Plan Review Notes
Plan Review Notes For Permit 17120495
Permit Number 17120495
Review Stop M
Sequence Number 2
Notes
Date Text
2018-02-28 10:22:582ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17120495
 2/28/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.1 COMBUSTION AIR CALCULATION: PLEASE REFER
 TO SHEETS CS1 AND A1.3. BASED ON THE 3520 SQ. FT. AREA
 AND AN AVERAGE CEILING HEIGHT OF 9'6" THE MAXIMUM
 VOLUME OF THE SPACE IN CUBIC FEET WOULD BE 33,440. THAT
 TOTAL WOULD ALSO BE CUT DRASTICALLY WHEN DEDUCTING
 CLOSED OFF SPACES SUCH AS THE RESTROOMS, STORAGE, AND
 OFFICE ROOMS ETC. HOW ARE YOU CALCULATING THE
  
 INDOOR VOLUME AT 46.392 FT3. IT DOES NOT SEEM
 PHYSICALLY POSSIBLE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  