ACCURATE LOAD CALCULATION PER NEC. NEC 220 |
| | 2. MAIN PANEL SHOWS TWO 200 AMP BREAKERS, ONE FEEDING |
| | PANEL A AND ONE FEEDING PANEL B. THE RISER DIAGRAM |
| | SHOWS THAT THESE PANELS ARE FED WITH CONDUCTOR SIZE |
| | 1/0. CONDUCTOR SIZE 1/0 IS NOT RATED FOR 200 AMPS. |
| | PROVIDE CORRECTION. NEC 310.15(B)(16) |
| | 3. RISER DIAGRAM SHOWS THE 600 AMP MAIN PANEL BEING FED |
| | WITH THREE 3/0 CONDUCTORS. CONDUCTOR SIZE 3/0 IS NOT |
| | RATED FOR 600 AMPS. ALSO, THIS IS SHOWN AS A 3 PHASE |
| | SERVICE, WHICH WOULD REQUIRE 4 WIRES FROM POWER |
| | COMPANY. AN EGC (EQUIPMENT GROUNDING CONDUCTOR) WOULD |
| | NOT BE INSTALLED IN THIS CONDUIT. PROVIDE CORRECTIONS |
| | NEC 310.15(B)(16), 250.6; FBC 107.2.1 |
| | 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | 5. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED |
| | IN THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW THE |
| | AUTOMATIC CONTROL REQUIRED, INCLUDING EXTERIOR AREAS. |
| | FBC EC 405.2.2, 405.2.2.2, 405.2.4 |
| | 6. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER |
| | ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE |
| | CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH |
| | CODE. THIS SHOULD BE EXPRESSED IN LIGHT FIXTURE WATTAGE |
| | IN RELATION TO SQUARE FOOT WATTAGE PERMITTED. IT HAS |
| | NOTHING TO DO WITH THE AMPACITY OF THE CIRCUIT FEEDING |
| | THE LIGHTING. FBC EC 405.5.2 |
| | 7. PROVIDE LIGHT FIXTURE SCHEDULE. FBC 107.2.1 |
| | 8. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1: |
| | 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE |
| | AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL |
| | 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE |
| | OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR |
| | PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS, |
| | CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE |
| | 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR |
| | FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC |
| | EC 405.7.1 |
| | 9. PROVIDE CONNECTION TO ALL GROUNDING ELECTRODES |
| | PRESENT AT BUILDING. NEC 250.50 |
| | 10. PER THE WPB AMENDMENTS TO THE FBC, 107.2.1.4 |
| | QUALITY OF BUILDING PLANS. BUILDING PLANS SHALL BE |
| | DRAWN TO A MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL |
| | PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. THIS POLICY |
| | MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE, |
| | CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS |
| | MANAGEMENT. PROVIDE CORRECTION. |
| | 11. PROVIDE SHOW WINDOW OUTLETS PER CODE. NEC 210.62 |
| | 12. PROVIDE DEDICATED SIGN CIRCUIT WITH AUTOMATIC |
| | CONTROL. NEC 600.5; FBC EC 405.2.4 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |