| 2021-02-22 14:08:33 | NEW SINGLE FAMILY RESIDENCE R3) SECOND BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | PERMIT#17120309 |
| | |
| | 1- OK |
| | |
| | 2- OK |
| | |
| | ORIGINAL COMMENT: |
| | 3- IT LOOKS LIKE SECOND FLOOR SINGLE HUNG EGRESS |
| | WINDOWS #2 HAVE THE WINDOW SILL LOCATED LESS THAN 24 |
| | INCHES ABOVE THE FINISH FLOOR. NEED TO COMPLY WITH THE |
| | WINDOW FALL PROTECTION SEC. R312.2 FBC-RESIDENTIAL. |
| | PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING |
| | COMPLIANCE. |
| | |
| | RESPONSE: |
| | SIZE OF SINGLE HUNG EGRESS WINDOW #2 WAS REVISED. NEW |
| | SIZE DOESN'T SEEM TO COMPLY WITH THE EGRESS |
| | REQUIREMENTS OF SEC. R310.2.1 FBC-RESIDENTIAL. 4'-11" |
| | HEIGHT SINGLE HUNG WINDOW DOESN'T SEEM PROVIDE THE MIN. |
| | 24" CLEAR HEIGHT OPENING. REVISE SIZE OF WINDOW OR |
| | PROVIDE MANUFACTURER'S CUT SHEETS SHOWING THAT |
| | SPECIFIED WINDOW SIZE WILL MEET ALL THE EGRESS |
| | REQUIREMENTS. CLEAR HEIGHT, CLEAR WIDTH AND TOTAL CLEAR |
| | OPENING (5.7 S.F. MIN.). |
| | |
| | 4- OK |
| | |
| | 5- OK |
| | |
| | 6-DEFERRED SUBMITTALS: |
| | WINDOWS, DOORS, SHUTTERS IF DOORS WITH GLAZING AND |
| | WINDOWS DON'T HAVE IMPACT GLASS, ROOFING AND ROOF |
| | VENTS, ALUMINUM SOFFITS, RAILINGS AND GUARDRAILS. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE FOR REVIEW PRIOR TO SUBMITTAL TO |
| | THIS OFFICE. SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 7- OK |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |