| 2018-01-24 14:18:41 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17120261 |
| | ADD: 1600 BELVEDERE RD. |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: NOT GIVEN ON PERMIT APPLICATION |
| | E-MAIL: NOT GIVEN ON THE PERMIT APPLICATION |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | DATE: WED. JAN. 24/2018 |
| | ACTION: DENIED |
| | |
| | ART IN PUBLIC PLACES |
| | 1) THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES |
| | ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR |
| | NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT |
| | APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL |
| | PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN |
| | $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE. |
| | PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND |
| | CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, |
| | ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION |
| | 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL |
| | PROJECT CONSTRUCTION COST. |
| | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| | PROJECTS. |
| | SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE |
| | DEVELOPMENT. |
| | (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND |
| | THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL |
| | PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW |
| | CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN |
| | EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE |
| | EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS |
| | WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED |
| | CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES |
| | REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED |
| | SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF |
| | THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW |
| | CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS. |
| | FOR CONTACT INFORMATION PLEASE CONTACT: |
| | MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR |
| | 822-1515 E-MAIL: [email protected] |
| | |
| | 2) 108.3* BUILDING PERMIT VALUATION. PLEASE NOTE THE |
| | BUILDING VALUATION SEEMS A LITTLE LOW. THE CODE SUMMARY |
| | SHEET CS-1 UNDER THE HEADING BUILDING DATA LIST THE |
| | SQUARE FOOTAGE PER FLOOR BUT NOT THE SQUARE FOOTAGE PER |
| | OCCUPANCY TYPE. THE ICC EVALUATION TABLES USES BUILDING |
| | TYPE, OCCUPANCY TYPE AND SQUARE FOOTAGE TO DETERMINE |
| | THE VALUATION OF THE BUILDING. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE |
| | MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS. |
| | WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING |
| | PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE |
| | QUALIFIER AND OWNER AND BRINGS IN THE LISTED |
| | SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE |
| | QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND |
| | LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE |
| | FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN |
| | LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR |
| | EACH PERMIT. |
| | ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK |
| | STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE |
| | AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS & |
| | FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL |
| | TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED |
| | SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, |
| | LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR |
| | FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE |
| | REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT. |
| | PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE |
| | ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE |
| | STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE |
| | REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE |
| | BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE |
| | BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR |
| | THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE |
| | PRIME PERMIT |
| | |
| | 3) THIS BUILDING IS TO BE CONSIDERED A THRESHOLD |
| | BUILDING BY DEFINITION. THRESHOLD BUILDING / FL S. S. |
| | 553.71(7) ?THRESHOLD BUILDING" MEANING ANY BUILDING |
| | WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, |
| | OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS |
| | DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 |
| | SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN |
| | 500 PERSONS. |
| | |
| | 3A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING |
| | AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL |
| | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | 3B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S |
| | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| | REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS |
| | ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH |
| | INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND |
| | REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE |
| | PLACE. |
| | |
| | FORMS WERE E-MAILED TO: [email protected] 1/24/2018 |
| | 2:30PM. |
| | |
| | |
| | 3C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. |
| | AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH |
| | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT |
| | OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| | BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE |
| | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 3D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' |
| | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | |
| | 3E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| | HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| | |
| | 3F) FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, PLEASE |
| | E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING ISSUED, |
| | THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE APPROVED |
| | AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, |
| | TWO SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) |
| | FOR THE THRESHOLD INSPECTOR, THE OTHER FOR THE MEP |
| | INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE IN BLACK |
| | & WHITE.. |
| | 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD |
| | BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS |
| | CONCERNING SPECIAL INSPECTORS. |
| | |
| | 3G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES, |
| | PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT |
| | AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING |
| | INSTALLATION SHALL BE SUPERVISED, INSPECTED AND |
| | CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING |
| | DOCUMENTS BY THE CONTRACTOR. |
| | |
| | 3H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL |
| | BUILDING INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 |
| | MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| | |
| | 3I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES |
| | FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER |
| | HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE |
| | MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR |
| | WALLS AND CEILINGS. |
| | |
| | 4) THIS PROPERTY IS LOCATED IN A AE FLOOD ZONE. THE |
| | BASE FLOOD ELEVATION IS 12.7 FT. NAVD 88 PLUS 2 FEET OR |
| | A FINISH FLOOR ELEVATION MINIMUM OF 14.77 NAVD 88. |
| | ARTICLE XVII ORDINANCES ARTICLE XVII FLOOD PREVENTION & |
| | CONTROL |
| | FBC BUILDING 1612 AND CITY OF WPB CODE OF SECTION |
| | 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A |
| | FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE |
| | REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS |
| | AFTER OCT. 11/ 2017 AN ADDITIONAL ONE FOOT OF FREE |
