| 2017-12-20 17:44:04 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17120517/ CHANGE OF OCCUPANCY |
| | ADD: 925 N. RAILROAD AVE. (PCN: |
| | 74-43-43-15-20-005-0110) |
| | CONT: FLORIDA GENERAL CONTRACTOR |
| | TEL: 561-704-5042 |
| | E-MAIL: JIG3684@ YAHOO.COM |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. DEC. 20/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE CORRECT THE PERMIT AND PLAN ADDRESS. THE |
| | ADDRESS INDICATED ON BOTH THE PLANS AND PERMIT |
| | APPLICATION INDICATE 925 N RAILROAD AVE. PCN: |
| | 74-43-43-15-20-005-0110. THE LOCATION OF THE BUILDING |
| | SHOWN ON SHEET C-1 IS LOCATED AT THE ADDRESS 1013 N. |
| | RAILROAD AVE. PCN: 74-43-43-15-20-005-0090. PLEASE |
| | CORRECT THE ADDRESS ON THE PERMIT APPLICATION AND |
| | PLANS. SHEET C-1 SHOWS THE SITE AS ONE PROPERTY, |
| | WHEREAS THERE IS 3 LOTS AND 3 ADDRESSES. |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED. |
| | |
| | 2014 FBC-B 01.2 ADDRESS IDENTIFICATION. NEW AND |
| | EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED |
| | ADDRESS IDENTIFICATION. |
| | |
| | 2A) DISCREPANCY IN AREA. SHEET C1 INDICATES THE SQUARE |
| | FOOT AREA OF THIS BUILDING AS 11,800 SQ. FT. IN |
| | MULTIPLE AREAS, WHEREAS THE PALM BEACH COUNTY PROPERTY |
| | APPRAISERS OFFICE SHOWS 6525 SQ. FT. OF WAREHOUSE, 715 |
| | SQ. FT. OF OFFICE AND A 2ND AREA OF WAREHOUSE OF 360 |
| | SQ. FT. FOR A TOTAL OF 7600 SQ. FT. DISCREPANCY IN |
| | SQUARE FEET. 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 2B) DISCREPANCY IN AREA. SHEET C1 UNDER THE HEADING OF |
| | OCCUPANT LOAD INDICATES THE SQUARE FOOT AREA OF THIS |
| | BUILDING AS 8442 SQ. FEET, WHEREAS THE PALM BEACH |
| | COUNTY PROPERTY APPRAISERS OFFICE SHOWS 6525 SQ. FT. OF |
| | WAREHOUSE, 715 SQ. FT. OF OFFICE AND A 2ND AREA OF |
| | WAREHOUSE OF 360 SQ. FT. FOR A TOTAL OF 7600 SQ. FT. |
| | DISCREPANCY IN SQUARE FEET. 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 3) SHEET C1 THE COVERSHEET UNDER THE HEADING OF PROJECT |
| | DATA & OCCUPANT LOAD DOES NOT LIST TO WHAT CODE THIS |
| | PLAN WAS DESIGNED, NOR DOES THE PLAN INDICATE |
| | COMPLIANCE WITH THE REQUIREMENTS OF THE 2014 EXISTING |
| | BUILDING CODE CHAPTER 10 FOR CHANGE IN OCCUPANCY. THE |
| | 2014 FLORIDA BUILDING CODE AND EXISTING BUILDING CODE |
| | WAS ENACTED STATEWIDE ON JUNE 30/ 2015. |
| | |
| | 4) 2014 FBC-EXISTING BUILDING CODE 1001.3 CHANGE OF |
| | OCCUPANCY CLASSIFICATION. WHERE THE OCCUPANCY |
| | CLASSIFICATION OF A BUILDING CHANGES, THE PROVISIONS OF |
| | SECTIONS 1002 THROUGH 1012 SHALL APPLY. THIS INCLUDES A |
| | CHANGE OF OCCUPANCY CLASSIFICATION WITHIN A GROUP AS |
| | WELL AS A CHANGE OF OCCUPANCY CLASSIFICATION FROM ONE |
| | GROUP TO A DIFFERENT GROUP. |
| | |
| | 5) SHEET A-1 TOWARD THE SOUTH SIDE OF THE BUILDING THE |
| | PLANS STATE THAT THERE IS AN EXISTING 2 HOUR, 8 INCH |
| | CMU FIRE SEPARATION WALL TO REMAIN, EXISTING ADJACENT |
| | PROPERTY COURTYARD. PLEASE NOTE THE PALM BEACH COUNTY |
| | PROPERTY APPRAISERS ARIELS SHOW THE PROPERTY LINE JUST |
| | ADJACENT TO THE 2 HOUR RATED EXTERIOR WALL. |
| | THIS MEANS THE SOUTH EXIT, ELEVATED DECK, LOADING DOCK |
| | AND PROPOSED NEW ADA LIFT IS ON A DIFFERENT LOT, |
| | PCN: 74-43-43-15-20-005-0110 ADDRESSED 925 N. RAILROAD |
| | AVE. IT WOULD APPEAR A UNITY OF TITLE WOULD BE REQUIRED |
| | TO ALLOW FOR OPENINGS IN THE SOUTH WALL AND ALLOWING |
| | EXITING ONTO THE LOT ADDRESSED 925 N. RAILROAD AVE. |
| | |
| | UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE |
| | TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS |
| | WHICH COMBINE TO FORM 'THE SITE'. A 'UNITY OF TITLE' |
| | SHALL BE RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A |
| | COPY OF THE RECORDED 'UNITY OF TITLE' DOCUMENT SO THAT |
| | FBC TABLE 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED |
| | NOT APPLICABLE. |
| | SEE WEBSITE FOR APPLICATION: |
| | HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP |
| | "APPLICATION FOR UNITY OF TITLE" |
| | HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45 |
| | -38-UNITYOFTITLE3.PDF |
| | VINCENT J NOEL |
| | SURVEYOR/REAL ESTATE SUPERVISOR |
| | ENGINEERING SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH, FL 33401 |
| | PHONE: 494-1040 EXT: 1096 |
| | FAX: 494-1116 |
| | E-MAIL: [email protected] |
| | ********************************************* |
| | MANUEL JULIAN GONZALEZ |
| | ENGINEERING PROJECT COORDINATOR |
| | ENGINEERING SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET, 4TH FLOOR |
| | WEST PALM BEACH, FL 33401 |
| | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) |
| | MAIN PHONE: (561) 822-1200 |
| | DIRECT: (561) 494-1085 |
| | FAX: (561) 494-1116 |
| | MOBILE: (561) 644-7301 |
| | EMAIL: [email protected] |
| | |
| | 6) NETHER SHEET A-1 NOR A-2 PROVIDE WHAT IS EXISTING |
| | AND WHAT IS NEW. PLEASE BE ADVISED GOOGLE STREET VIEW |
| | IN FEB. OF 2015 SHOWS THE 4 LOADING BAYS OPEN ALONG N. |
| | RAILROAD AVE. FOR 925 AND 1013 N. RAILROAD AVE. WITHIN |
| | THE LOADING BAYS THERE IS ONLY ONE EXISTING SET OF |
| | STAIR AND NO GUARDRAILS. THE OTHER ISSUE IS HOW THE |
| | BUILDINGS ARE BUILT BETWEEN 925 AND 1013 N. RAILROAD |
| | AVE. THERE WOULD HAVE BEEN A 4 HOUR FIRE WALL |
| | SEPARATING THE BUILDINGS, WE DO NOT HAVE PERMITS PULLED |
| | CREATING OPENINGS WITHIN THE 4 HOUR FIRE WALL NOR HOW |
| | THE STRUCTURE ABOVE IS BEING SUPPORTED? IT WOULD APPEAR |
| | THERE HAS BEEN A LOT OF WORK ALREADY COMPLETED WITHOUT |
| | THE BENEFIT OF A PERMIT. A THOROUGH REVIEW CANNOT BE |
| | MADE AT THIS TIME, AS A RESULT OF THE ADDITIONAL |
| | INFORMATION REQUESTED ADDITIONAL COMMENTS MAY APPEAR |
| | THAT WERE NOT PART OF THIS REVIEW. WORK COMPLETED |
| | WITHOUT THE BENEFIT OF A PERMIT MAY ALSO RESULT IN A 4X |
| | FEE FOR THE WORK NOT PERMITTED. |
| | 7) SHEET A-1 SHOWS THE EXIT ACCESS PATHS THROUGHOUT THE |
| | BUILDING BUT THE TRAVEL DISTANCE FOR EACH ROUTE HAS NOT |
| | BEEN INDICATED ON THE PLANS, PLEASE SHOW COMPLIANCE |
| | WITH 2014 FBC-B TABLE 1016.2. |
| | |
| | 8) THE COVERSHEET INDICATES THE OCCUPANT LOAD OF 302 |
| | AND SHEET A-1 SHOWS 2 EXITS AND ONLY 1 ACCESSIBLE EXIT. |
| | PLEASE REVIEW SECTION: |
| | |
| | 2014 FBC-EXISTING BUILDING CODE 1012.8 ACCESSIBILITY. |
| | EXISTING BUILDINGS THAT UNDERGO A CHANGE OF GROUP OR |
| | OCCUPANCY CLASSIFICATION SHALL COMPLY WITH THE |
| | PROVISIONS OF THE FLORIDA BUILDING CODE, ACCESSIBILITY. |
| | |
| | 2014 ACCESS. CODE 206.4.1 PUBLIC ENTRANCES. IN ADDITION |
