2018-02-28 12:08:253RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17120353
 2/28/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A REVISED OR CORRECTED AC EQUIPMENT SCHEDULE
 ON THE PLAN TO CORRELATE WITH THE COMPLIANCE DATA FOR
 THE SYSTEM SHOWN IN THE ENERGYGAUGE FORM. THE CURRENT
 SCHEDULE ON THE PLAN HAS BEEN CROSSED OUT.
  
 2) COMMENT #3 FROM THE PREVIOUS REVIEW STILL EXISTS. I
 HAVE REPRINTED IT BELOW- PLEASE COMPLY.
  
 3) M-1: THE AC LAYOUT PLAN IS INCOMPLETE: THE SIZE OF
 THE MAIN TRUNK IS NOT SHOWN, AND ONLY 3- 200 CFM SUPPLY
 DIFFUSERS ARE SHOWN WHICH INDICATES THE TOTAL SUPPLY
 AIR IN THE SPACE AT 600 CFMS FOR THE 3-TON SYSTEM.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  