| 2018-01-16 16:51:35 | 1ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION |
| | CODES |
| | PERMIT #17120261 |
| | 1/12/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE AC |
| | SYSTEMS INCLUDING THE RTU'S, THE SPLIT SYSTEMS, THE FAN |
| | COIL UNITS, THE INFRARED HEATERS, THE ECUH'S, AND |
| | EUH'S. - SECTION C403.2.1 FBC-14 ENERGY CONSERVATION |
| | AND SECTION 312.1 FBC-14 MECHANICAL. |
| | |
| | 2) THE COMCHECK ENERGY COMPLIANCE SUBMITTAL DOES NOT |
| | PROVIDE COMPLIANCE DATA FOR ANY OF THE PROPOSED HVAC |
| | SYSTEMS INCLUDING THE RTU'S, THE SPLIT SYSTEMS, THE FAN |
| | COIL UNITS, THE INFRARED HEATERS, THE ECUH'S, AND |
| | EUH'S- TABLE C403.2.3(1) FBC-14 ENERGY CONSERVATION. |
| | |
| | 3) COMMISSIONING OF THE MECHANICAL SYSTEMS IS REQUIRED |
| | PER SECTION C408.2 FBC-14 ENERGY CONSERVATION. SUBMIT A |
| | COMMISSIONING PLAN AS OUTLINED IN SECTION C408.2.1 AND |
| | DESCRIBED IN SECTIONS C403.2.2- C408.2.3.3. PLEASE NOTE |
| | THAT A COPY OF THE COMMISSIONING REPORT SHALL BE |
| | SUBMITTED FOR REVIEW AT FINAL INSPECTION. |
| | |
| | 4) SHEET MEPO-3: PROVIDE EXHAUST VENTILATION |
| | CALCULATIONS FOR ALL ROOMS AND SPACES BEING EXHAUSTED |
| | THROUGH RTU'S 1 & 2. REFER TO TABLE 403.3 FOOTNOTE G |
| | AND VERIFY NO MORE THAN 10% OF AIR EXHAUSTED FROM THE |
| | BATHROOMS AND LOCKERS ROOMS IS BEING RECIRCULATED. |
| | |
| | 5) MEPO-3: THE AIR BALANCE SCHEDULE FOR RTU-1 & 2 SHOWS |
| | MORE AIR BEING RETURN THAN IS BEING SUPPLIED- PLEASE |
| | CLARIFY. |
| | |
| | 6) SHEETS M2-1A, M2-1B, M2-2A, M2-2B, M2.3-A, M2.3-B, |
| | M2.4-A, M2-4B: IN ORDER TO HELP EXPEDITE THE REVIEW |
| | PLEASE IDENTIFY ALL ROOMS AND SPACES SHOWN ON THE |
| | LAYOUT PLANS. |
| | |
| | 7) SHEETS M2-1A & M2-1B: PLEASE CLARIFY HOW AIR |
| | SUPPLIED TO THE ROOMS AND SPACES SHOWN ON THE PLANS IS |
| | BEING RETURNED TO RTU-1. |
| | |
| | 8) DUCT SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR |
| | SYSTEMS OF: A) RTU'S 1- 4. B) FCU'S 103 & 104. C) AC |
| | 101- SECTION 606.2.1. PLEASE SHOW THE LOCATIONS OF THE |
| | DEVICES ON THE PLANS. PLEASE NOTE SMOKE DETECTORS ARE |
| | ALSO REQUIRED FOR COMMON RETURN AIR PLENUMS WITH |
| | DESIGNE CAPACITIES GREATER THAN 200 CFMS- SECTION |
| | 606.2.2. |
| | |
| | 9) DUCT SMOKE DETECTORS ARE REQUIRED FOR THE RETURN AIR |
| | RISER SERVING RTU-2. THE SMOKE DETECTORS SHALL BE |
| | PLACED AT EACH STORY- SECTION 606.2.3 |
| | |
| | 10) WIND LOAD ENGINEERING IS REQUIRED FOR ALL EXTERIOR |
| | MECHANICAL EQUIPMENT AND APPLIANCE INSTALLATIONS PER |
| | SECTION 301.15 FBC-14 MECHANICAL, AND SECTION 1609 |
| | FBC-14 BUILDING. PLEASE CORRECT THE NOTES ON SHEET M8-1 |
| | SPECIFYING 140 MPH WIND SPEED AND RISK CATEGORY III. |
| | REFER TO SECTION 1609.1.1 AND PROVIDE THE CORRECT |
| | DESIGN CRITERIA. SUBMIT VALID FLORIDA PRODUCT |
| | |
| | APPROVALS AND/OR MIAMI-DADE NOA'S FOR ANY RTU CURBS, |
| | ROOF STANDS, CONDENSER CLIPS, FANS, FAN CURBS, AND O/A |
| | AND EXHAUST LOUVERS TO BE USED ON THE PROJECT- RULE |
| | 9N-3 FAC. ALL SUBMITTALS SHALL HAVE SHOP DRAWING STAMPS |
| | BY THE EOR. |
| | |
| | 11) M8-1 & M8-2: PROVIDE COMPLETE ANCHORING AND |
| | ATTACHMENT DETAILS: RTU CURBS TO STRUCTURE, RTU TO |
| | CURB, AC STAND TO STRUCTURE, AC CONDENSER TO STAND, FAN |
| | CURBS TO STRUCTURE, FANS TO CURBS, AND ROOF TOP |
| | DUCTWORK TO STRUCTURE. |
| | |
| | 12) PROVIDE WIND LOAD DESIGN CRITERIA AND INSTALLATION |
| | DETAILS FOR THE INFRARED HEATERS AND THE |
| | DESTRATIFICATION FANS- SECTION 301.15. |
| | |
| | 13) M7-1: PROVIDE CONTROLS OPERATION DETAILS AND |
| | DIAGRAMS FOR THE INFRARED HEATERS AND DESTRATIFICATION |
| | FANS |
| | |
| | 14) M8-1: PROVIDE A HORIZONTAL FIRE DAMPER DETAIL. |
| | |
| | 15) SUBMIT SPECS FOR THE WATER HEATERS AND VENT FLUES |
| | AND PROVIDE EQUIPMENT SCHEDULES ON THE PLAN. |
| | |
| | 16) THE CONDENSATE IS NOTED IN MANY LOCATIONS ON THE |
| | PLAN TO BE DRAINED ONTO SPLASH BLOCKS ON THE ROOF WHICH |
| | IS NOT AN APPROVED PLACE OF DISPOSAL. REFER TO SECTION |
| | 307 AND SHOW ALL PIPING RUNS, PIPING DETAILS AND |
| | DISCHARGE LOCATIONS. |
| | |
| | 17) REFER TO SECTION 304 FBC-14 FUEL GAS AND PROVIDE |
| | COMBUSTION AIR CALCULATIONS FOR ALL GAS-FIRED COOKING |
| | APPLIANCES. |
| | |
| | 18) ACCESS FOR SERVICE AND REPLACEMENT OF ALL ABOVE |
| | CEILING FCU'S , HEATERS, FANS ETC. SHALL BE PROVIDED IN |
| | ACCORDANCE WITH SECTION 306.1. PLEASE SHOW ACCESS PANEL |
| | LOCATIONS ON THE PLAN AND INCLUDE PANEL DIMENSIONS. |
| | |
| | 19) ADVISORY: SEPARATE PERMITS ARE REQUIRED FOR THE |
| | KITCHEN HOOD AND FIRE SUPPRESSION SYSTEM, AND WALK-IN |
| | COOLER AND FREEZERS. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |