| Plan Review Notes For Permit 17120495 |
| Permit Number |
17120495 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-03-08 12:35:56 | 2ND REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. THE BTU LOAD FOR THE FRYER DOES NOT MATCH , ON THE | | | COMBUSTION AIR CALCS IT LIST 330 MBTU ON THE RISER IT | | | LIST 360 MBTU.PLEASE CLARIFY PER WPB AMEND TO FBC | | | 107.2.1 | | | | | | 2. THE RISER AND EQUIPMENT SCHEDULE LIST THE CONVECTION | | | OVEN AT 100 MBTU THE MANUFACTURE SPECS LIST 88 MBTU. | | | PLEASE CLARIFY PER WPB AMEND TO FBC 107.2.1 | | | | | | 3. THE RISER AND EQUIPMENT SCHEDULE LIST THE1 FRYER AT | | | 360 MBTU THE MANUFACTURE SPECS LIST MODEL SG14 AT110 | | | MBTU.PLEASE CLARIFY PER WPB AMEND TO FBC 107.2 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|