| 2018-01-18 13:35:54 | ****PLAN REVIEW COMMENTS**** |
| | |
| | ART LANGE BUILDING PLANS EXAMINER |
| | |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH, FL 33402 |
| | |
| | 561-805-6718 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | SECOND PLAN REVIEW: |
| | |
| | OCCUPANY CLASSIFICATION OK. |
| | 1. OCCUPANCY SHOWN ON PLANS IS SHOWN AS B2. IF THIS WAS |
| | RETAIL PREVIOUSLY THIS WAS A B OCCUPANCY. NOW AS A |
| | RESTAURANT THE CURRENT OCCUPANCY CLASSIFICATION IS A-2 |
| | RESTAURANT. |
| | FBC 303.3 ASSEMBLY GROUP A-2. |
| | |
| | ASSEMBLY USES INTENDED FOR FOOD AND/OR DRINK |
| | CONSUMPTION INCLUDING, BUT NOT LIMITED TO: |
| | |
| | RESTAURANTS, CAFETERIAS AND SIMILAR DINING FACILITIES |
| | (INCLUDING ASSOCIATED COMMERCIAL KITCHENS). |
| | |
| | NOT ADDRESSED. |
| | A) SHOW COMPLIANCE FOR CHANGE OF USE WITH THE EXISTING |
| | BUILDING CODE [A] 101.2 SCOPE. |
| | THE PROVISIONS OF THE FLORIDA BUILDING CODE, EXISTING |
| | BUILDING SHALL APPLY TO THE REPAIR, ALTERATION, CHANGE |
| | OF OCCUPANCY, ADDITION AND RELOCATION OF EXISTING |
| | BUILDINGS. |
| | |
| | NOT ADDRESSED. |
| | B) CHANGE OF OCCUPANCY SHALL COMPLY WITH THE ENERGY |
| | CONSERVATION CODE. |
| | C101.4.8 EXEMPT BUILDINGS. |
| | |
| | BUILDINGS EXEMPT FROM THE PROVISIONS OF THE FLORIDA |
| | BUILDING CODE, ENERGY CONSERVATION, INCLUDE EXISTING |
| | BUILDINGS EXCEPT THOSE CONSIDERED RENOVATED BUILDINGS, |
| | CHANGES OF OCCUPANCY TYPE, OR PREVIOUSLY UNCONDITIONED |
| | BUILDINGS TO WHICH COMFORT CONDITIONING IS ADDED. |
| | EXEMPT BUILDINGS INCLUDE THOSE SPECIFIED IN SECTIONS |
| | C101.4.8.1 THROUGH C101.4.8.4. |
| | |
| | NOT ADDRESSED. |
| | 2. SHOW IN YOUR PROJECT DATA THE LEVEL OF ALTERATION |
| | THAT IS SELECTED. FBC EXISTING BUILDING CODE 407 AND |
| | 501. |
| | |
| | A) SHOW ALSO THE COMPLIANCE WITH FBC EXISTING BUILDING |
| | 1001 CHANGE OF OCCUPANCY. |
| | |
| | OK. ADDRESSED. |
| | 3. (A) UPDATE TRAVEL DISTANCE ON PLANS. IT IS SHOWN AS |
| | 46 FEET BUT MEASURES APPROXIMATELY 53 FEET. |
| | |
| | PARTIALLY ADDRESSED. NOT UPDATED UNDER OCCUPANY |
| | CLASSIFICATION. |
| | (B) UPDATE SQUARE FOOTAGE IT IS SHOWN AS 600 SQ. FT. |
| | BUT IS ACTUALLY 586.4 SQ. FT. |
| | |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| | UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE |
| | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | |
| | OK. ADDRESSED. |
| | 4. UPDATE CODE DATA TO REFLECT 2014 FLORIDA PLUMBING |
| | CODE 5TH EDITION AND NFPA 2014 5TH EDITION. |
| | |
| | |
| | 5. ACCESSIBILITY: |
| | |
| | NOT ADDRESSED. |
| | (A) DOOR AT THE BATHROOM SHALL HAVE MANEUVERING |
| | CLEARANCES IN COMPLIANCE WITH FLORIDA ACCESSIBILITY |
| | CODE 5TH EDITION. |
| | 404.2.4 MANEUVERING CLEARANCES. |
| | MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL |
| | COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL |
| | EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED |
| | LATCH SIDE OR HINGE SIDE CLEARANCE. |
| | |
| | PARTIALLY ADDRESSED. THE 12" AT THE LATCH SIDE IS |
| | SHOWN. SEE 404.2.4.1 DETAILS (A) AND (D) FOR 60 INCHES |
| | CLEAR. |
| | 404.2.4.1 SWINGING DOORS AND GATES. |
| | SWINGING DOORS AND GATES SHALL HAVE MANEUVERING |
| | CLEARANCES COMPLYING WITH TABLE 404.2.4.1. DETAIL (A) |
| | AND (C). |
| | |
| | NOT ADDRESSED. |
| | (B) PROVIDE SCALED ELEVATIONS FOR WORK AREA AND |
| | CUSTOMER SERVICE COUNTER AREAS. SHOW COMPLIANCE WITH |
| | 203.9 EMPLOYEE WORK AREAS AND 904.4. |
| | 904 CHECK-OUT AISLES AND SALES AND SERVICE COUNTERS |
| | CHECK-OUT AISLES AND SALES AND SERVICE COUNTERS SHALL |
| | COMPLY WITH THE APPLICABLE REQUIREMENTS OF 904. |
| | |
| | PARTIALLY ADDRESSED. TABLE HEIGHT NOT SHOWN. |
| | (C) SHOW HOW THE DINING AREA WILL COMPLY WITH 902.1 |
| | GENERAL. |
| | DINING SURFACES AND WORK SURFACES SHALL COMPLY WITH |
| | 902.2 AND 902.3. |
| | |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| | UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE |
| | PERMITTED TO BE SUBMITTED WHEN APPROVED BY THE BUILDING |
| | OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE BUILDING OFFICIAL. |
| | |
| | NOT ADDRESSED. |
| | 6. (A) CLARIFY THE SCOPE OF WORK ON THE PLANS AND |
| | PERMIT APPLICATION. IT IS SHOWN AS EXISTING RETAIL |
| | SPACE BUT THE 1 HOUR WALL DETAIL IS SHOWING THE TENANT |
| | SEPARATION WALLS AS NEW. |
| | |
| | NOT ADDRESSED. |
| | (B ) LABEL ALL WALLS ON PLANS SHOW NEW AND EXISTING. |
| | |
| | NOT ADDRESSED. |
| | (C) BATHROOM IS SHOWN AS AN UPGRADE BUT INCLUDES NEW |
| | WALLS AND A COMPLETE RECONFIGURATION OF PLUMBING |
| | FIXTURES. |
| | |
| | OK SHOWN ON PLANS. |
| | (D) SHOW ADJACENT TENANT SPACE USE. |
| | |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| | UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE |
| | PERMITTED TO BE SUBMITTED WHEN APPROVED BY THE BUILDING |
| | OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE BUILDING OFFICIAL. |
| | |
| | FBC107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING |
| | OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA |
| | AND DOCUMENTS. |
| | SEE THIS SECTION FOR MINIMUM PLAN REVIEW CRITERIA. |
| | |
| | |
| | WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: |
| | |
| | HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2 |
| | 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION. |
| | |
| | WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED |
| | SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS |
| | READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE |
| | RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE |
| | FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR |
| | *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN |
| | THE PERMIT PACKAGE. |
| | |
| | A RESPONSE LETTER INDICATING HOW EACH ITEM WAS |
| | ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW. |
| | |