2018-08-10 08:16:573RD REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION,
 FUEL GAS CODES, AND WEST PALM BEACH AMENDMENTS TO THE
 FBC-14
 PERMIT #17120261
 8/10/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE UPDATED COMCHECK ENERGY CERTIFICATE IS NOT
 ELECTRONICALLY SIGNED AND SEALED BY THE ENGINEER OF
 RECORD- SECTION 61G15-23.005 FAC.
  
 2) SHEETS M2-2-B & M2-3-B: PLEASE ADD NOTES TO THE
 DRAWING TO INDICATE THE GREASE EXHAUST DUCT WILL BE
 ENCLOSED BY A FIELD-APPLIED GREASE DUCT ENCLOSURE THAT
 IS A LISTED AND LABELED WRAPPING MATERIAL OR PRODUCT
 THAT HAS BEEN SPECIFICALLY EVALUATED FOR SUCH PURPOSE
 IN ACCORDANCE WITH ASTM E 2336. PLEASE PROVIDE THE NAME
 OF THE PRODUCT ON THE PLAN AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS.
  
 3) MEPO-2: PLEASE CLARIFY WHY NO HEAT RECOVERY COOLING
 OR HEATING DATA FOR RTU-3 IS SHOWN IN THE SCHEDULE.
  
 4) THE FOLLOWING IS A LIST OF DEFERRED SUBMITTALS AS
 REQUESTED. PLEASE NOTE THAT ALL SUBMITTALS, AND ALL
 DELEGATED ENGINEERING, SHOP DRAWINGS ETC. SHALL BEAR
 APPROVAL STAMPS BY THE ENGINEER OF RECORD.
  
 A) WIND LOAD ENGINEERING FOR ALL ROOFTOP AND EXTERIOR
 MECHANICAL EQUIPMENT INCLUDING THE RTU'S, RTU CURBS,
 CONDENSERS AND STANDS, DUCTWORK AND SUPPORTS, FANS AND
 FAN CURBS, PIPE STANDS AND BRACKETS, INFRARED HEATERS,
 DESTRATIFICATION FANS, ETC.
  
 B) MIAMI-DADE NOA'S AND/OR FL. PRODUCT APPROVALS FOR
 LOUVERS AND ROOF STANDS, INCLUDING PRODUCT DATA SHEETS
 FOR THE LOUVERS FROM THE MANUFACTURER.
  
 C) WATER HEATER AND WATER HEATER VENT PIPING.
  
 D) FIRE DAMPERS.
  
 E) DUCT SMOKE DETECTORS.
  
 F) MOTORIZED DAMPERS.
  
 G) REFRIGERANT RISER DIAGRAM FOR THE AAON FAN COIL
 SYSTEMS.
  
 H) KITCHEN COOKING APPLIANCES
  
 I) FIRESTOPPING
  
 J) PIPE AND DUCT INSULATIONS.
  
 K) GREASE DUCT ENCLOSURE WRAPPING.
  
 L) COMMISSIONING OF THE MECHANICAL AND ELECTRICAL
 LIGHTING SYSTEMS.
  
 ADVISORY: PLEASE NOTE THAT THE FINAL COMMISSIONING
 REPORT MUST BE SUBMITTED TO BOTH THE OWNERSHIP OF THE
 BUILDING AND THE BUILDING DEPARTMENT PRIOR TO RECEIVING
 THE CERTIFICATE OF OCCUPANCY.
  
 ADVISORY: SEPATRATE PERMITS ARE REQUIRED FOR THE
 KITCHEN EXHAUST HOODS, FIRE SUPPRESSION SYSTEMS, FIRE
 SPRINKLERS, FIRE ALARM, AND WALK-IN COOLER AND FREEZER.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  