| | BOARD WILL BE REQUIRED OR (2) FEET ABOVE BASE FLOOD. |
| | |
| | DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE |
| | REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES |
| | REQUIRED: |
| | (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE |
| | PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR |
| | HEIGHT. W. P. B. ADMINISTRATIVE CODE 107.3.5.1.1 |
| | BUILDING MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL |
| | BUILDINGS. ( 8) FLOOD REQUIREMENTS ELEVATIONS, |
| | ENCLOSURES, FLOOD DAMAGE-RESISTANT MATERIALS. |
| | |
| | (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND |
| | ELEVATION CERTIFICATE IS REQUIRED. W. P. B. |
| | ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS 1.2 |
| | FLOOR/ SLAB INSPECTION. IN FLOOD HAZARD AREAS, UPON |
| | PLACEMENT OF THE LOWEST FLOOR, INCLUDING BASEMENT, AND |
| | PRIOR TO FURTHER VERTICAL CONSTRUCTION, THE ELEVATION |
| | CERTIFICATION, REQUIRED IN SECTION 1612.5, SHALL BE |
| | SUBMITTED TO THE BUILDING OFFICIAL. |
| | |
| | (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY |
| | OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE |
| | CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR |
| | ATTENDANTS A/C PADS OR OTHER SLABS FOR GENERATORS. |
| | W. P. B. ADMINISTRATIVE CODE 110.3 REQUIRED INSPECTIONS |
| | (6) FINAL INSPECTION. TO BE MADE AFTER THE BUILDING IS |
| | COMPLETED AND READY FOR OCCUPANCY. 6.1. LOWEST FLOOR |
| | ELEVATION. IN FLOOD HAZARD AREAS, AS PART OF THE FINAL |
| | INSPECTION, A FINAL CERTIFICATION OF THE LOWEST FLOOR |
| | ELEVATION SHALL BE SUBMITTED TO THE AUTHORITY HAVING |
| | JURISDICTION. |
| | FEMA NEW FORM AVAILABLE JUNE 13/2016. |
| | OMB NO. 1660-0008 |
| | EXPIRATION DATE: NOV. 30/2018 |
| | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM |
| | |
| | 5) THIS REVIEW NO SOILS REPORTS WERE FOUND IN THE FILE |
| | FOLDER. 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL. |
| | WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY |
| | OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE |
| | SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE |
| | BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| | GEOTECHNICAL INVESTIGATION BE CONDUCTED. |
| | |
| | 6A) FALL PROTECTION PDF. ATTACHMENT 1 HITTING BAY. |
| | UNDER THE 2014 FBC-B, THE CODE DOES NOT INCLUDE RAISED |
| | GOLFING PLATFORMS AS EXEMPT LOCATIONS TO THE |
| | REQUIREMENT FOR GUARDS AND OR GUARDRAILS SEE FBC-B |
| | 1013.2 WHERE REQUIRED. I WOULD RECOMMEND THAT YOU |
| | SHOULD MAKE A WRITTEN REQUEST TO THE BUILDING OFFICIAL |
| | ROBERT BROWN REQUESTING THE FALL PROTECTION PDF TO BE |
| | CONSIDERED UNDER THE: |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION SECTION 104.11 ALTERNATIVE MATERIALS, |
| | DESIGN AND METHODS OF CONSTRUCTION AND EQUIPMENT. THE |
| | PROVISIONS OF THIS CODE ARE NOT INTENDED TO PREVENT THE |
| | INSTALLATION OF ANY MATERIAL OR TO PROHIBIT ANY DESIGN |
| | OR METHOD OF CONSTRUCTION NOT SPECIFICALLY PRESCRIBED |
| | BY THIS CODE, PROVIDED THAT |
| | ANY SUCH ALTERNATIVE HAS BEEN APPROVED. AN ALTERNATIVE |
| | MATERIAL, DESIGN OR METHOD OF CONSTRUCTION SHALL BE |
| | APPROVED WHERE THE BUILDING OFFICIAL FINDS THAT THE |
| | PROPOSED DESIGN IS SATISFACTORY AND COMPLIES WITH THE |
| | INTENT OF THE PROVISIONS OF THIS CODE, AND THAT THE |
| | MATERIAL, METHOD OR WORK OFFERED IS, FOR THE PURPOSE |
| | INTENDED, AT LEAST THE EQUIVALENT OF THAT PRESCRIBED IN |
| | THIS CODE IN QUALITY, STRENGTH, EFFECTIVENESS, FIRE |
| | RESISTANCE, DURABILITY AND SAFETY. WHEN ALTERNATE LIFE |
| | SAFETY SYSTEMS ARE DESIGNED, THE SFPE ENGINEERING GUIDE |
| | TO PERFORMANCE-BASED FIRE PROTECTION ANALYSIS AND |
| | DESIGN OF BUILDINGS, OR OTHER METHODS APPROVED BY THE |
| | BUILDING OFFICIAL MAY BE USED. THE BUILDING OFFICIAL |
| | SHALL REQUIRE THAT SUFFICIENT EVIDENCE OR PROOF BE |
| | SUBMITTED TO SUBSTANTIATE ANY CLAIM MADE REGARDING THE |
| | ALTERNATIVE. |
| | |
| | 6B) 104.11.1 RESEARCH REPORTS. SUPPORTING DATA, WHERE |
| | NECESSARY TO ASSIST IN THE APPROVAL OF |
| | MATERIALS OR ASSEMBLIES NOT SPECIFICALLY PROVIDED FOR |
| | IN THIS CODE, SHALL CONSIST OF VALID |
| | RESEARCH REPORTS FROM APPROVED SOURCES. |
| | |
| | 6C) 104.11.2 TESTS. WHENEVER THERE IS INSUFFICIENT |
| | EVIDENCE OF COMPLIANCE WITH THE PROVISIONS OF |
| | THIS CODE, OR EVIDENCE THAT A MATERIAL OR METHOD DOES |
| | NOT CONFORM TO THE REQUIREMENTS OF THIS |
| | CODE, OR IN ORDER TO SUBSTANTIATE CLAIMS FOR |
| | ALTERNATIVE MATERIALS OR METHODS, THE BUILDING |
| | OFFICIAL SHALL HAVE THE AUTHORITY TO REQUIRE TESTS AS |
| | EVIDENCE OF COMPLIANCE TO BE MADE AT NO |
| | EXPENSE TO THE JURISDICTION. TEST METHODS SHALL BE AS |
| | SPECIFIED IN THIS CODE OR BY OTHER |
| | RECOGNIZED TEST STANDARDS. IN THE ABSENCE OF RECOGNIZED |
| | AND ACCEPTED TEST METHODS, THE |
| | BUILDING OFFICIAL SHALL APPROVE THE TESTING PROCEDURES. |
| | TESTS SHALL BE PERFORMED BY AN APPROVED |
| | AGENCY. REPORTS OF SUCH TESTS SHALL BE RETAINED BY THE |
| | BUILDING OFFICIAL FOR THE PERIOD REQUIRED |
| | FOR RETENTION OF PUBLIC RECORDS. |
| | |
| | 6D) 104.11.3 ACCESSIBILITY. ALTERNATIVE DESIGNS AND |
| | TECHNOLOGIES FOR PROVIDING ACCESS TO AND |
| | USABILITY OF A FACILITY FOR PERSONS WITH DISABILITIES |
| | SHALL BE IN ACCORDANCE WITH PROVISIONS OF |
| | THE FLORIDA BUILDING CODE, ACCESSIBILITY. |
| | |
| | 7) SHEET 003 CS-1 CODE SUMMARY: |
| | |
| | 7A) SEPARATED USE CALCULATIONS SHOWS THE FORMULA AND |
| | CHART BUT NEITHER IS FILLED OUT. PLEASE PROVIDE THE |
| | DOCUMENTATION SEE THE 2014 FBC-B SECTION 506.5.2. |
| | |
| | 7B) UNDER THE HEADING FIRE RESISTANCE RATINGS THERE IS |
| | NO ROW FOR FIRE BARRIER ASSEMBLIES OR HORIZONTAL |
| | ASSEMBLIES BETWEEN FIRE AREAS, SEE TABLE 707.3.10. |
| | |
| | 7C) HEADING: EXIT REQUIREMENTS LIST 50 FT. MAXIMUM DEAD |
| | END. PLEASE LIST THE OCCUPANCIES WHERE THIS IS TRUE. |
| | FBC-B 1018.4 SEE EXCEPTION 2. |
| | |
| | 7D) HEADING: ACCESSIBLE PARKING REQUIREMENTS CHART IS |
| | LEFT BLANK. WILL NEED TO COMPLY WITH THE 2014 |
| | ACCESSIBILITY CODE 208.2, TABLE 208.2 AND 208.2.4. VAN |
| | PARKING SPACES. |
| | |
| | 7E) HEADING: STRUCTURAL INDICATES WIND LOAD 170 MPH |
| | VULT. PLEASE REFER TO THE 2014 FBC-B TABLE 1604.5 FOR |
| | RISK CATEGORY OF BUILDINGS . RISK CATEGORY III INCLUDES |
| | BUILDINGS AND OTHER STRUCTURES WHOSE PRIMARY OCCUPANCY |
| | IS PUBLIC ASSEMBLY WITH AN OCCUPANT LOAD GREATER THAN |
| | 300. THIS BUILDING QUALIFIES WITH AN OCCUPANT LOAD OF |
| | 1708 PLUS. |
| | PLEASE ALSO REVIEW FIGURE 1609B THE V ULTIMATE DESIGN |
| | SPEEDS FOR RISK CATEGORY III BUILDINGS AND OTHER |
| | STRUCTURES. THE CITY OF WEST PALM BEACH IS LOCATED IN A |
| | 180 MPH (VULT) WIND ZONE. IMPORTANCE FACTOR SHOULD ALSO |
| | CHANGE FOR WIND. |
| | |
| | PLEASE ALSO CORRECT THE WIND DESIGN CRITERIA FOUND ON |
| | SHEET 3001 S0-01 GENERAL NOTE E WIND LOADS, THE PLANS |
| | STATE BUILDING CATEGORY II AND 170 MPH, VULT. |
| | |
| | 7F) OCCUPANCY CATEGORY (TABLE 1604.5) WILL ALSO CHANGE |
| | TO III. |
| | |
| | 7G) SOIL BEARING CAPACITY OF 3,000 PSF ASSUMED, NO |
| | SOILS REPORT SUBMITTED TO SEE WHAT VALUES ARE IN THE |
| | NATURAL SOILS. 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL. |
| | |
| | 8) 004- LS-01 LIFE SAFETY PLAN: |
| | |
| | 8A) FOR ALL 3 LEVELS PLEASE PROVIDE THE OCCUPANT LOAD |
| | FOR EACH ROOM IN THAT ROOM. WHEN TRAVELING THROUGH |
| | ADJACENT ROOMS COMBINE THE OCCUPANT LOADS FOR THE ROOMS |
| | AND WHEN YOU GET TO EITHER AN AISLE OR CORRIDOR PROVIDE |
| | THE OCCUPANT LOAD FOR THAT AREA BEING SERVED AND ADD |
| | THE ADDITIONAL OCCUPANTS BEING ADDED ALONG THE EGRESS |
| | PATH FROM THE INTERIOR OF THE BUILDING AS WELL AS THE |
| | HITTING AND SEATING BAYS, THIS SHOULD ADD UP TO THE |
| | AMOUNT GOING THROUGH THE VERTICAL EXITS AND STAIRS. |
| | |
| | 2014 FBC-B 1004.1.1.1 INTERVENING SPACES. WHERE |
| | OCCUPANTS EGRESS FROM ONE ROOM, AREA OR SPACE THROUGH |
| | ANOTHER, THE DESIGN OCCUPANT LOAD SHALL BE BASED ON THE |
| | CUMULATIVE OCCUPANT LOADS OF ALL ROOMS, AREAS OR SPACES |
| | TO THAT POINT ALONG THE PATH OF EGRESS TRAVEL. |
| | |
| | 8B) LOWER LEVEL. THE EXTERIOR TERRACE01.20.02 HAS 2338 |
| | SQ. FT. OF AREA WITH NO FURNITURE LAYOUT. 2338/ 07= 334 |
| | OCCUPANT LOAD. THERE IS ONLY ONE EXIT FROM THIS AREA. |
| | THE FBC-B TABLE 1015.1 ONLY ALLOWS FOR 49 OCCUPANTS |
| | WHEN THERE IS ONE EXIT. DOOR # 7 IS ALSO ADDING |
| | ADDITIONAL OCCUPANTS FROM THE INTERIOR OF THE BUILDING. |
| | FBC-B 1027.1. THE EXIT DISCHARGE SHALL NOT REENTER THE |
| | BUILDING. A SECOND MEANS OF EXITING WILL BE REQUIRED |
| | FOR THIS AREA. |
| | |
| | 8C) LOWER LEVEL, STAIR # 3 SHOWS A DOOR OPENING INTO |
| | THE ENCLOSURE FROM THE CASH VESTIBULE. EXIT ACCESS |
| | CORRIDORS ARE TO SEND OCCUPANTS INTO VERTICAL EXITS. |
| | THE LIFE SAFETY PLAN INDICATES THE VERTICAL EXIT WITH |
| | FIRE RATED WALLS, FIRE BARRIERS. |
| | PLEASE REVIEW 2014 FBC-B 1022.5 PENETRATIONS. |
| | PENETRATIONS INTO AND OPENINGS THROUGH INTERIOR EXIT |
| | STAIRWAYS ARE PROHIBITED EXCEPT FOR REQUIRED EXIT |
| | DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT |
| | VENTILATION OR PRESSURIZATION, SPRINKLER PIPING, |
| | STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT |
| | COMMUNICATION SYSTEMS AND ELECTRICAL RACEWAY SERVING |
| | THE INTERIOR EXIT STAIRWAY TERMINATING AT A STEEL BOX |
| | NOT EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH |
| | PENETRATIONS SHALL BE |
| | PROTECTED IN ACCORDANCE WITH SECTION 714. THERE SHALL |
| | BE NO PENETRATIONS OR COMMUNICATING OPENINGS, WHETHER |
| | PROTECTED OR NOT, BETWEEN ADJACENT INTERIOR EXIT |
| | STAIRWAYS AND RAMPS. |
| | |
| | 8D) LOWER LEVEL. STAIR # 4 SHOWS AT DOOR # 1 A MAXIMUM |
| | OF 227 OCCUPANTS ARE ALLOWED TO TRAVEL THROUGH A 34 |
| | INCH WIDE CLEAR DOOR OPENING. THE EXTERIOR DOOR IN THE |
| | SAME STAIRWELL IS NOT IDENTIFIED AS TO WIDTH BUT |
| | DEPICTED AS A SINGLE 3 FOOT WIDE DOOR WITH AN OCCUPANT |
| | LOAD OF 575 OCCUPANTS? PLEASE EXPLAIN? |
| | IT APPEARS YOU WERE USING THE 0.15 EGRESS FACTOR ON |
| | DOOR #1 OF THE STAIRWELL? |
| | FBC-B 1005.3.2 OTHER EGRESS COMPONENTS. EXCEPTION, |
| | OCCUPANT LOAD SERVED BY SUCH COMPONENT BY A MEANS OF |
| | EGRESS CAPACITY FACTOR OF 0.15 INCH (3.8 MM) PER |
| | OCCUPANT IN BUILDINGS EQUIPPED THROUGHOUT WITH AN |
| | AUTOMATIC SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH |
| | SECTION 903.3.1.1 OR 903.3.1.2 AND AN EMERGENCY |
| | VOICE/ALARM COMMUNICATION SYSTEM IN ACCORDANCE WITH |
| | SECTION 907.5.2.2. |
| | |
| | 8E) PLEASE BE AWARE THAT THE OCCUPANT LOADS TAKEN FOR |
| | DOORS IS OFF. EXAMPLE 34 / 0.15= 226.66 YOU ROUNDED UP |
| | TO 227. THIS HAPPENS AT ALL SINGLE 34 INCH DOORS. WHEN |
| | YOU HAVE A PORTION OF AN OCCUPANT YOU ALWAYS ROUND |
| | DOWN, THERE ARE NOT PARTS OF AN OCCUPANT. FLORIDA |
| | BUILDING CODE INFORMAL INTERPRETATION REPORT 5479, |
| | DATED 12/18/2007. THE FLORIDA BUILDING OFFICIALS |
| | ASSOCIATION OF FLORIDA, IN COOPERATION WITH THE FLORIDA |
| | BUILDING COMMISSION, THE FLORIDA DEPARTMENT OF |
| | COMMUNITY AFFAIRS. |
| | |
| | 8F) MAIN LEVEL. STAIR 3 HAS AN ENTRY DOOR FROM THE |
| | PANTRY/ SERVER STATION OPENING DIRECTLY INTO THE |
| | STAIRWELL. PLEASE REVIEW 2014 FBC-B 1022.5 |
| | PENETRATIONS. PENETRATIONS INTO AND OPENINGS THROUGH |
| | INTERIOR EXIT STAIRWAYS ARE PROHIBITED EXCEPT FOR |
| | REQUIRED EXIT DOORS, EQUIPMENT AND DUCTWORK NECESSARY |
| | FOR INDEPENDENT VENTILATION OR PRESSURIZATION, |
| | SPRINKLER PIPING, STANDPIPES, ELECTRICAL RACEWAY FOR |
| | FIRE DEPARTMENT COMMUNICATION SYSTEMS AND ELECTRICAL |
| | RACEWAY SERVING THE INTERIOR EXIT STAIRWAY TERMINATING |
| | AT A STEEL BOX NOT EXCEEDING 16 SQUARE INCHES (0.010 |
| | M2). SUCH PENETRATIONS SHALL BE PROTECTED IN ACCORDANCE |
