| Date |
Text |
| 2017-12-21 15:21:36 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET LS 01 - THERE ARE STAIRS INDICATED TOWARDS THE |
| | CENTER ON THE BUILDING.STAIR # 2. THERE IS NO |
| | INDICATION OF THE TYPE OF OPENING THESE STAIRS |
| | REPRESENT. PER THE FFPC, NFPA 101, CHAPTER 12 & 8 THESE |
| | STAIRS SHALL CONFORM TO ONE OF THE FOLLOWING. |
| | |
| | 12.3 PROTECTION. |
| | 12.3.1 PROTECTION OF VERTICAL OPENINGS. ANY VERTICAL |
| | OPENING SHALL BE ENCLOSED OR PROTECTED IN ACCORDANCE |
| | WITH SECTION 8.6, UNLESS OTHERWISE PERMITTED BY ONE OF |
| | THE FOLLOWING: |
| | (1)* STAIRS OR RAMPS SHALL BE PERMITTED TO BE |
| | UNENCLOSED BETWEEN BALCONIES OR MEZZANINES AND MAIN |
| | ASSEMBLY AREAS LOCATED BELOW, PROVIDED THAT THE BALCONY |
| | OR MEZZANINE IS OPEN TO THE MAIN ASSEMBLY AREA. |
| | (2) EXIT ACCESS STAIRS FROM LIGHTING AND ACCESS |
| | CATWALKS, GALLERIES, AND GRIDIRONS SHALL NOT BE |
| | REQUIRED TO BE ENCLOSED. |
| | (3) ASSEMBLY OCCUPANCIES PROTECTED BY AN APPROVED, |
| | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| | WITH SECTION 9.7 SHALL BE PERMITTED TO HAVE UNPROTECTED |
| | VERTICAL OPENINGS BETWEEN ANY TWO ADJACENT FLOORS, |
| | PROVIDED THAT SUCH OPENINGS ARE SEPARATED FROM |
| | UNPROTECTED VERTICAL OPENINGS SERVING OTHER FLOORS BY A |
| | BARRIER COMPLYING WITH 8.6.5. |
| | (4) ASSEMBLY OCCUPANCIES PROTECTED BY AN APPROVED, |
| | SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| | WITHSECTION 9.7 SHALL BE PERMITTED TO HAVE CONVENIENCE |
| | STAIR OPENINGS IN ACCORDANCE WITH 8.6.9.2. |
| | |
| | 8.6.6 COMMUNICATING SPACE. |
| | 8.6.7* ATRIUMS |
| | 8.6.9 CONVENIENCE OPENINGS. |
| | |
| | PLEASE INDICATE WHICH ONE REPRESENTS THE PROPOSED AND |
| | PROVIDE SPECIFIC DETAILS HOW IT COMPLIES WITH EACH OF |
| | THE CONDITIONS. |
| | |
| | |
| | |
| | |
| | 2) SHEET FP 00 - THERE ARE NO INDICATIONS OR DRAWINGS |
| | RELATING THE CURTAIN WALL AND CLOSELY SPACED SPRINKLERS |
| | NOTED IN # 1 ABOVE. |
| | |
| | PLEASE PROVIDE SPECIFIC DETAILS OF THIS DESIGN ARA |
| | REQIUREMENTS. |
| | |
| | |
| | |
| | |
| | 3) SHEET LS 01 - THERE IS AN INDICATION INVOLVING STAIR |
| | # 2 OF A "DRAFT CURTAIN AND CLOSELY SPACED SPRINKLERS". |
| | THERE ARE NO DETAILS INDICATED OR SPECIFIC FIRE CODE |
| | REFERENCES THAT PERMIT THIS TYPE OF LIFE SAFETY |
| | FEATURE. |
| | |
| | PLEASE PROVIDE SPECIFIC DETAILS. |
| | |
| | |
| | |
| | 4) SHEET LS 01 - IN THE CLACULATION OF THE EGRESS |
| | CAPACITY OF THE STAIRS A 0.2 FIGURE IS BEING USED. PER |
| | NFPA 101, CHAPTER 7, MEANS OF EGRESS 0.3 SHALL BE USED. |
| | THE EXCEPTION IN THE BUILDING CODE DOES NOT APPLY TO |
| | THE FIRE CODE. |
| | |
| | 7.3.3* EGRESS CAPACITY. |
| | 7.3.3.1 EGRESS CAPACITY FOR APPROVED COMPONENTS OF |
| | MEANS OF EGRESS SHALL BE BASED ON THE CAPACITY FACTORS |
| | SHOWN IN TABLE |
| | 7.3.3.1, UNLESS OTHERWISE PROVIDED IN 7.3.3.2 . |
| | THE TABLE INDICATES "ALL OTHERS 0.3" |
| | |
| | PLEASE REVIEW AND CORRECT OR PROVIDE JUSTIFICATIONS. |
| | |
| | |
| | |
| | 5) SHEET LS 01 - IN THE CALCULATION OF THE EGRESS |
| | CAPACITY FO THE EXIT DOOR A .15 IS BEING USED, PER NFPA |
| | 101, CHAPTER 7, MEANS OF EGRESS 0.2 SHALL BE USED. THE |
| | EXCEPTION IN THE BUILDING CODE DOES NOT APPLY TO THE |
| | FIRE CODE. |
| | |
| | 7.3.3* EGRESS CAPACITY. |
| | 7.3.3.1 EGRESS CAPACITY FOR APPROVED COMPONENTS OF |
| | MEANS OF EGRESS SHALL BE BASED ON THE CAPACITY FACTORS |
| | SHOWN IN TABLE |
| | 7.3.3.1, UNLESS OTHERWISE PROVIDED IN 7.3.3.2 . |
| | THE TABLE INDICATES "ALL OTHERS 0.2" |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY. |
| | |
| | |
| | 6) SHEETS FP & FP 01 - THERE ARE NO INDICATIONS |
| | RELATING TO THE CURTAIN WALL AND CLOSELY SPACED |
| | SPRINKLERS. THE EOR SHALL MAKE REFERENCE AND ACCEPT THE |
| | DESIGN AND FUNCTION OF THE PROPOSED OF # 1 ABOVE. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY. |
| | |
| | |
| | |
| | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |