| Plan Review Notes For Permit 17120442 |
| Permit Number |
17120442 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2018-01-16 12:28:37 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17120442 | | | 1/16/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE AC SYSTEM HAS BEEN CHANGED FROM A 2.5 TON TO A | | | 3.0 SYSTEM, HOWEVER THE PLAN IS INDICATING 1000 CFMS OF | | | SUPPLY AIR AND NOT 1200 CFMS AS THE NEW SCHEDULE SHOWS. | | | | | | 2) REVISE THE ENERGY COMPLIANCE FORM TO SHOW THE NEW | | | SYSTEM. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|