| Date |
Text |
| 2018-01-25 09:53:21 | |
| | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | GAS COMMENTS: |
| | |
| | 1. CLEARLY SHOW ALL CUT SECTIONS OF PIPE AND |
| | CORRESPONDING LENGTHS PER FBC-2014 FUEL GAS, SECS. |
| | 402.4.1, 402.4.2. |
| | |
| | 2. ON THE RISER SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, AND PRESURE. WPB AMENDMENTS TO FBC SEC. |
| | 107.2.1. |
| | |
| | |
| | 3. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE |
| | FBC-2014 FUEL GAS CODE SEC. 304. |
| | |
| | |
| | 4. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND |
| | TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE |
| | SEC. 502 THRU 505. |
| | |
| | 5. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL |
| | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA |
| | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 |
| | |
| | 6. PLEASE PROVIDE SIZING TABLES USED FROM FBC FG 402 |
| | |
| | 7. SHT. FS-12 SHOWS A ROOF TOP EQUIPMENT R6 WITH A MBH |
| | LOAD OF 288 IT IS NOT SHOWN ON THE GAS RISER PLEASE |
| | CLARIFY PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 8. SHT. FS-07 SHOWS EQUIPMENT #5-10 WITH A QUANITY OF 1 |
| | AND A MBH LOAD OF (3) 40 THE GAS RISER SHOWS IT AS 40 |
| | MBTU PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 9. SHT. P7-1 THE TOTAL MBH ON THE KITCHEN COOKING |
| | ISOMETRIC ADDS UO TP 1391 MBH THE MAIN RISER SHOWS AN |
| | 11/2? PIPE TO THE KITCHEN WITH 1471 MBH PLEASE CLARIFY. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 10. LABEL THE GAS RISER TO MATCH THE FLOOR PLAN. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | 11. PLEASE PROVIDE AN EXPANDED ISOMETRIC FOR THE AREA |
| | OF THE KITCEN AND WATER HEATERS COMBINED THE AREA IS TO |
| | CONJESTED ON THE MAIN RISER. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |