| 2017-12-27 12:57:31 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17120495 | | | 12/27/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) DUE TO THE LOW WALLS SEPARATING THE KITCHEN AND THE | | | DINING ROOMS, IT APPEARS THAT SOME OF THE AIR SUPPLIED | | | TO THE KIITCHEN WILL BE RECIRCULATED INTO THE DINING | | | ROOM WHICH IS PROHIBITED- TABLE 403.3 FOOTNOTE B. | | | | | | 2) PROVIDE COMBUSTION FOR THE COOKING APPLIANCES AND | | | SHOW HOW THE AIR WILL BE PROVIDED- SEE SECTION 304 | | | FBC-14 FUEL GAS. | | | | | | 3) SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN HOODS, | | | THE FIRE SUPPRESSION SYSTEMS, AND THE WALK-IN COOLER | | | AND FREEZER. PLEASE PLACE A NOTE ON THE PLAN. | | | | | | ADVISORY- KITCHEN HOOD PLANS: COMPLIANCE WITH SECTION | | | 508.1.1 MAKEUP AIR TEMPERATURE WILL BE REQUIRED. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|