| 2018-01-25 08:05:39 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17120353 | | | 1/25/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M-1: THE 180 CFMS OF OUTSIDE AIR WAS NOT | | | CALCULATED IN ACCORDANCE WITH TABLE 403.3, HOWEVER IT | | | EXCEEDS THE AMOUNT OF AIR REQUIRED BY CODE SO IT IS | | | ACCEPTED. | | | | | | 2) M-1: THE AC SCHEDULED IS INCORRECTLY INDCICATING | | | 2000 CFMS OF SUPPLY AIR FOR A 3-TON SYSTEM. A TYPICAL | | | 3-TON SYSTEM WILL PRODUCE 1200 CFMS +/-. PLEASE | | | CORRECT. | | | | | | 3) M-1: THE AC LAYOUT PLAN IS INCOMPLETE: THE SIZE OF | | | THE MAIN TRUNK IS NOT SHOWN, AND ONLY 3- 200 CFM SUPPLY | | | DIFFUSERS ARE SHOWN WHICH INDICATES THE TOTAL SUPPLY | | | AIR IN THE SPACE AT 600 CFMS FOR THE 3-TON SYSTEM. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|