2018-01-11 10:36:07CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS
 (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF
 THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE
 REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. PLANS FOR
 ANY OF THESE SYSTEMS WILL NEED TO BE SUBMITTED AT TIME
 OF APPLICATION FOR PERMIT. FBC 105.1, 107.2.1
 2. FEEDER SCHEDULES SHOW A # 2 EQUIPMENT GROUNDING
 CONDUCTOR (EGC) FOR THE 450 AMP FEEDER. PARALLEL
 FEEDERS ARE REQUIRED TO HAVE THE EGC SIZED FOR THE
 CIRCUIT IN EACH CONDUIT, WHICH WOULD BE A 1/0 AL
 CONDUCTOR. PROVIDE CORRECTION. NEC 250.122(F)
 3. LOAD CALCULATION SHOWS SEVERAL LOADS WITH DEMAND
 FACTORS NOT TO CODE. THIS MAY BE A FUNCTION OF THE
 PROGRAM USED. EXAMPLE: HVAC LOAD IS SHOWN WITH 90%
 DEMAND, KITCHEN IS SHOWN WITH 90% DEMAND, MISCELLANEOUS
 IS SHOWS AT 70% DEMAND. HOWEVER, IT IS REQUIRED TO SHOW
 A LOAD CALCULATION FOR FEEDERS AND SERVICE THAT WILL
 HANDLE 125% OF THE CONTINUOUS LOAD PLUS 100% OF THE NON
 CONTINUOUS LOAD. PROVIDE LOAD CALCULATIONS WITH THESE
 DETAILS. NEC 220.40, 215.2
 4. SHOW COMPLIANCE WITH NEC 240.87
 5. AN ESTIMATED FAULT CURRENT FROM POWER COMPANY IS NOT
 ACCEPTABLE. PROVIDE LETTER FROM FPL WITH FAULT CURRENT
 AT SOURCE AND USE THIS INFORMATION IN CALCULATION. FBC
 107.2.1, NEC 110.10
 6. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 7. FOOD SERVICE/KITCHEN AREAS REQUIRE THAT ALL
 RECEPTACLE OUTLETS BE GFCI PROTECTED, NOT JUST THOSE
 THAT SERVE THE COUNTERTOP. PROVIDE CORRECTION. NEC
 210.8(B)(2),(6)
 8. SHEET E8-1, SERVICE GROUNDING DETAIL, SHOWS THE
 "MAIN BONDING JUMPER" SIZED AT 3/0. THIS SHOULD BE
 SIZED AT 12.5% OF THE AREA OF THE PHASE CONDUCTORS.
 BASED ON CURRENTLY SHOWN FEEDERS THIS WOULD EQUAL: 600
 KCMIL X 5 RUNS= 3000000 X 12.5% = 375000. THIS MAIN
 BONDING JUMPER WOULD NEED TO BE SIZED A MINIMUM OF 375
 KCMIL, WHICH THE NEXT SIZE AVAILABLE IS 400 KCMIL.
 PROVIDE CORRECTION. NEC 250.28(D)(1)
 9. PANEL 1GR2 IS SHOWN AS A 100 AMP MAIN LUG ONLY PANEL
 WITH 111 AMPS ON A PHASE, 101 AMPS ON B PHASE, AND 106
 AMPS ON C PHASE. PANEL MUST BE SIZED TO HANDLE THE
 LOAD. PROVIDE CORRECTION. NEC 408.30
 10. PANEL 2CR2 IS SHOWN AS A 200 AMP MAIN LUG ONLY
 PANEL WITH 208 AMPS ON A PHASE, 186 AMPS ON B PHASE,
 AND 222 AMPS ON C PHASE. PANEL MUST BE SIZED TO HANDLE
 THE LOAD. PROVIDE CORRECTION. NEC 408.30
 11. PANEL 2CR3 IS SHOWN AS A 150 AMP MAIN LUG ONLY
 PANEL WITH 184 AMPS ON A PHASE, 161 AMPS ON B PHASE,
 AND 175 AMPS ON C PHASE. PANEL MUST BE SIZED TO HANDLE
 THE LOAD. PROVIDE CORRECTION. NEC 408.30
 12. IT APPEARS THERE WOULD BE A SUBSTANTIAL AMOUNT OF
 NONLINEAR LOADS WITH THIS INSTALLATION. BASED ON THIS,
 THE NEUTRAL CONDUCTOR WOULD BE COUNTED AS A CURRENT
 CARRYING CONDUCTOR FOR FEEDERS PER NEC 310.15(B)(5)(C).
 BASED ON THIS REASONING, WHEN APPLYING THE 80% DEMAND
 FACTOR IN TABLE 310.15(B)(3), SEVERAL FEEDER SIZES ARE
 INADEQUATE FOR THE LOADS SERVED. THIS WOULD INCLUDE THE
 WIRE SIZES FOR 125, 150, 175, 200, 225, 250, 300, 450,
 500, 600, 800, AND 1600 AMP FEEDERS. PROVIDE
 CORRECTION. NEC310.15(B)(3), 240.4(C)
 13. REVIEWER DID NOT SEE ANY CIRCUITS FOR DRINKING
 FOUNTAINS. PROVIDE GFCI PROTECTION FOR DRINKING
 FOUNTAIN IF INSTALLED. NEC 422.52
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  