| | WITH SECTION 714. THERE SHALL BE NO PENETRATIONS OR |
| | COMMUNICATING OPENINGS, WHETHER PROTECTED OR NOT, |
| | BETWEEN ADJACENT INTERIOR EXIT STAIRWAYS AND RAMPS. |
| | |
| | 8G) STAIR # 2 IS CONSIDERED AN EXIT ACCESS STAIRWAY AND |
| | HAVING TO MEET THE REQUIREMENTS FOUND UNDER 2014 FBC-B |
| | 1009.3 EXCEPTION 4. THE LIFE SAFETY PLAN SHOWS ON THE |
| | UPPER FLOOR AND MAIN FLOOR THE STAIR IS PROTECTED BY A |
| | DRAFT CURTAIN AND CLOSELY SPACED SPRINKLERS IN |
| | ACCORDANCE WITH NFPA BUT THIS NOTE IS NOT FOUND ON THE |
| | LOWER FLOOR. PLEASE ADD NOTE TO THE LOWER FLOOR FOR |
| | CODE COMPLIANCE WITH: 2014 FBC-B 1009.3 EXCEPTION 4. |
| | |
| | 8H) STAIR # 2 IS CONSIDERED AN EXIT ACCESS STAIRWAY |
| | PLEASE PROVIDE HOW COMPLIANCE WITH SECTION 1016.3.1 IS |
| | ACHIEVED. INDICATE THE FURTHEST DISTANCE ON THE UPPER |
| | LEVEL TO THE 1ST FLOOR EXIT IS ACHIEVED. |
| | |
| | 2014 FBC-B 1016.3.1 EXIT ACCESS STAIRWAYS AND RAMPS. |
| | TRAVEL DISTANCE ON EXIT ACCESS STAIRWAYS OR RAMPS SHALL |
| | BE INCLUDED IN THE EXIT ACCESS TRAVEL DISTANCE |
| | MEASUREMENT. THE MEASUREMENT ALONG STAIRWAYS SHALL BE |
| | MADE ON A PLANE PARALLEL AND TANGENT TO THE STAIR TREAD |
| | NOSINGS IN THE CENTER OF THE STAIR AND LANDINGS. THE |
| | MEASUREMENT ALONG RAMPS SHALL BE MADE ON THE WALKING |
| | SURFACE IN THE CENTER OF THE RAMP AND LANDINGS. |
| | |
| | 9) 004- LS-01 LIFE SAFETY PLAN AND FURNITURE PLANS. |
| | NEITHER OF THESE PLANS SHOW COMPLIANCE WITH THE |
| | ACCESSIBILITY CODE: |
| | 9A) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE |
| | CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE |
| | SEATING SPACES AND STANDING SPACES AT THE DINING |
| | SURFACES SHALL COMPLY WITH 902. |
| | |
| | 9B) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES |
| | REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED |
| | THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING |
| | SURFACES AND WORK SURFACES. |
| | |
| | 9C) 902.1 .DINING SURFACES AND WORK SURFACES SHALL |
| | COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL. |
| | DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS, |
| | TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK |
| | SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS, |
| | STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER |
| | TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON |
| | COUNTERS, AND WHERE COVERED BY THE ABA SCOPING |
| | PROVISIONS, EMPLOYEE WORK STATIONS. |
| | |
| | 9C)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR |
| | SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD |
| | APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 9C)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND |
| | WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | ADVISORY 226.1. IN FACILITIES COVERED BY THE ADA, THIS |
| | REQUIREMENT DOES NOT APPLY TO WORK SURFACES USED ONLY |
| | BY EMPLOYEES. HOWEVER, THE ADA AND, WHERE APPLICABLE, |
| | SECTION 504 OF THE REHABILITATION ACT OF 1973, AS |
| | AMENDED, PROVIDE THAT EMPLOYEES ARE ENTITLED TO |
| | ?REASONABLE ACCOMMODATIONS.? WITH RESPECT TO WORK |
| | SURFACES, THIS MEANS THAT EMPLOYERS MAY NEED TO PROCURE |
| | OR ADJUST WORK STATIONS SUCH AS DESKS, LABORATORY AND |
| | WORK BENCHES, FUME HOODS, RECEPTION COUNTERS, TELLER |
| | WINDOWS, STUDY CARRELS, COMMERCIAL KITCHEN COUNTERS, |
| | AND CONFERENCE TABLES TO ACCOMMODATE THE INDIVIDUAL |
| | NEEDS OF EMPLOYEES WITH DISABILITIES ON AN ?AS NEEDED? |
| | BASIS. CONSIDER WORK SURFACES THAT ARE FLEXIBLE AND |
| | PERMIT INSTALLATION AT VARIABLE HEIGHTS AND CLEARANCES. |
| | |
| | 10) NONE OF THE CIVIL PLANS WERE UPLOADED AS PART OF |
| | THIS REVIEW. COMPLIANCE WITH THE 2014 ACCESSIBILITY |
| | REQUIREMENTS CANNOT BE VERIFIED, NEED PLANS UPLOADED |
| | FOR THE NEXT REVIEW: |
| | |
| | 10A) 206.2.1. SITE ARRIVAL POINTS. AT LEAST ONE |
| | ACCESSIBLE ROUTE SHALL BE PROVIDED WITHIN THE SITE FROM |
