| 2021-03-08 09:43:32 | NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | ORIGINAL COMMENT: |
| | 1- ENERGY CALCULATIONS: |
| | THE ENERGY FORM R405-2017 IS REQUIRED TO BE SIGNED AND |
| | DATED BY THE OWNER, ARCHITECT OR OWNER'S LEGALLY |
| | DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS |
| | REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, |
| | 6TH EDITION (2017) PRIOR TO RECEIVING THE PERMIT TO |
| | BEGIN CONSTRUCTION. |
| | |
| | RESPONSE: |
| | SIGNED ENERGY CALCULATIONS SUBMITTED ARE FOR ANOTHER |
| | HOUSE. ENERGY CALCULATIONS SUBMITTED ARE FOR 425 HOGANS |
| | ST. THIS PERMIT APPLICATION IS FOR 422 20TH ST. PROVIDE |
| | CORRECT ENERGY CALCULATIONS. |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, |
| | |
| | 2- OK. |
| | |
| | 3- OK. |
| | |
| | ORIGINAL COMMENT: |
| | 4- PROVIDE BOUNDARY LINE SURVEY AS REQUIRED BY SEC. |
| | 107.2.5 CITY AMENDMENTS. |
| | PROVIDE SURVEY WITH ORIGINAL SEAL/SIGNATURE (DIGITAL |
| | SIGNATURE OR HARDCOPY ORIGINAL) AS REQUIRED BY CHAPTER |
| | 472 FLORIDA STATUTES WHEN SUBMITTING DOCUMENTS FOR |
| | PUBLIC RECORDS. |
| | |
| | RESPONSE: |
| | SURVEY UPLOADED IS FOR LOT 4. THIS PERMIT APPLICATION |
| | IS FOR LOT 2. PROVIDE CORRECT SURVEY. NOTE: PLEASE |
| | UPLOAD THE SURVEY IN THE "DRAWINGS" FOLDER NOT IN THE |
| | "SUPPORTING DOCUMENTS" FOLDER AS REQUIRED BY THE CITY |
| | GUIDELINES FOR DIGITAL SUBMITTALS. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | ORIGINAL COMMENT: |
| | 5- MERRY PLACE LOT GRADING SHEET C1: |
| | A) DRAWING C1 WAS UPLOADED IN THE "SUPPORTING |
| | DOCUMENTS" FOLDER INSTEAD OF THE "DRAWINGS" FOLDER. ALL |
| | DRAWINGS NEED TO BE UPLOADED IN THE "DRAWINGS" FOLDER |
| | (WITH PROPER DIGITAL SIGNATURE) AS REQUIRED BY THE CITY |
| | DIGITAL PLAN REVIEW INSTRUCTIONS AND SEC. 107.2.1.3 |
| | CITY AMENDMENTS FOR PROPER RECORDS RETENTION. |
| | |
| | RESPONSE: |
| | NOW WE ARE MISSING DRAWING C1. PLEASE UPLOAD DRAWING C1 |
| | INTO THE DRAWINGS FOLDER. |
| | |
| | 6-DEFERRED SUBMITTALS: |
| | WINDOWS, DOORS, ROOFING AND ROOF VENTS, ALUMINUM |
| | SOFFITS, RAILINGS AND GUARDRAILS. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE FOR REVIEW PRIOR TO SUBMITTAL TO |
| | THIS OFFICE. SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | |
| | 7- NEW COMMENT FOR CLARIFICATION: |
| | THERE ARE TWO SITE PLANS SUBMITTED. ONE OF THEM IS |
| | SHEET A-0.1 AND THE OTHER ONE IS SHEET SP-1. CLARIFY |
| | WHY SUBMITTING 2 DIFFERENT DRAWINGS FOR THE SITE PLAN |
| | AND WHICH ONE IS THE CORRECT ONE. PLEASE PROVIDE ONLY |
| | THE ONE TO BE CONSIDERED TO AVOID CONFLICTS/DELAYS. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |