2018-03-08 12:35:562ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE BTU LOAD FOR THE FRYER DOES NOT MATCH , ON THE
 COMBUSTION AIR CALCS IT LIST 330 MBTU ON THE RISER IT
 LIST 360 MBTU.PLEASE CLARIFY PER WPB AMEND TO FBC
 107.2.1
  
 2. THE RISER AND EQUIPMENT SCHEDULE LIST THE CONVECTION
 OVEN AT 100 MBTU THE MANUFACTURE SPECS LIST 88 MBTU.
 PLEASE CLARIFY PER WPB AMEND TO FBC 107.2.1
  
 3. THE RISER AND EQUIPMENT SCHEDULE LIST THE1 FRYER AT
 360 MBTU THE MANUFACTURE SPECS LIST MODEL SG14 AT110
 MBTU.PLEASE CLARIFY PER WPB AMEND TO FBC 107.2
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  