2018-01-08 15:12:061ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE IF MEASURED TO CENTERLINE OF BAR TO
 THE MAX OF 36" BARS WILL BE INSTALLED TO HIGH. PER FBC
 ACC 609.4
  
 2. SHT. A7.1-7.2 DETAILS SHOWS HORIZONTAL GRAB BARS PER
 FBC ACC 909.4 GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION,
  
 3. SHT. P1.1 SHOWS 3 GREASE INTERCEPTORS THE APPROVED
 PLANS FOR BUILDING SHELL SHOW FOUR GREASE INTERCEPTORS
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 4. THE SANITARY ISOMETRIC IS TO COMPACT TO DETERMINE
 CODE COMPLIANCE PLEASE EXPAND AND SEPARATE THE SANITARY
 AND GREASE ISOMETRIC DRAWINGS. PER WPB AMEND TO FBC
 107.2.1
  
 5. PROVIDE WATER ISOMETRIC SHOWING PIPE SIZE, ALL
 VALVES, HAMMER ARESTORS AND BACK FLOWS. PER WPB AMEND
 TO FBC 107.3.5.1.3(13)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  