| Plan Review Notes For Permit 17120353 |
| Permit Number |
17120353 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2018-02-28 12:08:25 | 3RD REVIEW FBC-2014 MECHANICAL | | | PERMIT #17120353 | | | 2/28/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE A REVISED OR CORRECTED AC EQUIPMENT SCHEDULE | | | ON THE PLAN TO CORRELATE WITH THE COMPLIANCE DATA FOR | | | THE SYSTEM SHOWN IN THE ENERGYGAUGE FORM. THE CURRENT | | | SCHEDULE ON THE PLAN HAS BEEN CROSSED OUT. | | | | | | 2) COMMENT #3 FROM THE PREVIOUS REVIEW STILL EXISTS. I | | | HAVE REPRINTED IT BELOW- PLEASE COMPLY. | | | | | | 3) M-1: THE AC LAYOUT PLAN IS INCOMPLETE: THE SIZE OF | | | THE MAIN TRUNK IS NOT SHOWN, AND ONLY 3- 200 CFM SUPPLY | | | DIFFUSERS ARE SHOWN WHICH INDICATES THE TOTAL SUPPLY | | | AIR IN THE SPACE AT 600 CFMS FOR THE 3-TON SYSTEM. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|