| Plan Review Notes For Permit 17120495 |
| Permit Number |
17120495 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-02-28 10:22:58 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17120495 | | | 2/28/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M1.1 COMBUSTION AIR CALCULATION: PLEASE REFER | | | TO SHEETS CS1 AND A1.3. BASED ON THE 3520 SQ. FT. AREA | | | AND AN AVERAGE CEILING HEIGHT OF 9'6" THE MAXIMUM | | | VOLUME OF THE SPACE IN CUBIC FEET WOULD BE 33,440. THAT | | | TOTAL WOULD ALSO BE CUT DRASTICALLY WHEN DEDUCTING | | | CLOSED OFF SPACES SUCH AS THE RESTROOMS, STORAGE, AND | | | OFFICE ROOMS ETC. HOW ARE YOU CALCULATING THE | | | | | | INDOOR VOLUME AT 46.392 FT3. IT DOES NOT SEEM | | | PHYSICALLY POSSIBLE. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|