| 2017-12-16 11:47:03 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. THE APPROVED SET OF DRAWINGS WAS SIGNED AND SEALED |
| | BY DESIGN PROFESSIONAL ANY REVISIONS SHALL BE SIGNED |
| | AND SEALED BY THE SAME DESIGN PROFESSIONAL. PER WPB |
| | AMEND TO FBC 107.2 AND FS 61G15-23.003 |
| | |
| | 2. PLEASE PROVIDE REVISED FLOOR PLAN SHT. P.1. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 3. THE TOTAL DEVELOPED LENGTH IS STATED AS 18' YET THE |
| | LAST SECTION OF PIPE TO THE DRYER IS LABELED AS 18' |
| | PLEASE LABEL ALL SECTIONS OF PIPE INCLUDING THE FIRST |
| | SECTION FROM THE METER AND THEY SHALL MATCH THE TOTAL |
| | DEVELOPED LENGTH. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 4. INDICATE THE DELIVERY PRESSURE (PSI) AND TYPE OF |
| | GAS, (LP OR NATURAL).PER FBC-2014 FUEL GAS SEC. 402.2. |
| | IF NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | |
| | 5. PLEASE PROVIDE TABLE THAT WAS USED FOR SIZING |
| | SYSTEM. PER FBC FG 402.4 |
| | |
| | 6. SHOW SHUT OFF VALVE FOR COOK TOP ON THE BRANCH |
| | CONNECTING APPLIANCE. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 7. SHOW THE REQUIRED DIRT LEG ON THE SYSTEM. PER FBC FG |
| | 408.4 |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |