Plan Review Notes
Plan Review Notes For Permit 17120261
Permit Number 17120261
Review Stop P-GREASE
Sequence Number 1
Notes
Date Text
2018-04-03 10:07:26 
 PARTIALLY COMPLIED 12. PLEASE PROVIDE SIZING
 CALCULATIONS FOR THE GREASE INTERCEPTORS. . PER WPB
 AMEND TO THE FBC 107.2.1
 THE SIZING CALCULATIONS FOR THE GREASE INTERCEPTOR
 APPEAR TO BE INCOMPLETE PLEASE PROVIDE THE WASTE WATER
 FACTOR AND THE LOAD FACTOR. I CANNOT DETERMINE HOW YOUR
 CALCULATION FIGURES OUT TO 3305 GAL PLEASE CLARIFY.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  