| 2017-12-19 06:13:47 | 1) CITY RECORDS SHOW THAT THE PREVIOUS BUSINESS IN THIS |
| | SPACE WAS A RETAIL STORE (MERCANTILE OCCUPANCY) . A |
| | HAIR SALON IS CONSIDERED A BUSINESS OCCUPANCY IN |
| | ACCORDANCE WITH THE 2014 FBC-BUILDING SEC.304.1. |
| | COMPLIANCE WITH THE 2014 FBC-EXISTING BUILDING SECS. |
| | 1001.3 IS REQUIRED. |
| | 2) 2014 FBC-EXISTING BUILDING VOLUME - SEC.1006.1 - |
| | ACCESSIBILITY - ACCESSIBILITY IN PORTIONS OF BUILDINGS |
| | UNDERGOING A CHANGE OF OCCUPANCY CLASSIFICATION SHALL |
| | COMPLY WITH THE PROVISIONS OF THE FLORIDA BUILDING |
| | CODE, ACCESSIBILITY. THE EXISTING TOILET ROOM SHALL |
| | COMPLY WITH THE REQUIREMENTS OF THE ACCESSIBILITY CODE. |
| | SUBMIT A FLOOR PLAN SHOWING COMPLIANCE. |
| | 3) CORRECT THE ADDRESS ON THE PLANS. THE PLANS NOTE THE |
| | ADDRESS AS 118 CLEMATIS ST. AND THE ADDRESS ON THE |
| | PERMIT APPLICATION IS LISTED AS 330 CLEMATIS ST., UNIT |
| | #118. CLARIFY. |
| | 4) SUBMIT A WATER RISER DIAGRAM THAT CLEARLY SHOWS THE |
| | ENTIRE SCOPE OF WATER PIPING TO BE INSTALLED. WPB |
| | AMEND. TO FBC SEC. 107.3.5.1.3 ( 3 ). |
| | 5) SUBMIT A SANITARY RISER DIAGRAM THAT CLEARLY SHOWS |
| | THE ENTIRE SCOPE OF DRAINAGE PIPING TO BE INSTALLED. |
| | WPB AMEND. TO FBC SEC. 107.3.5.1.3 ( 4 ).SHOW ALL PIPE |
| | SIZES ON THE SANITARY RISER. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 6) ALL INDIRECT WASTE PIPING THAT EXCEEDS 30 INCHES IN |
| | DEVELOPED LENGTH MEASURED HORIZONTALLY, OR 54 INCHES IN |
| | TOTAL DEVELOPED LENGTH SHALL BE TRAPPED. 2014 |
| | FBC-PLUMBING SEC. 802.2. |
| | 7) THE SUBMITTED PLANS HAVE A NOTE STATING THAT THE |
| | EXISTING PLUMBING FIXTURES IN THE TOILET ROOM ARE TO BE |
| | REMOVED AND TO SEE SHEET TWO OF THREE FOR THE NEW |
| | LAYOUT. THERE ARE NO SHEETS TWO OF THREE OR THREE OF |
| | THREE AND THERE IS NO OTHER INFORMATION AS TO THE |
| | INSTALLATION OF NEW FIXTURES OR WHAT ELSE WILL BE DONE. |
| | CLARIFY. A MINIMUM OF ONE TOILET ROOM COMPLYING WITH |
| | THE FLORIDA ACCESSIBILITY CODE SHALL BE PROVIDED. |
| | 8) HOT OR TEMPERED WATER SHALL BE SUPPLIED TO THE NEW |
| | WASH STATION SINKS AND TO THE HAND SINK PER 2014 |
| | FBC-PLUMBING SEC. 607.1. |
| | 9) TEMPERED WATER SHALL BE SUPPLIED THROUGH A WATER |
| | TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE 1070 |
| | AND SHALL LIMIT THE TEMPERED WATER TO A MAXIMUM OF 110 |
| | DEGREES. 2014 FBC-PLUMBING SEC.607.1.2. |
| | 10) MEANS SHALL BE PROVIDED FOR CONTROLLING INCREASED |
| | PRESSURE CAUSED BY THERMAL EXPANSION IN ACCORDANCE WITH |
| | 2014 FBC-PLUMBING SEC.607.3. |
| | 11) SHOW THE OCCUPANT LOAD FOR THE NEW OCCUPANCY ON THE |
| | PLANS. WPB AMEND. TO FBC SEC. 107.2.1. WPB AMEND. TO |
| | FBC SEC. 107.3.5.1.1. |
| | 12) BUILDINGS UNDERGOING A CHANGE OF OCCCUPANCY SHALL |
| | ALSO COMPLY WITH THE 2014 FBC - EXISTING BUILDING CODE |
| | CHAPTERS 7,8, & 9 PER 2014 FBC EXISTING BUILDING |
| | SEC.1012.1.1. |
| | |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |