2018-01-25 09:52:30 
 1ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THIS PROJECT SHALL COMPLY WITH FBC PL 403.1.3 POTTY
 PARITY. IN ASSEMBLY OCCUPANCIES, RESTROOMS WHICH ARE
 OPEN TO THE PUBLIC MUST HAVE A RATIO OF 3:2 WATER
 CLOSETS PROVIDED FOR WOMEN AS THE COMBINED TOTAL OF
 WATER CLOSETS AND URINALS PROVIDED FOR MEN, UNLESS
 THESE ARE TWO OR FEWER SUCH FIXTURES FOR MEN, IN
 ACCORDANCE WITH SECTION 553.86, FLORIDA STATUTES.
  
 2. PLEASE PROVIDE A BREAKDOWN OF THE FIXTURE COUNT FOR
 EACH SPACE SUCH AS THE RESTAURANT SPACE AS A2 THE AREA
 OF THE DRIVING RANGE WOULD BE A4 AREAS SUCH AS STORAGE
 AND MECHANICAL / MAINTENANCE ROOMS WOULD BE S1. PER FBC
 PL TABLE 403.1 AND SEC 403.1.1
  
 3. SHT. A0-03 SHOW THE GRAB BARS MEASURED FROM FINISHED
 FLOOR TO THE TOP OF THE GRIPPING SURFACE AND MOUNTED IN
 A HORIZONTAL POSITION VERTICAL GRAB BARS ARE NOT
 APPROVED PER FBC ACC 609.4
  
 4. WHAT TYPE OF EQUIPMENT WILL BE IN THE MAINTENANCE /
 MECHANICAL ROOM 01.07.07IF ANYTHING WITH OIL OR
 HYDRAULIC FLUID THE FLOOR DRAIN SHALL DISCHARGE THROUGH
 AN OIL SEPARATOR. PER FBC PL 1003.4
  
 5. WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS
 SHALL HAVE A SMOOTH, HARD, NONABSORBENT SURFACE, TO A
 HEIGHT OF NOT LESS THAN 4 FEET ABOVE THE FLOOR, AND
 EXCEPT FOR STRUCTURAL ELEMENTS, THE MATERIALS USED IN
 SUCH WALLS SHALL BE OF A TYPE THAT IS NOT ADVERSELY
 AFFECTED BY MOISTURE. PER FBC 1210.2.2
  
 6. PLEASE PROVIDE A LABELING SYSTEM FOR THE SANITARY,
 WATER AND GAS THAT WILL SHOW A COHESIVE CORRELATION
 BETWEEN THE RISER?S ISOMETRIC DRAWINGS AND FLOOR PLANS.
 PER WPB AMEND TO THE FBC 107.2.1
  
 7. PROVIDE A COLLECTION ISOMETRIC FOR THE SANITARY AND
 GREASE SYSTEMS PER WPB AMEND TO THE FBC 107.2.1
  
 8. PROVIDE A COMPLETE SANITARY AND GREASE ISOMETRIC FOR
 THE SECOND AND THIRD FLOOR SHOWING THE KITCHEN,
 BATHROOMS AND BAR AREAS, ON THE BRANCHES FOR EACH AREA
 YOU CAN LABEL IT TO COINCIDE TO THE ENLARGED ISOMETRIC
 DRAWING INSTEAD OF DRAWING THE AREA TWICE. PER WPB
 AMEND TO THE FBC 107.2.1
  
 9. ANY SANITARY VENT TERMINALS ON THE ROOF SHALL BE A
 MIN OF 10? AWAY FROM ANY AIR INTAKE OPENINGS. PER FBC
 PL 903.5
  
 10. WHERE ARE THE ELEVATOR SUMP PUMPS DISCHARGING. .
 PER WPB AMEND TO THE FBC 107.2.1
  
 11. PROVIDE CIVIL DRAWINGS SHOWING THE LOCATION OF THE
 SANITARY, WATER, GREASE AND STORM DRAINS, IT LIST CIVIL
 DRAWING IN THE INDEX BUT THEY ARE NOT IN THE PLAN SET.
 . PER WPB AMEND TO THE FBC 107.2.1
  
 12. PLEASE PROVIDE SIZING CALCULATIONS FOR THE GREASE
 INTERCEPTORS. . PER WPB AMEND TO THE FBC 107.2.1
  
 13. PLEASE SHOW SQFT ON ALL OF THE PIPING ON THE STORM
 DRAIN ISOMETRIC. . PER WPB AMEND TO THE FBC 107.2.1
  
 14. A SEPARATE PERMIT IS REQUIRED FOR ANY BACKFLOW
 DEVICES ON THE DOMESTIC WATER MAIN AND FIRE LINE AND
 THE GREASE INTERCEPTOR. PER WPB UTILITIES DEPT. PLEASE
 PLACE NOTE ON THE PLAN. . PER WPB AMEND TO THE FBC
 107.2.1
  
 15. THE ROOM OR AREA NUMBERS ON THE FOOD SERVICE SHEETS
 DO NOT MATCH THE ARCHITECTAUL SHEETS.
 A) SHT. FS-01 SHOWS THE PANTRY HALLWAY/LOCKER ROOM AS
 01.05.02 SHT. A2.01.B SHOWS THIS AREA AS 01.07.02
 B) SHT. FS-01 SHOWS THE PANTRY AS 1.11.02 AND THE EVENT
 BAR AS 01.11.03 SHT. A2-01-A SHOWS THE PANTRY AS
 0.14.02 AND THE EVENT BAR AS 01.14.03
 C) SHT. FS-02 SHOWS THE PANTRY AS 02.05.02 SHT. A2-02-B
 SHOWS IT AS 02.07.02
 D) SHT. FS-03 SHOWS THE PANTRY AS 02.09.02 THE
 RESTAURANT IS SHOWN AS 02.12.02 SHT. A2-02-A SHOWS THE
 PANTRY AS 02.12.03 THE RESTAURANT AS 02.14.02
 E) SHT. FS-04 SHOWS THE PANTRY AS 03.5.04 SHT. A2-03-B
 SHOWS THE PANTRY AS 03.07.04
 PLEASE CHECK ALL THE FOOD SERVICE SHEETS AND CORRECT.
 PER WPB AMEND TO FBC 107.2.1
  
 16. ALL FLOOR DRAINS SHALL HAVE TRAP PRIMERS PLEASE
 SHOW ON ISOMETRIC DRAWING. PER FBC PL 1002.4
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  