| 2018-01-02 15:49:24 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. SHEET EO.1, NOTE 10 REFERENCES NEC 250.95 FOR |
| | EQUIPMENT GROUNDING CONDUCTOR SIZE. THIS CODE SECTION |
| | DOES NOT EXIST IN THE 2011 NEC. PROVIDE CORRECTION. NEC |
| | 250.122; FBC 107.2.1 |
| | 2. RISER SHOWS AN EXISTING SERVICE, BUT THE PROPERTY |
| | APPRAISER'S SITE SHOWS THIS AS A VACANT LOT. WHAT IS |
| | EXISTING ON SITE? IF THIS IS FED FROM AN EXISTING |
| | SERVICE, PROVIDE LOAD CALCULATION FOR ENTIRE SERVICE. |
| | PROVIDE CLARIFICATION. NEC 220, FBC 107.2.1 |
| | 3. PROVIDE GROUNDING ELECTRODE SYSTEM AND CONDUCTORS |
| | PER CODE. PROVIDE DETAIL ON PLAN. NEC 250.50, 250.66; |
| | FBC 107.2.1 |
| | 4. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. NEC 250.94 |
| | 5. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| | LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| | SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS |
| | (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF |
| | THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE |
| | REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| | SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1, |
| | 107.2.1 |
| | 6. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | 7. IT APPEARS THAT THE PANEL SCHEDULES HAVE NOT BEEN |
| | COMPLETELY FILLED OUT. DOES PANEL A HAVE A MAIN |
| | BREAKER, OR WILL THERE BE A DISCONNECT OUTSIDE? PROVIDE |
| | CLARIFICATION. FBC 107.2.1; NEC 230.71 |
| | 8. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| | 9. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER |
| | ALLOWANCES EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE |
| | IN RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR |
| | LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC 405.5.2 |
| | 10. PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED |
| | IN THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW THE |
| | AUTOMATIC CONTROL REQUIRED. FBC EC 405.2.2, 405.2.2.2, |
| | 405.2.4 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |