| 2018-08-10 08:16:57 | 3RD REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION, |
| | FUEL GAS CODES, AND WEST PALM BEACH AMENDMENTS TO THE |
| | FBC-14 |
| | PERMIT #17120261 |
| | 8/10/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE UPDATED COMCHECK ENERGY CERTIFICATE IS NOT |
| | ELECTRONICALLY SIGNED AND SEALED BY THE ENGINEER OF |
| | RECORD- SECTION 61G15-23.005 FAC. |
| | |
| | 2) SHEETS M2-2-B & M2-3-B: PLEASE ADD NOTES TO THE |
| | DRAWING TO INDICATE THE GREASE EXHAUST DUCT WILL BE |
| | ENCLOSED BY A FIELD-APPLIED GREASE DUCT ENCLOSURE THAT |
| | IS A LISTED AND LABELED WRAPPING MATERIAL OR PRODUCT |
| | THAT HAS BEEN SPECIFICALLY EVALUATED FOR SUCH PURPOSE |
| | IN ACCORDANCE WITH ASTM E 2336. PLEASE PROVIDE THE NAME |
| | OF THE PRODUCT ON THE PLAN AND SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS. |
| | |
| | 3) MEPO-2: PLEASE CLARIFY WHY NO HEAT RECOVERY COOLING |
| | OR HEATING DATA FOR RTU-3 IS SHOWN IN THE SCHEDULE. |
| | |
| | 4) THE FOLLOWING IS A LIST OF DEFERRED SUBMITTALS AS |
| | REQUESTED. PLEASE NOTE THAT ALL SUBMITTALS, AND ALL |
| | DELEGATED ENGINEERING, SHOP DRAWINGS ETC. SHALL BEAR |
| | APPROVAL STAMPS BY THE ENGINEER OF RECORD. |
| | |
| | A) WIND LOAD ENGINEERING FOR ALL ROOFTOP AND EXTERIOR |
| | MECHANICAL EQUIPMENT INCLUDING THE RTU'S, RTU CURBS, |
| | CONDENSERS AND STANDS, DUCTWORK AND SUPPORTS, FANS AND |
| | FAN CURBS, PIPE STANDS AND BRACKETS, INFRARED HEATERS, |
| | DESTRATIFICATION FANS, ETC. |
| | |
| | B) MIAMI-DADE NOA'S AND/OR FL. PRODUCT APPROVALS FOR |
| | LOUVERS AND ROOF STANDS, INCLUDING PRODUCT DATA SHEETS |
| | FOR THE LOUVERS FROM THE MANUFACTURER. |
| | |
| | C) WATER HEATER AND WATER HEATER VENT PIPING. |
| | |
| | D) FIRE DAMPERS. |
| | |
| | E) DUCT SMOKE DETECTORS. |
| | |
| | F) MOTORIZED DAMPERS. |
| | |
| | G) REFRIGERANT RISER DIAGRAM FOR THE AAON FAN COIL |
| | SYSTEMS. |
| | |
| | H) KITCHEN COOKING APPLIANCES |
| | |
| | I) FIRESTOPPING |
| | |
| | J) PIPE AND DUCT INSULATIONS. |
| | |
| | K) GREASE DUCT ENCLOSURE WRAPPING. |
| | |
| | L) COMMISSIONING OF THE MECHANICAL AND ELECTRICAL |
| | LIGHTING SYSTEMS. |
| | |
| | ADVISORY: PLEASE NOTE THAT THE FINAL COMMISSIONING |
| | REPORT MUST BE SUBMITTED TO BOTH THE OWNERSHIP OF THE |
| | BUILDING AND THE BUILDING DEPARTMENT PRIOR TO RECEIVING |
| | THE CERTIFICATE OF OCCUPANCY. |
| | |
| | ADVISORY: SEPATRATE PERMITS ARE REQUIRED FOR THE |
| | KITCHEN EXHAUST HOODS, FIRE SUPPRESSION SYSTEMS, FIRE |
| | SPRINKLERS, FIRE ALARM, AND WALK-IN COOLER AND FREEZER. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |