 2ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE GREASE INTERCEPTOR SIZING CALCULATIONS SHALL
 INCLUDE ALL THE FLOOR DRAINS, FLOOR SINKS, TROUGH
 DRAINS AND HUBDRAINS RECEIVING DISCHARGE OF GREASY
 WASTE SUCH AS THE KETTLE.AND HOT WELLS OR USE THE
 SIZING METHOD FOR RESTAURANT USING THE NUMBER OF SEATS
 X GALLONS PER SEAT X HR OF OPERATION X LOAD FACTOR. PER
 FBC PL 1003.2, 1003.3.1
  
 2. ON THE WATER RISER SHUT OFF VALVES ARE REQUIRED ON
 ALL DROPS A NOTE ON THE PLAN SHALL COMPLY. PER FBC PL
 606.1(5)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  