| 2018-07-19 18:59:55 | 3RD REVIEW / 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17120261 |
| | ADD: 1600 BELVEDERE RD. |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: NOT GIVEN ON PERMIT APPLICATION |
| | E-MAIL: NOT GIVEN ON THE PERMIT APPLICATION |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | PLAN |
| | REVIEW COMMENTS |
| | |
| | 3RD REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) PROVISO: ART IN PUBLIC PLACES. THE CITY OF WEST PALM |
| | BEACH ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT |
| | APPLIES TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR |
| | WHICH THE PERMIT APPLICATION WAS SUBMITTED AFTER |
| | 6/29/14, AND THE TOTAL PROJECT CONSTRUCTION COSTS ARE |
| | EQUAL TO OR GREATER THAN $750,000 WILL NEED TO COMPLY |
| | WITH THIS ORDINANCE. |
| | PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND |
| | CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, |
| | ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION |
| | 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL |
| | PROJECT CONSTRUCTION COST. |
| | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| | PROJECTS. |
| | SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE |
| | DEVELOPMENT. |
| | (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND |
| | THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL |
| | PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW |
| | CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN |
| | EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE |
| | EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS |
| | WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED |
| | CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES |
| | REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED |
| | SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF |
| | THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW |
| | CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS. |
| | FOR CONTACT INFORMATION PLEASE CONTACT: |
| | MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR |
| | 822-1515 E-MAIL: [email protected] |
| | |
| | 2) 2ND ROUND COMMENT. WE HAVE CALCULATED THE VALUE OF |
| | THE BUILDING USING THE ICC TABLES FROM AUGUST 01/2017. |
| | THERE IS NO A5 CLASS IN THE TABLES; THE CLOSEST USE IS |
| | A4 ARENAS. |
| | 63,885.0 SQ. FT. X $190.84 BUILDING TYPE II-B = |
| | $12,191,813.00 (CALCULATED VALUE) |
| | PLEASE PROVIDE AN ITEMIZED LIST OF THE SUB-PERMITS NOT |
| | COVERED UNDER THE MAIN PERMIT AND DEDUCT THERE VALUE |
| | FROM THE OVERALL CALCULATED VALUE OF THE BUILDING. THIS |
| | WILL BECOME THE NEW ADJUSTED VALUE OF THE BUILDING |
| | PERMIT. |
| | THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE |
| | MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS. |
| | WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING |
| | PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE |
| | QUALIFIER AND OWNER AND BRINGS IN THE LISTED |
| | SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE |
| | QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND |
| | LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE |
| | FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN |
| | LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR |
| | EACH PERMIT. |
| | ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK |
| | STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE |
| | AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS & |
| | FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL |
| | TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED |
| | SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, |
| | LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR |
| | FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE |
| | REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT. |
| | PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE |
| | ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE |
| | STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE |
| | REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE |
| | BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE |
| | BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR |
| | THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE |
| | PRIME PERMIT |
| | |
| | 3) COMPLIED. |
| | |
| | 3A) COMPLIED. |
| | |
| | 3B) COMPLIED. |
| | |
| | 3C) COMPLIED. W.P.B. AMENDMENT 110.3.7.4.4 . 633 |
| | FLORIDA STATUTE. |
| | |
| | 3D)COMPLIED. |
| | |
| | 3E) COMPLIED. |
| | |
| | 3F) NOTICE ONLY: FOR DIGITAL PLANS, AFTER PERMIT |
| | ISSUANCE, PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE |
| | PERMIT BEING ISSUED, THE PERMIT LIBRARIAN WILL THEN |
| | E-MAIL YOU THE APPROVED AND BATCH STAMPED PLANS SO YOU |
| | MAY PRINT YOUR PLANS, TWO SETS OF PLANS WILL NEED TO BE |
| | PRINTED IN COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE |
| | OTHER FOR THE MEP INSPECTORS OTHER PLANS YOU WISH TO |
| | PRINT MAYBE IN BLACK & WHITE.. |
| | 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD |
| | BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS |
| | CONCERNING SPECIAL INSPECTORS. |
| | |
| | 3G) PROVISO/ NOTICE ONLY. 110.3.7.4.3 ALL SHORING AND |
| | RESHORING PROCEDURES, PLANS AND DETAILS SHALL BE |
| | SUBMITTED TO THE ENFORCEMENT AGENCY FOR RECORDKEEPING. |
| | EACH SHORING AND RESHORING INSTALLATION SHALL BE |
| | SUPERVISED, INSPECTED AND CERTIFIED TO BE IN COMPLIANCE |
| | WITH THE SHORING DOCUMENTS BY THE CONTRACTOR. |
| | |
| | 3H) PROVISO/ NOTICE ONLY. PLEASE CALL THE CITY OF WEST |
| | PALM BEACHS AUTOMATED TELEPHONE INSPECTIONS LINE (561) |
| | 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF |
| | JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN |
| | 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| | |
| | 3I) PROVISO/ NOTICE ONLY. 109.3.6 THRESHOLD BUILDINGS, |
| | OPERATING GUIDELINES FOR THRESHOLD INSPECTORS #26. |
| | ASSURE THAT THE DESIGNER HAS REQUIRED ON THE PLANS OR |
| | SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING |
| | PENETRATIONS, FOR WALLS AND CEILINGS. |
| | |
| | 4) PROVISO. THIS PROPERTY IS LOCATED IN A AE FLOOD |
| | ZONE. THE BASE FLOOD ELEVATION IS 12.7 FT. NAVD 88 PLUS |
| | 2 FEET OR A FINISH FLOOR ELEVATION MINIMUM OF 14.77 |
| | NAVD 88. |
| | ARTICLE XVII ORDINANCES ARTICLE XVII FLOOD PREVENTION & |
| | CONTROL |
| | FBC BUILDING 1612 AND CITY OF WPB CODE OF SECTION |
| | 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A |
| | FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE |
| | REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS |
| | AFTER OCT. 11/ 2017 AN ADDITIONAL ONE FOOT OF FREE |
| | BOARD WILL BE REQUIRED OR (2) FEET ABOVE BASE FLOOD. |
| | |
| | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE |
| | REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES |
| | REQUIRED: |
| | 4) (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF |
| | THE PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH |
| | FLOOR HEIGHT. W. P. B. ADMINISTRATIVE CODE 107.3.5.1.1 |
| | BUILDING MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL |
| | BUILDINGS. ( 8) FLOOD REQUIREMENTS ELEVATIONS, |
| | ENCLOSURES, FLOOD DAMAGE-RESISTANT MATERIALS. |
| | |
| | 4) (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND |
| | ELEVATION CERTIFICATE IS REQUIRED. W. P. B. |
| | ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS 1.2 |
| | FLOOR/ SLAB INSPECTION. IN FLOOD HAZARD AREAS, UPON |
| | PLACEMENT OF THE LOWEST FLOOR, INCLUDING BASEMENT, AND |
| | PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE ELEVATION |
| | CERTIFICATION, REQUIRED IN SECTION 1612.5, SHALL BE |
| | SUBMITTED TO THE BUILDING OFFICIAL. |
| | |
| | 4) (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF |
| | OCCUPANCY OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD |
| | ZONE CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL |
| | EXTERIOR ATTENDANTS A/C PADS OR OTHER SLABS FOR |
| | GENERATORS. |
| | W. P. B. ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS |
| | (6) FINAL INSPECTION. TO BE MADE AFTER THE BUILDING IS |
| | COMPLETED AND READY FOR OCCUPANCY. 6.1. LOWEST FLOOR |
| | ELEVATION. IN FLOOD HAZARD AREAS, AS PART OF THE FINAL |
| | INSPECTION, A FINAL CERTIFICATION OF THE LOWEST FLOOR |
| | ELEVATION SHALL BE SUBMITTED TO THE AUTHORITY HAVING |
| | JURISDICTION. |
| | FEMA NEW FORM AVAILABLE JUNE 13/2016. |
| | OMB NO. 1660-0008 |
| | EXPIRATION DATE: NOV. 30/2018 |
| | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM |
| | |
| | 5) COMPLIED. |
| | 5A) COMPLIED. |
| | 5B) COMPLIED. |
| | 5C) COMPLIED. |
| | 5D) COMPLIED. |
| | 5E) NOTICE ONLY. THE SOILS REPORT INDICATES THERE ARE |
| | TO BE 160 FOOT TALL POLES WITH NETTING TO CATCH THE |
| | GOLF BALLS. THE POLES AND NETTING ARE NOT PART OF THIS |
| | PERMIT AND WILL REQUIRE A SEPARATE PERMIT REVIEW AND |
| | ASSOCIATED FEES. IN THE ANALYSIS FOR THE POLES IT WILL |
| | NEED TO BE MADE CLEAR IF THE NETTING IS TO BE DROPPED |
| | WHEN A HIGH WIND EVENT WILL OCCUR. NOTE THIS ALSO NEEDS |
| | TO BE INCORPORATED INTO THE O & M MANUAL. |
| | 1ST REVIEW. THIS REVIEW NO SOILS REPORTS WERE FOUND IN |
| | THE FILE FOLDER. 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL. |
| | WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY |
| | OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE |
| | SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE |
| | BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| | GEOTECHNICAL INVESTIGATION BE CONDUCTED. |
| | |
| | 6A-D) COMPLIED. |
| | |
| | 7A-G) COMPLIED. |
| | |
| | 8A-H) COMPLIED. 004- LS-01 LIFE SAFETY PLAN. |
| | NEW COMMENTS. |
| | 1) FBC 1014.3 SHOW THE COMMON PATHS OF EGRESS TRAVEL |
| | AND THEIR DISTANCES ON THE LIFE SAFETY PLANS. |
| | 2) ON SHEET 004-LS-01, CLARIFY THE 68" CLEAR DOOR |
| | LISTED IN THE EXIT CAPACITY SUMMARY AT LEVEL 2 FOR |
| | STAIR #3. FBC 107.2.1 |
| | 3) REVISE THE NOTES FOR THE DOORS ON THE HOLD OPEN |
| | DEVICES AT STAIR #3. THESE DOORS SHOULD BE OPENABLE |
| | FROM THE PANTRY SIDE AND SHOULD BE USED AS EXIT EGRESS |
| | DOORS FROM THOSE AREAS. THE ONLY OPENINGS INTO EXIT |
| | ACCESS STAIRWAYS ENCLOSURE ARE THOSE NECESSARY FOR THE |
| | PURPOSE OF THE STAIRWAY. FBC 1009.3.1.4.1 THE FIRE |
| | DEPARTMENT DOES NOT WANT THESE DOORS TO BE OPENABLE |
| | FROM THE STAIRWAY SIDE. |
| | 4) THE EXIT SIGN ON THE GROUND FLOOR DIRECTING THE |
| | GROUND FLOOR OCCUPANTS INTO STAIR #4 SHOULD BE REMOVED. |
| | THE OCCUPANTS OF THE FIRST FLOOR WILL USE THE EXIT DOOR |
| | THAT OPENS TO THE EXTERIOR OF THE BUILDING. THE |
| | OCCUPANTS FROM THE SECOND AND THIRD LEVELS USING STAIR |
| | #3 WILL USE THIS SAME DOOR TO EXIT THE BUILDING. |
| | OTHERWISE, THE OCCUPANTS OF THE UPPER LEVELS MAY |
| | ATTEMPT TO EXIT THROUGH STAIR #4 AND CONVERGE WITH THE |
| | OCCUPANTS USING THIS STAIR. |
| | 5) THE LIFE SAFETY PLAN ON SHEET 004-LS-01 DOES NOT |
| | SHOW THE FIRE RATED WALLS ON ALL SIDES OF STAIR #S 1 |
| | AND 4, AS THEY ARE ON SHEETS 206-A2-01-A AND |
| | 206-A2-01-B. CLARIFY. |
| | |
| | 9) 004- LS-01 LIFE SAFETY PLAN AND FURNITURE PLANS. |
| | NEITHER OF THESE PLANS SHOW COMPLIANCE WITH THE |
| | ACCESSIBILITY CODE: |
| | NEW COMMENTS. THE ADA BAR AREA IS NOT IDENTIFIED AT THE |
| | UPPER LEVEL BAR ONT SHEET 210-A2-01-B. PROVIDE |
| | DIMENSIONS ON THE BAR ELEVATION DRAWINGS TO SHOW THAT |
| | ADA PORTIONS OF THE BARS ARE IN COMPLIANCE AND SHOW THE |
| | CLEAR FLOOR SPACE AT THE BARS AND ANY FIXED SEATING. |
| | |
| | 9A) 2ND REQUEST. 226.1 WHERE DINING SURFACES ARE |
| | PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST |
| | 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT |
| | THE DINING SURFACES SHALL COMPLY WITH 902. |
| | |
| | 9B) 2ND REQUEST. 226.2 DISPERSION. DINING SURFACES AND |
| | WORK SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE |
| | DISPERSED THROUGHOUT THE SPACE OR FACILITY CONTAINING |
| | DINING SURFACES AND WORK SURFACES. |
| | |
| | 9C) 2ND REQUEST. SEMI-COMPLIED. THE PLANS DO SHOW A |
| | DROPPED PORTION OF THE BARS FOR ACCESSIBLE DRINKING |
| | AREA. |
| | NEW COMMENTS. PROVIDE DIMENSIONS ON THE BAR ELEVATION |
| | DRAWINGS TO SHOW THAT ADA PORTIONS OF THE BARS ARE IN |
| | COMPLIANCE AND SHOW THE CLEAR FLOOR SPACE AT THE BARS |
| | AND ANY FIXED SEATING. |
| | |
| | 1ST ROUND COMMENT. 902.1 .DINING SURFACES AND WORK |
| | SURFACES SHALL COMPLY WITH 902.2 AND 902.3. ADVISORY |
| | 902.1 GENERAL. DINING SURFACES INCLUDE, BUT ARE NOT |
| | LIMITED TO, BARS, TABLES, LUNCH COUNTERS, AND BOOTHS. |
| | 9C)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR |
| | SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD |
| | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED. |
| | 9C)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND |
| | WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 10A-E) COMPLIED. |
| | |
| | 10E) COMPLIED. 206.2.15 GOLF FACILITIES. |
| | |
| | 11A-C)COMPLIED. EMERGENCY OVER FLOW SCUPPERS & |
| | SECONDARY (EMERGENCY OVERFLOW) DRAINS OR SCUPPERS. |
| | |
| | 12-23) BUILDING PROVISO: THE DESIGNER OF RECORD WISHES |
| | TO DEFER THE PRODUCT APPROVALS UNTIL AFTER PERMIT |
| | ISSUANCE. SEE THE COVERSHEET 003-CS-1. |
| | 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| | VENTILATORS |
| | (E) SHUTTERS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 24) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| | ONE SET OF PLANS WILL HAVE TO BE TAKEN (BY THE |
| | CONTRACTOR OR REPRESENTATIVE) TO THE PALM BEACH COUNTY |
| | IMPACT FEE OFFICE LOCATED AT 2300 N. JOG RD. ROOMS |
| | 2W01-2W14 WEST PALM BEACH, FL. THE ACTUAL PERMIT SET OF |
| | PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE |
| | PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE |
| | CALL (561)233-5025 FOR MORE INFORMATION. |
| | |
| | 25) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | |
| | |
| | |