| | TO ENTRANCES REQUIRED BY 206.4.2 THROUGH 206.4.9, AT |
| | LEAST 60 PERCENT OF ALL PUBLIC ENTRANCES SHALL COMPLY |
| | WITH 404. |
| | |
| | (GRAY BOX FLORIDA SPECIFIC). BARRIERS AT COMMON OR |
| | EMERGENCY ENTRANCES AND EXITS OF BUSINESS |
| | ESTABLISHMENTS CONDUCTING BUSINESS WITH THE GENERAL |
| | PUBLIC THAT ARE EXISTING, UNDER CONSTRUCTION, OR UNDER |
| | CONTRACT FOR CONSTRUCTION WHICH WOULD PREVENT A PERSON |
| | FROM USING SUCH ENTRANCES OR EXITS SHALL BE REMOVED. |
| | |
| | 9) SHEET A-1 INDICATES THE USE OF (2) NEW LIFTS, PLEASE |
| | BE MORE SPECIFIC, TO BE LIMITED USE/ LIMITED- |
| | APPLICATION UNDER SECTION 408 OF THE ACCESSIBILITY CODE |
| | COMPLYING WITH ASME A17.1 OR PLATFORM LIFTS UNDER |
| | SECTION 410 OF THE ACCESSIBILITY CODE COMPLYING WITH |
| | ASME A18.1. PLEASE PROVIDE THE MANUFACTURERS |
| | SPECIFICATION AND INSTALLATION INSTRUCTIONS. |
| | |
| | 10) SHEET A-1 SHOWS THE LIFE SAFETY PLAN, PLEASE |
| | PROVIDE A FLOOR PLAN WITH ACTUAL LAYOUT OF ARTWORK, |
| | FURNITURE, TEMPORARY PARTITIONS FOR HANGING ART WORK |
| | AND OR KIOSK SHOW TRAVEL DISTANCES, AND COMMON PATH OF |
| | TRAVEL IT WOULD APPEAR THERE MAYBE ISSUES WITH COMMON |
| | PATH OF TRAVEL FROM THE NORTHWEST CORNER OF THE |
| | BUILDING. 2014 FBC-B TABLE 1014.3 AND TABLE 1016.2. |
| | |
| | 11) SHEET A-1 THE ELEVATED MERCANTILE ART AREA ONLY |
| | SHOWS ONE MEANS OF EGRESS. FBC-B TABLE 1015.1 REQUIRES |
| | 2 MEANS OF EGRESS WHEN THE OCCUPANT LOAD IS 50 OR MORE |
| | OCCUPANTS. ALTHOUGH THE ENTRY DOOR FROM NORTH RAILROAD |
| | AVENUE WOULD BE THE 2ND MEANS OF EGRESS, TO LEAVE FROM |
| | THE ELEVATED MERCANTILE ART AREA, ONE WOULD HAVE TO |
| | TRAVEL THROUGH THE DOUBLE DOORS AND THROUGH THE OFFICE |
| | AREA AND OUT THE EXIT DOOR ONTO THE SIDEWALK AT NORTH |
| | RAILROAD AVENUE. |
| | |
| | 11A) THE DOUBLE DOORS AT THE OFFICE WOULD HAVE TO BE |
| | SWUNG AROUND TO COMPLY WITH 1008.1.2, DOORS SHALL SWING |
| | IN THE DIRECTION OF EGRESS TRAVEL WHEN THE OCCUPANT |
| | LOAD IS GREATER THAN 49. |
| | |
| | 11B) PLEASE PROVIDE THE DIFFERENCE IN HEIGHT BETWEEN |
| | THE CITY SIDEWALK AND THE BOTTOM LANDING OF THE |
| | STAIRWAY, THIS NEEDS TO BE PART OF AN ACCESSIBLE |
| | ENTRANCE/ EXIT. 2014 ACCESS. CODE 206.4.1 PUBLIC |
| | ENTRANCES. IN ADDITION TO ENTRANCES REQUIRED BY 206.4.2 |
| | THROUGH 206.4.9, AT LEAST 60 PERCENT OF ALL PUBLIC |
| | ENTRANCES SHALL COMPLY WITH 404. |
| | THE PICTURES FROM GOOGLE STREET VIEW OF FEB. 2015 IT |
| | WOULD APPEAR THERE IS AT LEAST A 4 INCH DIFFERENCE IN |
| | HEIGHT FROM THE CITY SIDEWALK TO THE ENTRY DOOR FLOOR |
| | LEVEL. |
| | |
| | 10C) NOTICE ONLY!!!! PLEASE NOTE THE EGRESS DOOR THAT |
| | OPENS ONTO NORTH RAILROAD AVENUE IS AN EXISTING |
| | NON-CONFORMING DOORWAY THAT SWINGS OUT OVER THE PUBLIC |
| | SIDEWALK, NOTE IF THE DOOR IS NOT REPLACED IT DOES NOT |
| | NEED TO BE REPLACED, BUT WHEN THE DOOR AND JAMB ARE |
| | REPLACED IT WILL STILL NEED TO SWING OUT BUT RECESSED |
| | BACK IN AN ALCOVE. |
| | 2014 FBC-B 3202.2 ENCROACHMENTS ABOVE GRADE AND BELOW 8 |
| | FEET IN HEIGHT. ENCROACHMENTS INTO THE PUBLIC |
| | RIGHT-OF-WAY ABOVE GRADE AND BELOW 8 FEET (2438 MM) IN |
| | HEIGHT SHALL BE PROHIBITED EXCEPT AS PROVIDED FOR IN |
| | SECTIONS 3202.2.1 THROUGH 3202.2.3. DOORS AND WINDOWS |
| | SHALL NOT OPEN OR PROJECT INTO THE PUBLIC RIGHT-OF-WAY. |
| | |
| | 10D) GOOGLE STREET VIEW OF FEB. 2015 SHOWS THE N. |
| | RAILROAD ENTRY DOOR, IT SEEMS TO BE NARROW, PLEASE |
| | PROVIDE HOW WIDE THIS DOOR ACTUALLY IS. 2014 FBC-B |
| | 1008.1.1 SIZE OF DOORS. THE MINIMUM WIDTH OF EACH DOOR |
| | OPENING SHALL BE SUFFICIENT FOR THE OCCUPANT LOAD |
| | THEREOF AND SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES. |
| | CLEAR OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE |
| | MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP, |
| | WITH THE DOOR OPEN 90 DEGREES. |
| | |
| | 10E) IN THE GOOGLE STREET VIEW SHOOT IN FEB. 2015 |
| | PLEASE ALSO NOTE THE GARAGE DOORS ARE STILL IN THE |
| | OPENINGS AT THE LOADING BAYS, HOW CAN THE SUPPOSED |
| | EXISTING GUARDRAILS BE EXISTING? 107.2.1.3 ADDITIONAL |
| | INFORMATION WILL BE REQUIRED. |
| | |
| | 11) SHEET A1 & A2 BOTH WILL NEED TO SHOW COMPLIANCE |
| | WITH HANDRAILS AND GUARDRAILS MEETING ALL (3) SECTIONS |
| | OF CODE. |
| | 2014 FBC-B 1607.8.1 HANDRAILS AND GUARDS. |
| | HANDRAILS AND GUARDS SHALL BE DESIGNED TO RESIST A |
| | LINEAR LOAD OF 50 POUNDS PER LINEAR FOOT (PLF) IN |
| | ACCORDANCE WITH SECTION 4.5.1 OF ASCE 7. GLASS HANDRAIL |
| | ASSEMBLIES AND GUARDS SHALL ALSO COMPLY WITH SECTION |
| | 2407. |
| | |
| | 11A) 2014 FBC-B 1607.8.1.1 CONCENTRATED LOAD. HANDRAILS |
| | AND GUARDS SHALL ALSO BE DESIGNED TO RESIST A |
| | CONCENTRATED LOAD OF 200 POUNDS IN ACCORDANCE WITH |
| | SECTION 4.5.1 OF ASCE 7. |
| | |
| | 11B) 2014 FBC-B 1607.8.1.2 INTERMEDIATE RAILS. |
| | INTERMEDIATE RAILS (ALL THOSE EXCEPT THE HANDRAIL), |
| | BALUSTERS AND PANEL FILLERS SHALL BE DESIGNED TO RESIST |
| | A CONCENTRATED LOAD OF 50 POUNDS IN ACCORDANCE WITH |
| | SECTION 4.5.1 OF ASCE 7. |
| | |
| | 11C) PLEASE DO NOT RESTATE THE CODE, BUT PROVIDE |
| | CALCULATIONS. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. SUCH INFORMATION SHALL BE SPECIFIC, AND THE |
| | TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE OR IN |
| | PART, NOR SHALL THE TERM "LEGAL" OR ITS EQUIVALENT BE |
| | USED AS A SUBSTITUTE FOR SPECIFIC INFORMATION. ALL |
| | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING |
| | DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN. (SEE ALSO SECTION 107.3.5). |
| | |
| | 11D) SHEETS A1 AND A2 DOESN?T SHOW A HANDRAIL FOR ANY |
| | OF THE EXISTING STAIRS OR FOR THE EXISTING (PROPOSED) |
| | STAIRS. 805.9 HANDRAILS. EXISTING BUILDING CODE. THE |
| | REQUIREMENTS OF SECTIONS 805.9.1 AND 805.9.2 SHALL |
| | APPLY TO HANDRAILS FROM THE WORK AREA FLOOR TO, AND |
| | INCLUDING, THE LEVEL OF EXIT DISCHARGE. |
| | |
| | 11D)(1) 805.9.1 MINIMUM REQUIREMENT. EVERY REQUIRED |
| | EXIT STAIRWAY THAT IS PART OF THE MEANS OF EGRESS FOR |
| | ANY WORK AREA AND THAT HAS THREE OR MORE RISERS AND IS |
| | NOT PROVIDED WITH AT LEAST ONE HANDRAIL, OR IN WHICH |
| | THE EXISTING HANDRAILS ARE JUDGED TO BE IN DANGER OF |
| | COLLAPSING, SHALL BE PROVIDED WITH HANDRAILS FOR THE |
| | FULL LENGTH OF THE RUN OF STEPS ON AT LEAST ONE SIDE. |
| | ALL EXIT STAIRWAYS WITH A REQUIRED EGRESS WIDTH OF MORE |
| | THAN 66 INCHES (1676 MM) SHALL HAVE HANDRAILS ON BOTH |
| | SIDES. |
| | |
| | 11D)(2) 805.9.2 DESIGN. HANDRAILS REQUIRED IN |
| | ACCORDANCE WITH SECTION 805.9.1 SHALL BE DESIGNED AND |
| | INSTALLED IN ACCORDANCE WITH THE PROVISIONS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 12) THE PERMIT VALUE IS VERY LOW FOR THE WORK SHOWN ON |
| | THE PLANS AS WELL AS THE WORK THAT WAS DONE WITHOUT A |
| | PERMIT. |
| | |
| | 108.3* BUILDING PERMIT VALUATION. IF, IN THE OPINION OF |
| | THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF |
| | BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, |
| | MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE UNDER |
| | ESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| | DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| | AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL |
| | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL, |
| | PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE |
| | WORK (EXCAVATION AND BACKFILL FOR BUILDINGS), |
| | ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD |
| | AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION |
| | REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF |
| | NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE |
| | MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS. |
| | WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING |
| | PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE |
| | QUALIFIER AND OWNER AND BRINGS IN THE LISTED |
| | SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE |
| | QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND |
| | LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE |
| | FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN |
| | LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR |
| | EACH PERMIT. |
| | |
| | ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK |
| | STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE |
| | AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS & |
| | FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL |
| | TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED |
| | SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, |
| | LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR |
| | FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE |
| | REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT. |
| | PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE |
| | ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE |
| | STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE |
| | REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE |
| | BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE |
| | BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR |
| | THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE |
| | PRIME OR MASTER PERMIT. |
| | |
| | 13) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF |
| | PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR |
| | REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE |
| | OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST |
| | PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE |
| | STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL |
| | (561)233-5025 FOR MORE INFORMATION. |
| | |
| | 14) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |