2017-12-21 14:42:271ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #17120353
 12/21/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO SECTION 1009.1 FBC-14 EXISTING BUILDING
 CODE AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR
 ALL ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED CFMS OF
 OUTDOOR AIR AND THE AMOUNT OF CFMS PROVIDED BY THE
 EXISTING SYSTEM.
  
 2) NO MECHANICAL PLANS WERE SUBMITTED. PLEASE PROVIDE
 PLANS SHOWING ALL CHANGES TO BE MADE TO THE EXISTING
 SYSTEMS.
  