| 2018-04-03 10:05:52 | |
| | 2ND REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: PREVIOUS COMMENTS |
| | |
| | PARTIALLY COMPLIED 6. PLEASE PROVIDE A LABELING SYSTEM |
| | FOR THE SANITARY, WATER AND GAS THAT WILL SHOW A |
| | COHESIVE CORRELATION BETWEEN THE RISER?S ISOMETRIC |
| | DRAWINGS AND FLOOR PLANS. PER WPB AMEND TO THE FBC |
| | 107.2.1 |
| | THE ISOMETRIC DRAWINGS ARE STILL EXTREMELY CONFUSING I |
| | CANNOT DETERMINE CODE COMPLIANCE. PER WPB AMEND TO FBC |
| | 2017 SEC 107.2.1 CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | A) THE TAGS ON THE SANITARY STACKS ON THE FLOOR PLAN |
| | ARE ALL LABELLED THE SAME WITH THE KEY NOTE NUMBER |
| | PLEASE TAG WITH INDIVIDUAL NUMBERS OR LETTERS THAT CAN |
| | BE FOUND ON THE ISOMETRIC DRAWINGS. |
| | B) ON THE ENLARGED ISOMETRIC DRAWINGS THE INDIVIDUAL |
| | PIPES NEED TO BE LABELED MATCH TO THE PIPE IT IS |
| | CONNECTED TO ON OTHER ISOMETRICS THE ONES SHOWN NOW |
| | JUST INDICATE OTHER ISOMETRIC NOT INDIVIDUAL PIPES. |
| | C) THE OVERALL ISOMETRIC ON SHT P7-3 NEEDS TO BE SPLIT |
| | UP AND ENLARGED ALSO THE FIXTURE AND SOIL STACKS NEED |
| | TO BE LABELED. |
| | D) ON ALL THE ISOMETRIC DRAWING PLEASE REMOVE ALL STRAY |
| | PIPING THAT IS NOT SHOWN TO CONNECT ANYWHERE OR LABEL |
| | IT. |
| | E) THE ENLARGED ISOMETRIC DRAWING ARE STILL TO COMPACT |
| | PLEASE ENLARGE. |
| | |
| | PARTIALLY COMPLIED 8. PROVIDE A COMPLETE SANITARY AND |
| | GREASE ISOMETRIC FOR THE SECOND AND THIRD FLOOR SHOWING |
| | THE KITCHEN, BATHROOMS AND BAR AREAS, ON THE BRANCHES |
| | FOR EACH AREA YOU CAN LABEL IT TO COINCIDE TO THE |
| | ENLARGED ISOMETRIC DRAWING INSTEAD OF DRAWING THE AREA |
| | TWICE. PER WPB AMEND TO THE FBC 107.2.1 |
| | PLEASE LABEL GREASE AND SANITARY SEPARATELY. |
| | |
| | PARTIALLY COMPLIED 12. PLEASE PROVIDE SIZING |
| | CALCULATIONS FOR THE GREASE INTERCEPTORS. . PER WPB |
| | AMEND TO THE FBC 107.2.1 |
| | THE SIZING CALCULATIONS FOR THE GREASE INTERCEPTOR |
| | APPEAR TO BE INCOMPLETE PLEASE PROVIDE THE WASTE WATER |
| | FACTOR AND THE LOAD FACTOR. I CANNOT DETERMINE HOW YOUR |
| | CALCULATION FIGURES OUT TO 3305 GAL PLEASE CLARIFY. |
| | |
| | NEW COMMENTS: |
| | |
| | 1. IS THE ELEVATOR A TRACTION TYPE OR HYDRAULIC IF IT |
| | IS HYDRAULIC AN OIL SEPARATOR IS REQUIRED OR AN OIL |
| | ALARM SYSTEM. PER FBC PL 1003.4 |
| | 2. SHT. P0-1 NOTE #1 THE PLUMBING SHALL BE DESIGNED AND |
| | SIZED PER THE 2014 FBC PLUMBING 5TH EDITION THE 2012 IS |
| | SHOWN. |
| | 3. MAXIMUM SIZE OF THE GREASE INTERCEPTOR PER WPB |
| | UTILITIES IS 1250 GAL YOU CAN CONTACT JEFFERY ODOMS PH |
| | # 561-822-2172 OR [email protected] |
| | 4. SHT. P4-2 THE 6? HORIZONTAL OVERFLOW STORM DRAIN |
| | PIPING WITH 5700 + 5740 SQFT IS UNDERSIZED @ 1/8 FT. |
| | THE MAX FOR 6? IS 4280SQFT.PER FBC PL TABLE 1106.3 |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |