2018-01-25 08:05:392ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17120353
 1/25/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: THE 180 CFMS OF OUTSIDE AIR WAS NOT
 CALCULATED IN ACCORDANCE WITH TABLE 403.3, HOWEVER IT
 EXCEEDS THE AMOUNT OF AIR REQUIRED BY CODE SO IT IS
 ACCEPTED.
  
 2) M-1: THE AC SCHEDULED IS INCORRECTLY INDCICATING
 2000 CFMS OF SUPPLY AIR FOR A 3-TON SYSTEM. A TYPICAL
 3-TON SYSTEM WILL PRODUCE 1200 CFMS +/-. PLEASE
 CORRECT.
  
 3) M-1: THE AC LAYOUT PLAN IS INCOMPLETE: THE SIZE OF
 THE MAIN TRUNK IS NOT SHOWN, AND ONLY 3- 200 CFM SUPPLY
 DIFFUSERS ARE SHOWN WHICH INDICATES THE TOTAL SUPPLY
 AIR IN THE SPACE AT 600 CFMS FOR THE 3-TON SYSTEM.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  