| 2017-12-21 14:42:27 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES | | | PERMIT #17120353 | | | 12/21/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) REFER TO SECTION 1009.1 FBC-14 EXISTING BUILDING | | | CODE AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR | | | ALL ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. | | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED CFMS OF | | | OUTDOOR AIR AND THE AMOUNT OF CFMS PROVIDED BY THE | | | EXISTING SYSTEM. | | | | | | 2) NO MECHANICAL PLANS WERE SUBMITTED. PLEASE PROVIDE | | | PLANS SHOWING ALL CHANGES TO BE MADE TO THE EXISTING | | | SYSTEMS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|