Plan Review Notes
Plan Review Notes For Permit 17120353
Permit Number 17120353
Review Stop E
Sequence Number 1
Notes
Date Text
2017-12-27 16:10:11CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE GRAPH/CALCULATION OF INTERIOR LIGHTING POWER
 ALLOWANCES PER THE FBC ENERGY CODE IN RELATION TO THE
 CONNECTED INTERIOR LIGHTING PROPOSED TO COMPLY WITH
 CODE. FBC EC 405.5.2
 2. PROVIDE THE ADDITIONAL AUTOMATIC LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. PLAN NEEDS TO SHOW
 LOCATION AND DESIGN OF CONTROL. FBC EC 405.2.2,
 405.2.2.2
 3. PROVIDE SHOW WINDOW OUTLETS REQUIRED PER CODE. NEC
 210.62
 4. PROVIDE GFCI PROTECTION FOR ALL OUTLETS IN KITCHEN /
 PREP AREAS. NEC 210.8
 5. PROVIDE LIGHTING CONTROLS FOR SIGN CIRCUIT AND SHOW
 WINDOW CIRCUIT. PER CODE: "LIGHTING NOT DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A
 COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN
 ASTRONOMICAL TIME SWITCH. LIGHTING DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY AN
 ASTRONOMICAL TIME SWITCH OR PHOTOSENSOR. ALL TIME
 SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMMING AND
 THE TIME SETTING DURING LOSS OF POWER FOR A PERIOD OF
 AT LEAST 10 HOURS.' FBC EC 405.2.4
 6. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1,
 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  