2018-01-16 16:51:351ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION
 CODES
 PERMIT #17120261
 1/12/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE AC
 SYSTEMS INCLUDING THE RTU'S, THE SPLIT SYSTEMS, THE FAN
 COIL UNITS, THE INFRARED HEATERS, THE ECUH'S, AND
 EUH'S. - SECTION C403.2.1 FBC-14 ENERGY CONSERVATION
 AND SECTION 312.1 FBC-14 MECHANICAL.
  
 2) THE COMCHECK ENERGY COMPLIANCE SUBMITTAL DOES NOT
 PROVIDE COMPLIANCE DATA FOR ANY OF THE PROPOSED HVAC
 SYSTEMS INCLUDING THE RTU'S, THE SPLIT SYSTEMS, THE FAN
 COIL UNITS, THE INFRARED HEATERS, THE ECUH'S, AND
 EUH'S- TABLE C403.2.3(1) FBC-14 ENERGY CONSERVATION.
  
 3) COMMISSIONING OF THE MECHANICAL SYSTEMS IS REQUIRED
 PER SECTION C408.2 FBC-14 ENERGY CONSERVATION. SUBMIT A
 COMMISSIONING PLAN AS OUTLINED IN SECTION C408.2.1 AND
 DESCRIBED IN SECTIONS C403.2.2- C408.2.3.3. PLEASE NOTE
 THAT A COPY OF THE COMMISSIONING REPORT SHALL BE
 SUBMITTED FOR REVIEW AT FINAL INSPECTION.
  
 4) SHEET MEPO-3: PROVIDE EXHAUST VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES BEING EXHAUSTED
 THROUGH RTU'S 1 & 2. REFER TO TABLE 403.3 FOOTNOTE G
 AND VERIFY NO MORE THAN 10% OF AIR EXHAUSTED FROM THE
 BATHROOMS AND LOCKERS ROOMS IS BEING RECIRCULATED.
  
 5) MEPO-3: THE AIR BALANCE SCHEDULE FOR RTU-1 & 2 SHOWS
 MORE AIR BEING RETURN THAN IS BEING SUPPLIED- PLEASE
 CLARIFY.
  
 6) SHEETS M2-1A, M2-1B, M2-2A, M2-2B, M2.3-A, M2.3-B,
 M2.4-A, M2-4B: IN ORDER TO HELP EXPEDITE THE REVIEW
 PLEASE IDENTIFY ALL ROOMS AND SPACES SHOWN ON THE
 LAYOUT PLANS.
  
 7) SHEETS M2-1A & M2-1B: PLEASE CLARIFY HOW AIR
 SUPPLIED TO THE ROOMS AND SPACES SHOWN ON THE PLANS IS
 BEING RETURNED TO RTU-1.
  
 8) DUCT SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR
 SYSTEMS OF: A) RTU'S 1- 4. B) FCU'S 103 & 104. C) AC
 101- SECTION 606.2.1. PLEASE SHOW THE LOCATIONS OF THE
 DEVICES ON THE PLANS. PLEASE NOTE SMOKE DETECTORS ARE
 ALSO REQUIRED FOR COMMON RETURN AIR PLENUMS WITH
 DESIGNE CAPACITIES GREATER THAN 200 CFMS- SECTION
 606.2.2.
  
 9) DUCT SMOKE DETECTORS ARE REQUIRED FOR THE RETURN AIR
 RISER SERVING RTU-2. THE SMOKE DETECTORS SHALL BE
 PLACED AT EACH STORY- SECTION 606.2.3
  
 10) WIND LOAD ENGINEERING IS REQUIRED FOR ALL EXTERIOR
 MECHANICAL EQUIPMENT AND APPLIANCE INSTALLATIONS PER
 SECTION 301.15 FBC-14 MECHANICAL, AND SECTION 1609
 FBC-14 BUILDING. PLEASE CORRECT THE NOTES ON SHEET M8-1
 SPECIFYING 140 MPH WIND SPEED AND RISK CATEGORY III.
 REFER TO SECTION 1609.1.1 AND PROVIDE THE CORRECT
 DESIGN CRITERIA. SUBMIT VALID FLORIDA PRODUCT
  
 APPROVALS AND/OR MIAMI-DADE NOA'S FOR ANY RTU CURBS,
 ROOF STANDS, CONDENSER CLIPS, FANS, FAN CURBS, AND O/A
 AND EXHAUST LOUVERS TO BE USED ON THE PROJECT- RULE
 9N-3 FAC. ALL SUBMITTALS SHALL HAVE SHOP DRAWING STAMPS
 BY THE EOR.
  
 11) M8-1 & M8-2: PROVIDE COMPLETE ANCHORING AND
 ATTACHMENT DETAILS: RTU CURBS TO STRUCTURE, RTU TO
 CURB, AC STAND TO STRUCTURE, AC CONDENSER TO STAND, FAN
 CURBS TO STRUCTURE, FANS TO CURBS, AND ROOF TOP
 DUCTWORK TO STRUCTURE.
  
 12) PROVIDE WIND LOAD DESIGN CRITERIA AND INSTALLATION
 DETAILS FOR THE INFRARED HEATERS AND THE
 DESTRATIFICATION FANS- SECTION 301.15.
  
 13) M7-1: PROVIDE CONTROLS OPERATION DETAILS AND
 DIAGRAMS FOR THE INFRARED HEATERS AND DESTRATIFICATION
 FANS
  
 14) M8-1: PROVIDE A HORIZONTAL FIRE DAMPER DETAIL.
  
 15) SUBMIT SPECS FOR THE WATER HEATERS AND VENT FLUES
 AND PROVIDE EQUIPMENT SCHEDULES ON THE PLAN.
  
 16) THE CONDENSATE IS NOTED IN MANY LOCATIONS ON THE
 PLAN TO BE DRAINED ONTO SPLASH BLOCKS ON THE ROOF WHICH
 IS NOT AN APPROVED PLACE OF DISPOSAL. REFER TO SECTION
 307 AND SHOW ALL PIPING RUNS, PIPING DETAILS AND
 DISCHARGE LOCATIONS.
  
 17) REFER TO SECTION 304 FBC-14 FUEL GAS AND PROVIDE
 COMBUSTION AIR CALCULATIONS FOR ALL GAS-FIRED COOKING
 APPLIANCES.
  
 18) ACCESS FOR SERVICE AND REPLACEMENT OF ALL ABOVE
 CEILING FCU'S , HEATERS, FANS ETC. SHALL BE PROVIDED IN
 ACCORDANCE WITH SECTION 306.1. PLEASE SHOW ACCESS PANEL
 LOCATIONS ON THE PLAN AND INCLUDE PANEL DIMENSIONS.
  
 19) ADVISORY: SEPARATE PERMITS ARE REQUIRED FOR THE
 KITCHEN HOOD AND FIRE SUPPRESSION SYSTEM, AND WALK-IN
 COOLER AND FREEZERS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  