Plan Review Notes
Plan Review Notes For Permit 17120261
Permit Number 17120261
Review Stop B
Sequence Number 2
Notes
Date Text
2018-04-06 15:12:28E-MAIL SENT TO MR. FRED HENDERSON 04/06/2018 03:11 PM
 630 K ATTACHMENT
 APRIL 06/2018
 W. P. B. DRIVE SHACK
 ADDRESS 1600 BELVEDERE RD.
 PERMIT: 17120261
  
 TO: MR. FRED HENDERSON,
  
 THE CITY IS IN RECEIPT OF THE SUBMITTED THRESHOLD
 INSPECTION PLAN. THE CITY HAS REVIEWED YOUR THRESHOLD
 INSPECTION PLAN AND FOUND EVERYTHING IN THE THRESHOLD
 INSPECTION PLAN AS WELL AS IN THE STRUCTURAL PLANS
 REFERS BACK TO SECTIONS 1704 AND OR 1705 OF THE IBC.
 PLEASE NOTE UNDER THE 2014 OR THE 2017 FBC-B THESE
 SECTIONS ARE RESERVED. FLORIDA STATUTE 553.79(5) STATES
 THE STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO AND
 APPROVED BY THE ENFORCING AGENCY BEFORE THE ISSUANCE OF
 A BUILDING PERMIT FOR THE CONSTRUCTION OF A THRESHOLD
 BUILDING. WE HAVE HAD THE BUILDING OFFICIAL AND ONE OF
 OUR ASSISTANT BUILDING OFFICIALS LOOK AT THE SUBMITTED
 DOCUMENT AND FOUND IT LACKING. THE PURPOSE OF THE
 STRUCTURAL INSPECTION PLAN IS TO PROVIDE SPECIFIC
 INSPECTION PROCEDURES AND SCHEDULES SO THAT THE
 BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 PLEASE REFER TO THE THRESHOLD INSPECTION PLAN THAT HAS
 BEEN SUBMITTED TO THE CITY AND APPROVED. THE ONLY THING
 THAT WE WOULD RECOMMEND IN REGARDS TO A THRESHOLD
 INSPECTION PLAN WE WOULD PREFER TO ALSO HAVE THE
 BUILDING TYPE, OCCUPANCY AND USE, STORIES OF BUILDING
 AND IF FIRE SPRINKLERED.
  
 SEE THE NEXT SHEET FOR A SAMPLE OF A THRESHOLD
 INSPECTION PLAN.
  
 THRESHOLD INSPECTION . PDF
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
2018-03-29 16:57:142ND REVIEW / 2014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17120261
 ADD: 1600 BELVEDERE RD.
 CONT: TBD/ TO BE DETERMINED
 TEL: NOT GIVEN ON PERMIT APPLICATION
 E-MAIL: NOT GIVEN ON THE PERMIT APPLICATION
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: WED.-THURS. MARCH 28-29/2018
 ACTION: DENIED
  
 1) PROVISO: ART IN PUBLIC PLACES. THE CITY OF WEST PALM
 BEACH ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT
 APPLIES TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR
 WHICH THE PERMIT APPLICATION WAS SUBMITTED AFTER
 6/29/14, AND THE TOTAL PROJECT CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $750,000 WILL NEED TO COMPLY
 WITH THIS ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE
 DEVELOPMENT.
 (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND
 THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL
 PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW
 CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN
 EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS
 WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED
 CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES
 REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED
 SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF
 THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW
 CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 2) 2ND ROUND COMMENT. WE HAVE CALCULATED THE VALUE OF
 THE BUILDING USING THE ICC TABLES FROM AUGUST 01/2017.
 THERE IS NO A5 CLASS IN THE TABLES; THE CLOSEST USE IS
 A4 ARENAS.
 68,885.0 SQ. FT.
 X 190.84 BUILDING TYPE II-B
 $13,146,013.00 IN VALUE CALCULATED VALUE
 PLEASE PROVIDE AN ITEMIZED LIST OF THE SUB-PERMITS NOT
 COVERED UNDER THE MAIN PERMIT AND DEDUCT THERE VALUE
 FROM THE OVERALL CALCULATED VALUE OF THE BUILDING. THIS
 WILL BECOME THE NEW ADJUSTED VALUE OF THE BUILDING
 PERMIT.
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME PERMIT
  
 1ST ROUND OF COMMENTS. 108.3* BUILDING PERMIT
 VALUATION. PLEASE NOTE THE BUILDING VALUATION SEEMS A
 LITTLE LOW. THE CODE SUMMARY SHEET CS-1 UNDER THE
 HEADING BUILDING DATA LIST THE SQUARE FOOTAGE PER FLOOR
 BUT NOT THE SQUARE FOOTAGE PER OCCUPANCY TYPE. THE ICC
 EVALUATION TABLES USES BUILDING TYPE, OCCUPANCY TYPE
 AND SQUARE FOOTAGE TO DETERMINE THE VALUATION OF THE
 BUILDING.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME PERMIT
  
 3) THIS BUILDING IS TO BE CONSIDERED A THRESHOLD
 BUILDING BY DEFINITION. THRESHOLD BUILDING / FL S. S.
 553.71(7) ?THRESHOLD BUILDING" MEANING ANY BUILDING
 WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT,
 OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS
 DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000
 SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN
 500 PERSONS.
  
 3A) 2ND REQUEST. 109.3.6.1 THRESHOLD INSPECTION PLAN.
 THE ENFORCING AGENCY SHALL REQUIRE A (WRITTEN/ TYPED)
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 3B) 2ND REQUEST. THRESHOLD INSPECTOR: WPB AMENDMENT
 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY FL S 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE. THE
 THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE FILED OUT
 BY ALL PARTIES WITH INTEREST, NOTARIZED AND RETURNED TO
 THIS OFFICE, AND REVIEWED AND APPROVED BEFORE PERMIT
 ISSUANCE WILL TAKE PLACE.
  
 FORMS WERE E-MAILED TO: [email protected] 1/24/2018
 2:30PM.
  
  
 3C) COMPLIED. W.P.B. AMENDMENT 110.3.7.4.4 . 633
 FLORIDA STATUTE.
  
 3D)SEMI-COMPLIED. IN THE DOCUMENT FILE DOCUMENTS HAD
 BEEN UPLOADED FOR DONALD G BELLAMY, JR. P. E. , S. I.
 FOR LICENSING AND RESUME (UNIVERSAL ENGINEERING
 SERVICES, INC.). WHAT WE DID NOT SEE WERE HIS DESIGNEES
 LICENSED UNDER PART XII OF CHAPTER 468, FLORIDA
 STATUTES AND THEIR RESUMES. 110.3.7.6 THE BUILDING
 DEPARTMENT MAY ALLOW A SPECIAL INSPECTOR TO CONDUCT THE
 MINIMUM STRUCTURAL INSPECTION OF THRESHOLD BUILDINGS
 REQUIRED BY THIS CODE, SECTION 553.73, FLORIDA
 STATUTES, WITHOUT DUPLICATIVE INSPECTION BY THE
 BUILDING DEPARTMENT. THE BUILDING
 OFFICIAL IS RESPONSIBLE FOR ENSURING THAT ANY PERSON
 CONDUCTING INSPECTIONS IS QUALIFIED AS A BUILDING
 INSPECTOR UNDER PART XII OF CHAPTER 468, FLORIDA
 STATUTES, OR CERTIFIED AS A SPECIAL INSPECTOR UNDER
 CHAPTER 471 OR 481, FLORIDA STATUTES. INSPECTIONS OF
 THRESHOLD BUILDINGS REQUIRED BY SECTION 553.79(5),
 FLORIDA STATUTES, ARE IN ADDITION TO THE MINIMUM
 INSPECTIONS REQUIRED BY THIS CODE.
  
 1ST ROUND OF COMMENTS. FOR THE SPECIAL INSPECTOR PLEASE
 PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS
 PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL
 CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL
 OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE
 RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED.
 UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED
 FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA.
  
 3E) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB
 SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 3F) NOTICE ONLY: FOR DIGITAL PLANS, AFTER PERMIT
 ISSUANCE, PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE
 PERMIT BEING ISSUED, THE PERMIT LIBRARIAN WILL THEN
 E-MAIL YOU THE APPROVED AND BATCH STAMPED PLANS SO YOU
 MAY PRINT YOUR PLANS, TWO SETS OF PLANS WILL NEED TO BE
 PRINTED IN COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE
 OTHER FOR THE MEP INSPECTORS OTHER PLANS YOU WISH TO
 PRINT MAYBE IN BLACK & WHITE..
 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 3G) PROVISO/ NOTICE ONLY. 110.3.7.4.3 ALL SHORING AND
 RESHORING PROCEDURES, PLANS AND DETAILS SHALL BE
 SUBMITTED TO THE ENFORCEMENT AGENCY FOR RECORDKEEPING.
 EACH SHORING AND RESHORING INSTALLATION SHALL BE
 SUPERVISED, INSPECTED AND CERTIFIED TO BE IN COMPLIANCE
 WITH THE SHORING DOCUMENTS BY THE CONTRACTOR.
  
 3H) PROVISO/ NOTICE ONLY. PLEASE CALL THE CITY OF WEST
 PALM BEACHS AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR ALL BUILDING INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN
 6 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 3I) PROVISO/ NOTICE ONLY. 109.3.6 THRESHOLD BUILDINGS,
 OPERATING GUIDELINES FOR THRESHOLD INSPECTORS #26.
 ASSURE THAT THE DESIGNER HAS REQUIRED ON THE PLANS OR
 SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING
 PENETRATIONS, FOR WALLS AND CEILINGS.
  
 4) 2ND REQUEST. THIS PROPERTY IS LOCATED IN A AE FLOOD
 ZONE. THE BASE FLOOD ELEVATION IS 12.7 FT. NAVD 88 PLUS
 2 FEET OR A FINISH FLOOR ELEVATION MINIMUM OF 14.77
 NAVD 88.
 ARTICLE XVII ORDINANCES ARTICLE XVII FLOOD PREVENTION &
 CONTROL
 FBC BUILDING 1612 AND CITY OF WPB CODE OF SECTION
 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A
 FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE
 REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS
 AFTER OCT. 11/ 2017 AN ADDITIONAL ONE FOOT OF FREE
 BOARD WILL BE REQUIRED OR (2) FEET ABOVE BASE FLOOD.
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 4) (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF
 THE PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH
 FLOOR HEIGHT. W. P. B. ADMINISTRATIVE CODE 107.3.5.1.1
 BUILDING MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL
 BUILDINGS. ( 8) FLOOD REQUIREMENTS ELEVATIONS,
 ENCLOSURES, FLOOD DAMAGE-RESISTANT MATERIALS.
  
 4) (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED. W. P. B.
 ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS 1.2
 FLOOR/ SLAB INSPECTION. IN FLOOD HAZARD AREAS, UPON
 PLACEMENT OF THE LOWEST FLOOR, INCLUDING BASEMENT, AND
 PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE ELEVATION
 CERTIFICATION, REQUIRED IN SECTION 1612.5, SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL.
  
 4) (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF
 OCCUPANCY OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD
 ZONE CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL
 EXTERIOR ATTENDANTS A/C PADS OR OTHER SLABS FOR
 GENERATORS.
 W. P. B. ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS
 (6) FINAL INSPECTION. TO BE MADE AFTER THE BUILDING IS
 COMPLETED AND READY FOR OCCUPANCY. 6.1. LOWEST FLOOR
 ELEVATION. IN FLOOD HAZARD AREAS, AS PART OF THE FINAL
 INSPECTION, A FINAL CERTIFICATION OF THE LOWEST FLOOR
 ELEVATION SHALL BE SUBMITTED TO THE AUTHORITY HAVING
 JURISDICTION.
 FEMA NEW FORM AVAILABLE JUNE 13/2016.
 OMB NO. 1660-0008
 EXPIRATION DATE: NOV. 30/2018
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 5) 2ND REVIEW. SOILS REPORT BY ESC FLORIDA, LLC. JOSE
 N. GOMEZ P. E. D.GE SEAL AND COPIED SIGNATURE AND DATE
 ARE ON PAGE 2 OF THE REPORT. WILL NEED TO SEND (1)
 ORIGINAL PAPER SOILS REPORT, IT WILL BE KEPT WITH OTHER
 PAPER DOCUMENTS FOR SEAL AND SIGNATURE PURPOSES OR SHOW
 COMPLIANCE WITH:
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
 61G15-23.002(2)(B) FL. ADMIN. CODE. A COVER SHEET WITH
 LISTED PAGES OR INDEX SHEET FOR ENGINEERING
 SPECIFICATIONS MAY BE USED AND THAT SHEET MUST BE
 SIGNED IN RESPONSIBLE CHARGE OF THE PRODUCTION &
 PREPARATION OF EACH SECTION OF THE ENGINEERING
 SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER
 SHEET OR INDEX LISTING HOW MANY PAGES ARE COVERED UNDER
 THE COVER SHEET OR INDEX SHEET.
  
 5A) WITHIN THE SOILS REPORT ON PAGE 11 TABLE 5.1.1.1
 FOUNDATION DESIGN THE TABLE LIST A NET ALLOWABLE
 BEARING PRESSURE OF 3,000 PSF FOR BOTH COLUMN AND WALL
 FOOTINGS. THE TABLE ALSO LIST A MINIMUM FOOTING
 EMBEDMENT DEPTH (BELOW SLAB OR FINISH GRADE) OF 48
 INCHES FOR BOTH COLUMN AND WALL FOOTINGS. THE QUESTION
 IS HAS THE STRUCTURAL ENGINEER OF RECORD REVIEWED THESE
 RECOMMENDATIONS? OR IS THERE OTHER REASONS THEY ARE NOT
 OF CONCERN AS OF FROST LINE PER 2014 FBC-B 1809.5 FROST
 PROTECTION? 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 SHEET 309-S2-01A NOTE 3 2 INDICATES THE TOP OF
 FOUNDATION ELEVATION IS (-) 2 FEET UNLESS OTHERWISE
 NOTED.
 SHEET 320-S4-11 UNDER THE FOOTING SCHEDULE LIST
 FOOTINGS F1-F7. FOOTINGS F4,F5, & F6 WILL ALWAYS COMPLY
 WITH THE 4 FOOT FOOTING DEPTH. FOOTINGS F1, F2, F3, &
 F7 WILL ALL BE ABOVE THE REQUIRED 4 FOOT DEPTH.
  
 5B) IN REVIEWING FOR THE FOOTING DEPTHS ON SHEET
 309-S2-01A NOTE # 1 INDICATES THE CIVIL DRAWINGS
 ELEVATION OF 182.00 FEET. PLEASE CORRECT THE ELEVATION,
 THIS PROJECT IS IN AN A FLOOD ZONE.
  
 5C) IN REVIEWING FOR THE FOOTING DEPTHS ON SHEET
 309-S2-01A THERE IS A NOTE BY GRID LINES 22/C.8 FOR
 VERTICAL REBAR MISSING THE SIZE AND SPACING OF THE
 REBAR. 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED.
  
 5D) THE SOILS REPORT ON PAGES 10 & 11 HIGHLY RECOMMENDS
 CONDUCTING TEST PITS, AND OR OTHER GEOPHYSICAL
 TECHNIQUES TO DETERMINE THE PRESENCE OF AND DELINEATE
 THE EXTENTS OF BURIED CONCRETE, METALS, PLASTICS AND
 GLASS DEBRIS AT THE EASTERN PORTION OF THE SITE, AS
 THESE DELETERIOUS MATERIALS WILL NEED TO BE ADDRESSED
 DURING THE EARTHWORK OPERATIONS PRIOR TO START OF
 CONSTRUCTION. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED, PLEASE PROVIDE A RESPONSE.
  
 5E) NOTICE ONLY. THE SOILS REPORT INDICATES THERE ARE
 TO BE 160 FOOT TALL POLES WITH NETTING TO CATCH THE
 GOLF BALLS. THE POLES AND NETTING ARE NOT PART OF THIS
 PERMIT AND WILL REQUIRE A SEPARATE PERMIT REVIEW AND
 ASSOCIATED FEES. IN THE ANALYSIS FOR THE POLES IT WILL
 NEED TO BE MADE CLEAR IF THE NETTING IS TO BE DROPPED
 WHEN A HIGH WIND EVENT WILL OCCUR. NOTE THIS ALSO NEEDS
 TO BE INCORPORATED INTO THE O & M MANUAL.
 1ST REVIEW. THIS REVIEW NO SOILS REPORTS WERE FOUND IN
 THE FILE FOLDER. 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL.
 WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY
 OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 6A) 2ND REQUEST. RESPONSE INDICATES THE REQUEST FOR
 ALTERNATE MATERIALS, DESIGN AND METHODS OF CONSTRUCTION
 HAS ALREADY BEEN MADE TO ROBERT BROWN THE BUILDING
 OFFICIAL. I SPOKE WITH MR. BROWN YESTERDAY AND HE HAS
 NOT SEEN ANY WRITTEN REQUEST FOR COMPLIANCE THROUGH
 104.11 ALTERNATIVE MATERIALS, DESIGN AND METHODS OF
 CONSTRUCTION AND EQUIPMENT FOR NETTING TO COMPLY WITH
 FALL PROTECTION. IT IS IN PDF FORM UNDER THE PROJECT
 DOCS PROGRAM INFORMATION FOLDER.
  
 1ST ROUND OF COMMENTS. FALL PROTECTION PDF. ATTACHMENT
 1 HITTING BAY. UNDER THE 2014 FBC-B, THE CODE DOES NOT
 INCLUDE RAISED GOLFING PLATFORMS AS EXEMPT LOCATIONS TO
 THE REQUIREMENT FOR GUARDS AND OR GUARDRAILS SEE FBC-B
 1013.2 WHERE REQUIRED. I WOULD RECOMMEND THAT YOU
 SHOULD MAKE A WRITTEN REQUEST TO THE BUILDING OFFICIAL
 ROBERT BROWN REQUESTING THE FALL PROTECTION PDF TO BE
 CONSIDERED UNDER THE:
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION SECTION 104.11 ALTERNATIVE MATERIALS,
 DESIGN AND METHODS OF CONSTRUCTION AND EQUIPMENT. THE
 PROVISIONS OF THIS CODE ARE NOT INTENDED TO PREVENT THE
 INSTALLATION OF ANY MATERIAL OR TO PROHIBIT ANY DESIGN
 OR METHOD OF CONSTRUCTION NOT SPECIFICALLY PRESCRIBED
 BY THIS CODE, PROVIDED THAT
 ANY SUCH ALTERNATIVE HAS BEEN APPROVED. AN ALTERNATIVE
 MATERIAL, DESIGN OR METHOD OF CONSTRUCTION SHALL BE
 APPROVED WHERE THE BUILDING OFFICIAL FINDS THAT THE
 PROPOSED DESIGN IS SATISFACTORY AND COMPLIES WITH THE
 INTENT OF THE PROVISIONS OF THIS CODE, AND THAT THE
 MATERIAL, METHOD OR WORK OFFERED IS, FOR THE PURPOSE
 INTENDED, AT LEAST THE EQUIVALENT OF THAT PRESCRIBED IN
 THIS CODE IN QUALITY, STRENGTH, EFFECTIVENESS, FIRE
 RESISTANCE, DURABILITY AND SAFETY. WHEN ALTERNATE LIFE
 SAFETY SYSTEMS ARE DESIGNED, THE SFPE ENGINEERING GUIDE
 TO PERFORMANCE-BASED FIRE PROTECTION ANALYSIS AND
 DESIGN OF BUILDINGS, OR OTHER METHODS APPROVED BY THE
 BUILDING OFFICIAL MAY BE USED. THE BUILDING OFFICIAL
 SHALL REQUIRE THAT SUFFICIENT EVIDENCE OR PROOF BE
 SUBMITTED TO SUBSTANTIATE ANY CLAIM MADE REGARDING THE
 ALTERNATIVE.
  
 6B) 2ND REQUEST. RESPONSE INDICATES THE REQUEST FOR
 ALTERNATE MATERIALS, DESIGN AND METHODS OF CONSTRUCTION
 HAS ALREADY BEEN MADE TO ROBERT BROWN THE BUILDING
 OFFICIAL. I SPOKE WITH MR. BROWN YESTERDAY AND HE HAS
 NOT SEEN ANY WRITTEN REQUEST FOR COMPLIANCE THROUGH
 104.11 ALTERNATIVE MATERIALS, DESIGN AND METHODS OF
 CONSTRUCTION AND EQUIPMENT FOR NETTING TO COMPLY WITH
 FALL PROTECTION. IT IS IN PDF FORM UNDER THE PROJECT
 DOCS PROGRAM INFORMATION FOLDER.
 1ST ROUND OF COMMENTS. 104.11.1 RESEARCH REPORTS.
 SUPPORTING DATA, WHERE NECESSARY TO ASSIST IN THE
 APPROVAL OF MATERIALS OR ASSEMBLIES NOT SPECIFICALLY
 PROVIDED FOR IN THIS CODE, SHALL CONSIST OF VALID
 RESEARCH REPORTS FROM APPROVED SOURCES.
  
 6C) 2ND REQUEST. RESPONSE INDICATES THE REQUEST FOR
 ALTERNATE MATERIALS, DESIGN AND METHODS OF CONSTRUCTION
 HAS ALREADY BEEN MADE TO ROBERT BROWN THE BUILDING
 OFFICIAL. I SPOKE WITH MR. BROWN YESTERDAY AND HE HAS
 NOT SEEN ANY WRITTEN REQUEST FOR COMPLIANCE THROUGH
 104.11 ALTERNATIVE MATERIALS, DESIGN AND METHODS OF
 CONSTRUCTION AND EQUIPMENT FOR NETTING TO COMPLY WITH
 FALL PROTECTION. IT IS IN PDF FORM UNDER THE PROJECT
 DOCS PROGRAM INFORMATION FOLDER.
  
 1ST ROUND OF COMMENTS. 104.11.2 TESTS. WHENEVER THERE
 IS INSUFFICIENT EVIDENCE OF COMPLIANCE WITH THE
 PROVISIONS OF THIS CODE, OR EVIDENCE THAT A MATERIAL OR
 METHOD DOES NOT CONFORM TO THE REQUIREMENTS OF THIS
 CODE, OR IN ORDER TO SUBSTANTIATE CLAIMS FOR
 ALTERNATIVE MATERIALS OR METHODS, THE BUILDING
 OFFICIAL SHALL HAVE THE AUTHORITY TO REQUIRE TESTS AS
 EVIDENCE OF COMPLIANCE TO BE MADE AT NO
 EXPENSE TO THE JURISDICTION. TEST METHODS SHALL BE AS
 SPECIFIED IN THIS CODE OR BY OTHER
 RECOGNIZED TEST STANDARDS. IN THE ABSENCE OF RECOGNIZED
 AND ACCEPTED TEST METHODS, THE
 BUILDING OFFICIAL SHALL APPROVE THE TESTING PROCEDURES.
 TESTS SHALL BE PERFORMED BY AN APPROVED
 AGENCY. REPORTS OF SUCH TESTS SHALL BE RETAINED BY THE
 BUILDING OFFICIAL FOR THE PERIOD REQUIRED
 FOR RETENTION OF PUBLIC RECORDS.
  
 6D) 2ND REQUEST. RESPONSE INDICATES THE REQUEST FOR
 ALTERNATE MATERIALS, DESIGN AND METHODS OF CONSTRUCTION
 HAS ALREADY BEEN MADE TO ROBERT BROWN THE BUILDING
 OFFICIAL. I SPOKE WITH MR. BROWN YESTERDAY AND HE HAS
 NOT SEEN ANY WRITTEN REQUEST FOR COMPLIANCE THROUGH
 104.11 ALTERNATIVE MATERIALS, DESIGN AND METHODS OF
 CONSTRUCTION AND EQUIPMENT FOR NETTING TO COMPLY WITH
 FALL PROTECTION. IT IS IN PDF FORM UNDER THE PROJECT
 DOCS PROGRAM INFORMATION FOLDER.
 1ST ROUND OF COMMENTS. 104.11.3 ACCESSIBILITY.
 ALTERNATIVE DESIGNS AND TECHNOLOGIES FOR PROVIDING
 ACCESS TO AND USABILITY OF A FACILITY FOR PERSONS WITH
 DISABILITIES SHALL BE IN ACCORDANCE WITH PROVISIONS OF
 THE FLORIDA BUILDING CODE, ACCESSIBILITY.
  
 7) SHEET 003 CS-1 CODE SUMMARY:
  
 7A-C) COMPLIED.
  
 7D)SEMI- COMPLIED. HEADING: ACCESSIBLE PARKING
 REQUIREMENTS CHART. SIGNAGE IS REQUIRED FOR THE VAN
 ACCESSIBLE PARKING, EVEN THOUGH IT IS NOT IN A PARKING
 GARAGE, FOR EVERY 6 OR FRACTION THERE OF A VAN
 ACCESSIBLE SPACE NEEDS TO BE DECLARED WITH SIGNAGE.
  
 FBC-ACCESSIBILITY CODE: ADVISORY 208.2 MINIMUM NUMBER.
 THE TERM ?PARKING FACILITY? IS USED SECTION 208.2
 INSTEAD OF THE TERM ?PARKING LOT? SO THAT IT IS CLEAR
 THAT BOTH PARKING LOTS AND PARKING STRUCTURES ARE
 REQUIRED TO COMPLY WITH THIS SECTION.
 2014 FBC-ACCESSIBILITY CODE 502.6 IDENTIFICATION.
 PARKING SPACE IDENTIFICATION SIGNS SHALL INCLUDE THE
 INTERNATIONAL SYMBOL OF ACCESSIBILITY COMPLYING WITH
 703.7.2.1. SIGNS IDENTIFYING VAN PARKING SPACES WHEN
 REQUIRED BY 502.2 SHALL CONTAIN THE DESIGNATION ?VAN
 ACCESSIBLE.?
  
  
  
 7E) COMPLIED. 9:30 AM. 3/30/3018. PRESSURES OK. PLEASE
 PROVIDE ALSO IN VASD SINCE THE PRODUCT APPROVALS ARE
 ALL IN VASD. THANK YOU WITH YOUR ANTICIPATED
 COOPERATION.
  
 7F-G) COMPLIED.
  
 8A-H) COMPLIED. 004- LS-01 LIFE SAFETY PLAN.
  
  
 9) 004- LS-01 LIFE SAFETY PLAN AND FURNITURE PLANS.
 NEITHER OF THESE PLANS SHOW COMPLIANCE WITH THE
 ACCESSIBILITY CODE:
 9A) 2ND REQUEST. 226.1 WHERE DINING SURFACES ARE
 PROVIDED FOR THE CONSUMPTION OF FOOD OR DRINK, AT LEAST
 5 PERCENT OF THE SEATING SPACES AND STANDING SPACES AT
 THE DINING SURFACES SHALL COMPLY WITH 902.
  
 9B) 2ND REQUEST. 226.2 DISPERSION. DINING SURFACES AND
 WORK SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE
 DISPERSED THROUGHOUT THE SPACE OR FACILITY CONTAINING
 DINING SURFACES AND WORK SURFACES.
  
 9C)2ND REQUEST. SEMI-COMPLIED. THE PLANS DO SHOW A
 DROPPED PORTION OF THE BARS FOR ACCESSIBLE DRINKING
 AREA.
 1ST ROUND COMMENT. 902.1 .DINING SURFACES AND WORK
 SURFACES SHALL COMPLY WITH 902.2 AND 902.3. ADVISORY
 902.1 GENERAL. DINING SURFACES INCLUDE, BUT ARE NOT
 LIMITED TO, BARS, TABLES, LUNCH COUNTERS, AND BOOTHS.
 9C)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 9C)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 10)COMPLIED.
 10A-C) COMPLIED.
  
 10D) SEE COMMENT 7D). 208.2.4 VAN PARKING SPACES. WHERE
 VAN PARKING IS PROVIDED PURSUANT TO SECTION 502.2, FOR
 EVERY SIX OR FRACTION OF SIX PARKING SPACES REQUIRED BY
 208.2 TO COMPLY WITH 502, AT LEAST ONE SHALL BE A VAN
 PARKING SPACE COMPLYING WITH 502.
  
 10E) COMPLIED. 206.2.15 GOLF FACILITIES.
  
 11A-C)COMPLIED. EMERGENCY OVER FLOW SCUPPERS &
 SECONDARY (EMERGENCY OVERFLOW) DRAINS OR SCUPPERS.
  
 12-23) BUILDING PROVISO: THE DESIGNER OF RECORD WISHES
 TO DEFER THE PRODUCT APPROVALS UNTIL AFTER PERMIT
 ISSUANCE. SEE THE COVERSHEET 003-CS-1.
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (G) PRE-ENGINEERED A/C STANDS
  
 24) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 ONE SET OF PLANS WILL HAVE TO BE TAKEN (BY THE
 CONTRACTOR OR REPRESENTATIVE) TO THE PALM BEACH COUNTY
 IMPACT FEE OFFICE LOCATED AT 2300 N. JOG RD. ROOMS
 2W01-2W14 WEST PALM BEACH, FL. THE ACTUAL PERMIT SET OF
 PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE
 PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE
 CALL (561)233-5025 FOR MORE INFORMATION.
  
 25) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  