| 2018-01-12 09:45:30 | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17120347 |
| | 1/12/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | |
| | 1) NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW. SEE |
| | REQUIREMENTS BELOW: |
| | |
| | A) THE MAIN MECHANICAL REQUIREMENT FOR A HAIR SALON IS |
| | AN EXHAUST VENTILATION SYSTEM THAT HAS AN EXHAUST RATE |
| | OF 0.6 CFMS PER SQ. FT FOR THE SALON AREA- TABLE 403.3 |
| | |
| | B) THE EXHAUST FAN MUST BE SUPPLIED WITH A SOURCE OF |
| | MAKEUP AIR AND MUST RUN CONTINUOUSLY WHENEVER THE SALON |
| | IS IN OPERATION- SECTION 501.4 |
| | |
| | C) THE EXISTING OR NEW AC SYSTEM(S) MUST BE ABLE TO |
| | PROVIDE OUTDOOR AIR TO OCCUPANTS AT A RATE OF 20 CFMS |
| | PER PERSON AND 0.12 CFMS PER SQ. FT. THE OCCUPANT LOAD |
| | PER THE MECHANICAL CODE IS CALCULATED AT 25 |
| | PERSONS/SQ.FT.. PLEASE PROVIDE VENTILATION |
| | CALCULATIONS. |
| | |
| | D) PLEASE NOTE IT IS PROHIBITED FOR AIR THAT IS |
| | SUPPLIED TO THE SALON SPACE TO BE RECIRCULATED TO OTHER |
| | ROOMS OR SPACES IN THE TENANT SPACE OR IN THE BUILDING |
| | IN GENERAL- TABLE 403.3 FOOTNOTE B. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |