| Plan Review Notes For Permit 17120398 |
| Permit Number |
17120398 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-12-28 07:51:11 | 12/28/2017 1ST PLUMBING REVIEW**DENIED** | | | | | | 1) A SANITARY ISOMETRIC DRAWING IS REQUIRED FBC 107.2.1 | | | | | | 2) A WATER ISOMETRIC DRAWING IS REQUIRED FBC 107.2.1 | | | | | | 3) CITY RECORD SHOW THIS AS A BUSINESS OCCUPANCY. | | | PLEASE EXPLAIN THE PURPOSE FOR ADDING THESE SINKS FBC | | | 107.2.1. PLEASE BE ADVISED IF THERE IS TO BE ANY FOOD | | | COOKED OR SERVED THEN THIS WOUD BE A CHANGE OF | | | OCCUPANCY AND A FULL SET OF PLANS WOULD NEED TO BE | | | SUBMITTED SHOWING SUCH AND ALL ACCESSIBILTY WOULD NEED | | | TO BE BROUGHT UP TO CODE. ZONING WOULD NEED TO APPROVE | | | THE CHANGE OF OCCUPANCY FIRST. THIS PLAN REVIEWER HAS | | | CALL AND LEFT MESSAGE FOR THIS CONTRACTOR | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | |
|