Plan Review Notes
Plan Review Notes For Permit 17120261
Permit Number 17120261
Review Stop M
Sequence Number 4
Notes
Date Text
2018-09-06 14:06:22MECHANICAL PROVISOS:
 CCOLE- 9/6/18
  
 THE FOLLOWING IS A LIST OF DEFERRED SUBMITTALS AS
 REQUESTED. PLEASE NOTE THAT ALL SUBMITTALS, AND ALL
 DELEGATED ENGINEERING, SHOP DRAWINGS ETC. SHALL BEAR
 APPROVAL STAMPS BY THE ENGINEER OF RECORD.
  
 1) WIND LOAD ENGINEERING FOR ALL ROOFTOP AND EXTERIOR
 MECHANICAL EQUIPMENT INCLUDING THE RTU'S, RTU CURBS,
 CONDENSERS AND STANDS, DUCTWORK AND SUPPORTS, FANS AND
 FAN CURBS, PIPE STANDS AND BRACKETS, INFRARED HEATERS,
 DESTRATIFICATION FANS, ETC.
  
 2) MIAMI-DADE NOA'S AND/OR FL. PRODUCT APPROVALS FOR
 LOUVERS AND ROOF STANDS, INCLUDING PRODUCT DATA SHEETS
 FOR THE LOUVERS FROM THE MANUFACTURER.
  
 3) WATER HEATER AND WATER HEATER VENT PIPING.
  
 4) FIRE DAMPERS, AND FIRE/SMOKE DAMPERS.
  
 5) DUCT SMOKE DETECTORS.
  
 6) MOTORIZED DAMPERS.
  
 7) REFRIGERANT RISER DIAGRAM FOR THE AAON FAN COIL
 SYSTEMS.
  
 8) KITCHEN COOKING APPLIANCES
  
 9) FIRESTOPPING
  
 10) PIPE AND DUCT INSULATIONS.
  
 11) GREASE DUCT ENCLOSURE WRAPPING.
  
 12) COMMISSIONING OF THE MECHANICAL AND ELECTRICAL
 LIGHTING SYSTEMS.
  
 ADVISORY: PLEASE NOTE THAT THE FINAL COMMISSIONING
 REPORT MUST BE SUBMITTED TO BOTH THE OWNERSHIP OF THE
 BUILDING AND THE BUILDING DEPARTMENT PRIOR TO RECEIVING
 THE CERTIFICATE OF OCCUPANCY.
  
 ADVISORY: SEPATRATE PERMITS ARE REQUIRED FOR THE
 KITCHEN EXHAUST HOODS, FIRE SUPPRESSION SYSTEMS, FIRE
 SPRINKLERS, FIRE ALARM, AND WALK-IN COOLER AND FREEZER.
  
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  