2018-07-19 18:59:553RD REVIEW / 2014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17120261
 ADD: 1600 BELVEDERE RD.
 CONT: TBD/ TO BE DETERMINED
 TEL: NOT GIVEN ON PERMIT APPLICATION
 E-MAIL: NOT GIVEN ON THE PERMIT APPLICATION
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVISO: ART IN PUBLIC PLACES. THE CITY OF WEST PALM
 BEACH ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT
 APPLIES TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR
 WHICH THE PERMIT APPLICATION WAS SUBMITTED AFTER
 6/29/14, AND THE TOTAL PROJECT CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $750,000 WILL NEED TO COMPLY
 WITH THIS ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE
 DEVELOPMENT.
 (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND
 THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL
 PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW
 CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN
 EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS
 WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED
 CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES
 REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED
 SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF
 THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW
 CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 2) 2ND ROUND COMMENT. WE HAVE CALCULATED THE VALUE OF
 THE BUILDING USING THE ICC TABLES FROM AUGUST 01/2017.
 THERE IS NO A5 CLASS IN THE TABLES; THE CLOSEST USE IS
 A4 ARENAS.
 63,885.0 SQ. FT. X $190.84 BUILDING TYPE II-B =
 $12,191,813.00 (CALCULATED VALUE)
 PLEASE PROVIDE AN ITEMIZED LIST OF THE SUB-PERMITS NOT
 COVERED UNDER THE MAIN PERMIT AND DEDUCT THERE VALUE
 FROM THE OVERALL CALCULATED VALUE OF THE BUILDING. THIS
 WILL BECOME THE NEW ADJUSTED VALUE OF THE BUILDING
 PERMIT.
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME PERMIT
  
 3) COMPLIED.
  
 3A) COMPLIED.
  
 3B) COMPLIED.
  
 3C) COMPLIED. W.P.B. AMENDMENT 110.3.7.4.4 . 633
 FLORIDA STATUTE.
  
 3D)COMPLIED.
  
 3E) COMPLIED.
  
 3F) NOTICE ONLY: FOR DIGITAL PLANS, AFTER PERMIT
 ISSUANCE, PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE
 PERMIT BEING ISSUED, THE PERMIT LIBRARIAN WILL THEN
 E-MAIL YOU THE APPROVED AND BATCH STAMPED PLANS SO YOU
 MAY PRINT YOUR PLANS, TWO SETS OF PLANS WILL NEED TO BE
 PRINTED IN COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE
 OTHER FOR THE MEP INSPECTORS OTHER PLANS YOU WISH TO
 PRINT MAYBE IN BLACK & WHITE..
 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 3G) PROVISO/ NOTICE ONLY. 110.3.7.4.3 ALL SHORING AND
 RESHORING PROCEDURES, PLANS AND DETAILS SHALL BE
 SUBMITTED TO THE ENFORCEMENT AGENCY FOR RECORDKEEPING.
 EACH SHORING AND RESHORING INSTALLATION SHALL BE
 SUPERVISED, INSPECTED AND CERTIFIED TO BE IN COMPLIANCE
 WITH THE SHORING DOCUMENTS BY THE CONTRACTOR.
  
 3H) PROVISO/ NOTICE ONLY. PLEASE CALL THE CITY OF WEST
 PALM BEACHS AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN
 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 3I) PROVISO/ NOTICE ONLY. 109.3.6 THRESHOLD BUILDINGS,
 OPERATING GUIDELINES FOR THRESHOLD INSPECTORS #26.
 ASSURE THAT THE DESIGNER HAS REQUIRED ON THE PLANS OR
 SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING
 PENETRATIONS, FOR WALLS AND CEILINGS.
  
 4) PROVISO. THIS PROPERTY IS LOCATED IN A AE FLOOD
 ZONE. THE BASE FLOOD ELEVATION IS 12.7 FT. NAVD 88 PLUS
 2 FEET OR A FINISH FLOOR ELEVATION MINIMUM OF 14.77
 NAVD 88.
 ARTICLE XVII ORDINANCES ARTICLE XVII FLOOD PREVENTION &
 CONTROL
 FBC BUILDING 1612 AND CITY OF WPB CODE OF SECTION
 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A
 FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE
 REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS
 AFTER OCT. 11/ 2017 AN ADDITIONAL ONE FOOT OF FREE
 BOARD WILL BE REQUIRED OR (2) FEET ABOVE BASE FLOOD.
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 4) (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF
 THE PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH
 FLOOR HEIGHT. W. P. B. ADMINISTRATIVE CODE 107.3.5.1.1
 BUILDING MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL
 BUILDINGS. ( 8) FLOOD REQUIREMENTS ELEVATIONS,
 ENCLOSURES, FLOOD DAMAGE-RESISTANT MATERIALS.
  
 4) (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED. W. P. B.
 ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS 1.2
 FLOOR/ SLAB INSPECTION. IN FLOOD HAZARD AREAS, UPON
 PLACEMENT OF THE LOWEST FLOOR, INCLUDING BASEMENT, AND
 PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE ELEVATION
 CERTIFICATION, REQUIRED IN SECTION 1612.5, SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL.
  
 4) (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF
 OCCUPANCY OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD
 ZONE CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL
 EXTERIOR ATTENDANTS A/C PADS OR OTHER SLABS FOR
 GENERATORS.
 W. P. B. ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS
 (6) FINAL INSPECTION. TO BE MADE AFTER THE BUILDING IS
 COMPLETED AND READY FOR OCCUPANCY. 6.1. LOWEST FLOOR
 ELEVATION. IN FLOOD HAZARD AREAS, AS PART OF THE FINAL
 INSPECTION, A FINAL CERTIFICATION OF THE LOWEST FLOOR
 ELEVATION SHALL BE SUBMITTED TO THE AUTHORITY HAVING
 JURISDICTION.
 FEMA NEW FORM AVAILABLE JUNE 13/2016.
 OMB NO. 1660-0008
 EXPIRATION DATE: NOV. 30/2018
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 5) COMPLIED.
 5A) COMPLIED.
 5B) COMPLIED.
 5C) COMPLIED.
 5D) COMPLIED.
 5E) NOTICE ONLY. THE SOILS REPORT INDICATES THERE ARE
 TO BE 160 FOOT TALL POLES WITH NETTING TO CATCH THE
 GOLF BALLS. THE POLES AND NETTING ARE NOT PART OF THIS
 PERMIT AND WILL REQUIRE A SEPARATE PERMIT REVIEW AND
 ASSOCIATED FEES. IN THE ANALYSIS FOR THE POLES IT WILL
 NEED TO BE MADE CLEAR IF THE NETTING IS TO BE DROPPED
 WHEN A HIGH WIND EVENT WILL OCCUR. NOTE THIS ALSO NEEDS
 TO BE INCORPORATED INTO THE O & M MANUAL.
 1ST REVIEW. THIS REVIEW NO SOILS REPORTS WERE FOUND IN
 THE FILE FOLDER. 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL.
 WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY
 OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 6A-D) COMPLIED.
  
 7A-G) COMPLIED.
  
 8A-H) COMPLIED. 004- LS-01 LIFE SAFETY PLAN.
 NEW COMMENTS.
 1) FBC 1014.3 SHOW THE COMMON PATHS OF EGRESS TRAVEL
 AND THEIR DISTANCES ON THE LIFE SAFETY PLANS.
 2) ON SHEET 004-LS-01, CLARIFY THE 68" CLEAR DOOR
 LISTED IN THE EXIT CAPACITY SUMMARY AT LEVEL 2 FOR
 STAIR #3. FBC 107.2.1
 3) REVISE THE NOTES FOR THE DOORS ON THE HOLD OPEN
 DEVICES AT STAIR #3. THESE DOORS SHOULD BE OPENABLE
 FROM THE PANTRY SIDE AND SHOULD BE USED AS EXIT EGRESS
 DOORS FROM THOSE AREAS. THE ONLY OPENINGS INTO EXIT
 ACCESS STAIRWAYS ENCLOSURE ARE THOSE NECESSARY FOR THE
 PURPOSE OF THE STAIRWAY. FBC 1009.3.1.4.1 THE FIRE
 DEPARTMENT DOES NOT WANT THESE DOORS TO BE OPENABLE
 FROM THE STAIRWAY SIDE.
 4) THE EXIT SIGN ON THE GROUND FLOOR DIRECTING THE
 GROUND FLOOR OCCUPANTS INTO STAIR #4 SHOULD BE REMOVED.
 THE OCCUPANTS OF THE FIRST FLOOR WILL USE THE EXIT DOOR
 THAT OPENS TO THE EXTERIOR OF THE BUILDING. THE
 OCCUPANTS FROM THE SECOND AND THIRD LEVELS USING STAIR
 #3 WILL USE THIS SAME DOOR TO EXIT THE BUILDING.
 OTHERWISE, THE OCCUPANTS OF THE UPPER LEVELS MAY
 ATTEMPT TO EXIT THROUGH STAIR #4 AND CONVERGE WITH THE
 OCCUPANTS USING THIS STAIR.
 5) THE LIFE SAFETY PLAN ON SHEET 004-LS-01 DOES NOT
 SHOW THE FIRE RATED WALLS ON ALL SIDES OF STAIR #S 1
 AND 4, AS THEY ARE ON SHEETS 206-A2-01-A AND
 206-A2-01-B. CLARIFY.
  
 9) 004- LS-01 LIFE SAFETY PLAN AND FURNITURE PLANS.
 NEITHER OF THESE PLANS SHOW COMPLIANCE WITH THE
 ACCESSIBILITY CODE:
 NEW COMMENTS. THE ADA BAR AREA IS NOT IDENTIFIED AT THE
 UPPER LEVEL BAR ONT SHEET 210-A2-01-B. PROVIDE
 DIMENSIONS ON THE BAR ELEVATION DRAWINGS TO SHOW THAT
 ADA PORTIONS OF THE BARS ARE IN COMPLIANCE AND SHOW THE
 CLEAR FLOOR SPACE AT THE BARS AND ANY FIXED SEATING.
  
 9A) 2ND REQUEST. 226.1 WHERE DINING SURFACES ARE
 PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST
 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902.
  
 9B) 2ND REQUEST. 226.2 DISPERSION. DINING SURFACES AND
 WORK SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE
 DISPERSED THROUGHOUT THE SPACE OR FACILITY CONTAINING
 DINING SURFACES AND WORK SURFACES.
  
 9C) 2ND REQUEST. SEMI-COMPLIED. THE PLANS DO SHOW A
 DROPPED PORTION OF THE BARS FOR ACCESSIBLE DRINKING
 AREA.
 NEW COMMENTS. PROVIDE DIMENSIONS ON THE BAR ELEVATION
 DRAWINGS TO SHOW THAT ADA PORTIONS OF THE BARS ARE IN
 COMPLIANCE AND SHOW THE CLEAR FLOOR SPACE AT THE BARS
 AND ANY FIXED SEATING.
  
 1ST ROUND COMMENT. 902.1 .DINING SURFACES AND WORK
 SURFACES SHALL COMPLY WITH 902.2 AND 902.3. ADVISORY
 902.1 GENERAL. DINING SURFACES INCLUDE, BUT ARE NOT
 LIMITED TO, BARS, TABLES, LUNCH COUNTERS, AND BOOTHS.
 9C)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
 9C)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 10A-E) COMPLIED.
  
 10E) COMPLIED. 206.2.15 GOLF FACILITIES.
  
 11A-C)COMPLIED. EMERGENCY OVER FLOW SCUPPERS &
 SECONDARY (EMERGENCY OVERFLOW) DRAINS OR SCUPPERS.
  
 12-23) BUILDING PROVISO: THE DESIGNER OF RECORD WISHES
 TO DEFER THE PRODUCT APPROVALS UNTIL AFTER PERMIT
 ISSUANCE. SEE THE COVERSHEET 003-CS-1.
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (G) PRE-ENGINEERED A/C STANDS
  
 24) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 ONE SET OF PLANS WILL HAVE TO BE TAKEN (BY THE
 CONTRACTOR OR REPRESENTATIVE) TO THE PALM BEACH COUNTY
 IMPACT FEE OFFICE LOCATED AT 2300 N. JOG RD. ROOMS
 2W01-2W14 WEST PALM BEACH, FL. THE ACTUAL PERMIT SET OF
 PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE
 PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE
 CALL (561)233-5025 FOR MORE INFORMATION.
  
 25) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
  
  