Plan Review Notes
Plan Review Notes For Permit 17120495
Permit Number 17120495
Review Stop M
Sequence Number 1
Notes
Date Text
2017-12-27 12:57:311ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17120495
 12/27/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) DUE TO THE LOW WALLS SEPARATING THE KITCHEN AND THE
 DINING ROOMS, IT APPEARS THAT SOME OF THE AIR SUPPLIED
 TO THE KIITCHEN WILL BE RECIRCULATED INTO THE DINING
 ROOM WHICH IS PROHIBITED- TABLE 403.3 FOOTNOTE B.
  
 2) PROVIDE COMBUSTION FOR THE COOKING APPLIANCES AND
 SHOW HOW THE AIR WILL BE PROVIDED- SEE SECTION 304
 FBC-14 FUEL GAS.
  
 3) SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN HOODS,
 THE FIRE SUPPRESSION SYSTEMS, AND THE WALK-IN COOLER
 AND FREEZER. PLEASE PLACE A NOTE ON THE PLAN.
  
 ADVISORY- KITCHEN HOOD PLANS: COMPLIANCE WITH SECTION
 508.1.1 MAKEUP AIR TEMPERATURE WILL BE REQUIRED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  