| | ACCESSIBLE PARKING SPACES AND ACCESSIBLE PASSENGER |
| | LOADING ZONES; PUBLIC STREETS AND SIDEWALKS; AND PUBLIC |
| | TRANSPORTATION STOPS TO THE ACCESSIBLE BUILDING OR |
| | FACILITY ENTRANCE THEY SERVE. |
| | |
| | 10B) 206.2.2. WITHIN A SITE. AT LEAST ONE ACCESSIBLE |
| | ROUTE SHALL CONNECT ACCESSIBLE BUILDINGS, ACCESSIBLE |
| | FACILITIES, ACCESSIBLE ELEMENTS, AND ACCESSIBLE SPACES |
| | THAT ARE ON THE SAME SITE. |
| | |
| | 10C) 208.2 MINIMUM NUMBER OF ACCESSIBLE PARKING SPACES. |
| | PARKING SPACES COMPLYING WITH 502 SHALL BE PROVIDED IN |
| | ACCORDANCE WITH TABLE 208.2 EXCEPT AS REQUIRED BY |
| | 208.2.1, 208.2.2, AND 208.2.3. WHERE MORE THAN ONE |
| | PARKING FACILITY IS PROVIDED ON A SITE, THE NUMBER OF |
| | ACCESSIBLE SPACES PROVIDED ON THE SITE SHALL BE |
| | CALCULATED ACCORDING TO THE NUMBER OF SPACES REQUIRED |
| | FOR EACH PARKING FACILITY. |
| | |
| | 10D) 208.2.4 VAN PARKING SPACES. WHERE VAN PARKING IS |
| | PROVIDED PURSUANT TO SECTION 502.2, FOR EVERY SIX OR |
| | FRACTION OF SIX PARKING SPACES REQUIRED BY 208.2 TO |
| | COMPLY WITH 502, AT LEAST ONE SHALL BE A VAN PARKING |
| | SPACE COMPLYING WITH 502. |
| | |
| | 10E) 206.2.15 GOLF FACILITIES. AT LEAST ONE ACCESSIBLE |
| | ROUTE SHALL CONNECT ACCESSIBLE ELEMENTS AND SPACES |
| | WITHIN THE BOUNDARY OF THE GOLF COURSE. IN ADDITION, |
| | ACCESSIBLE ROUTES SERVING GOLF CAR RENTAL AREAS; BAG |
| | DROP AREAS; COURSE WEATHER SHELTERS COMPLYING WITH |
| | 238.2.3; COURSE TOILET ROOMS; AND PRACTICE PUTTING |
| | GREENS, PRACTICE TEEING GROUNDS, AND TEEING STATIONS AT |
| | DRIVING RANGES COMPLYING WITH 238.3 SHALL COMPLY WITH |
| | CHAPTER 4 EXCEPT AS MODIFIED BY 1006.2. |
| | 11) 212-ROOF PLAN A2-04A- AREA A & 213 ROOF PLAN |
| | A2-04-B AREA B: |
| | |
| | 11A) BOTH ROOF PLANS SHOW THE USE OF EMERGENCY OVER |
| | FLOW SCUPPERS. THERE ARE 2 DETAILS FOR EMERGENCY |
| | OVERFLOW SCUPPERS DETAIL 8 & 9 OF SHEET 243- A8-09. |
| | PLEASE PROVIDE THE SQ. FT. AREA TO BE DRAINED BY BOTH |
| | EMERGENCY OVERFLOW SCUPPERS INCLUDING ? OF THE HEIGHT |
| | OF THE PARAPET. WHY IS DETAIL 8 SHOWING THE SIZE OF THE |
| | SCUPPER 4X16 WHEREAS DETAIL 9 SHOW A SIZE OF 8X16 TWICE |
| | AS LARGE FOR CLOSE TO THE SAME AREA? |
| | |
| | 2014 FBC-B 1503.4.1 SECONDARY (EMERGENCY OVERFLOW) |
| | DRAINS OR SCUPPERS. |
| | WHERE ROOF DRAINS ARE REQUIRED, SECONDARY (EMERGENCY |
| | OVERFLOW) ROOF DRAINS OR SCUPPERS SHALL BE PROVIDED |
| | WHERE THE ROOF PERIMETER CONSTRUCTION EXTENDS ABOVE THE |
| | ROOF IN SUCH A MANNER THAT WATER WILL BE ENTRAPPED IF |
| | THE PRIMARY DRAINS ALLOW BUILDUP FOR ANY REASON. THE |
| | INSTALLATION AND SIZING OF SECONDARY EMERGENCY OVERFLOW |
| | DRAINS, LEADERS AND CONDUCTORS SHALL COMPLY WITH |
| | SECTIONS 1106 AND 1107, AS APPLICABLE, OF CHAPTER 11 OF |
| | THE FLORIDA BUILDING CODE, PLUMBING. |
| | |
| | 11B) SHEET 213-A2-04B. ON BOTH ROOF DRAINAGE SHEETS THE |
| | PLANS SHOW A DETAIL # 5 WITH 2 ROOF DRAINS 4 FEET APART |
| | CENTER TO CENTER BUT AT THE SAME ELEVATION. DOES IT |
| | TAKE 2 DRAINS TO TAKE THE WATER OFF THE ROOF OR IS IT |
| | THE INTENT FOR ONE OF THE ROOF DRAINS TO BE CONSIDERED |
| | THE SECONDARY EMERGENCY OVERFLOW DRAIN? |
| | IF THE ONE DRAIN IS TO BE CONSIDER A SECONDARY |
| | EMERGENCY OVERFLOW DRAIN A SEPARATE SYSTEM IS REQUIRED. |
| | SHEET 616-P4-2 SHOWS A 6 INCH ROOF DRAIN AND A 6 INCH |
| | OVERFLOW DRAIN EMPTYING INTO THE SAME RISER (1555). SEE |
| | FBC-P 1108.2. |
| | |
| | 10C) SHEET 611P2-3-B PLEASE SEE STAIRWELL # 3. A 6 INCH |
| | ROOF DRAIN IS IN STAIRWELL # 3. |
| | PLEASE REVIEW 2014 FBC-B 1022.5 PENETRATIONS. |
| | PENETRATIONS INTO AND OPENINGS THROUGH INTERIOR EXIT |
| | STAIRWAYS ARE PROHIBITED EXCEPT FOR REQUIRED EXIT |
| | DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT |
| | VENTILATION OR PRESSURIZATION, SPRINKLER PIPING, |
| | STANDPIPES, ELECTRICAL RACEWAY FOR FIRE DEPARTMENT |
| | COMMUNICATION SYSTEMS AND ELECTRICAL RACEWAY SERVING |
| | THE INTERIOR EXIT STAIRWAY TERMINATING AT A STEEL BOX |
| | NOT EXCEEDING 16 SQUARE INCHES (0.010 M2). SUCH |
| | PENETRATIONS SHALL BE |
| | PROTECTED IN ACCORDANCE WITH SECTION 714. THERE SHALL |
| | BE NO PENETRATIONS OR COMMUNICATING OPENINGS, WHETHER |
| | PROTECTED OR NOT, BETWEEN ADJACENT INTERIOR EXIT |
| | STAIRWAYS AND RAMPS. |
| | |
| | 11) PLEASE NOTE THAT THE SUBMITTED PRODUCT APPROVALS |
| | CANNOT BE REVIEWED FOR POSITIVE AND NEGATIVE PRESSURES |
| | UNTIL THE CORRECT WIND DESIGN CRITERIA AND PRESSURES |
| | ARE PROVIDE. SEE COMMENTS 7E AND 7F. |
| | |
| | 12) PLEASE SHOW COMPLIANCE WITH: |
| | W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 13) KAWNEER COMPANY CURTAIN WALL 1600 SYSTEM PLEASE |
| | SUBMIT EITHER A MIAMI-DADE OR FLORIDA APPROVAL WITH |
| | THIS TEST REPORT. , 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE |
| | CODE 61G20-3.005, |
| | |
| | 14A) CENTRIA INTERCEPT ENTYRE PANEL SYSTEM, PLEASE |
| | PROVIDE WHERE THIS SYSTEM IS TO BE INSTALLED ON THE |
| | BUILDING, AND WHAT TYPE OF BACKING IS REQUIRED. |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 14B) CENTRIA INTERCEPT ENTYRE PANEL SYSTEM PLEASE |
| | SUBMIT EITHER A MIAMI-DADE OR FLORIDA APPROVAL WITH |
| | THIS TEST REPORT. , 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE |
| | CODE 61G20-3.005, |
| | |
| | 15) CECO DOOR IT APPEARS HAS A FLORIDA APPROVAL, SUBMIT |
| | THE COVERSHEETS FOR FL 16355.1-R1. , 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | |
| | 16) OVERHEAD DOORS SERIES521 & 610/620 ROLLING STEEL |
| | DOORS, PLEASE SUBMIT THE FLORIDA APPROVAL COVERSHEETS. |
| | , 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| | DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE |
| | 61G20-3.005, |
| | |
| | 17A) ROOFING REPORT CARLISLE SUBMIT THE FLORIDA |
| | APPROVAL COVERSHEET FOR FL 16440-R10. |
| | |
| | 17B) PLEASE NOTE NONE OF THE SUB-SYSTEMS HAVE BEEN |
| | IDENTIFIED WITH ASSOCIATED PRESSURES. REVIEW |
| | LIMITATIONS AS TO IF ENHANCED FASTENING CAN OCCUR. |
| | 107.2.1.3. ADDITIONAL INFORMATION REQUIRED. |
| | FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING |
| | SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF |
| | ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF |
| | ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3. |
| | FASTENER DENSITIES SHALL BE INCREASED FOR BOTH |
| | INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE |
| | WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION |
| | PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED |
| | PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT. |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | |
| | 18) EURO-LS100 LIFT AND SLIDING GLASS DOORS PLEASE |
| | PROVIDE EITHER A FLORIDA APPROVAL OR MIAMI-DADE NOA. |
| | , 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| | DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE |
| | 61G20-3.005, |
| | |
| | 19) KAWNEER IR501 LMI ALUMINUM STORE FRONT SYSTEMS, |
| | PLEASE SUBMIT EITHER A MIAMI-DADE OR FLORIDA APPROVAL |
| | WITH THIS TEST REPORT. , 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| | ADMINISTRATIVE CODE 61G20-3.005, |
| | |
| | 20) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| | VENTILATORS |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 21) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| | RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| | MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| | PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1 |
| | INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| | FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| | INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| | LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 22) EFIS SYSTEMS: PLEASE PROVIDE THE PRODUCT APPROVAL |
| | FOR THE SYSTEM TO BE INSTALLED. PLEASE ALSO PROVIDE THE |
| | MANUFACTURERS INSTALLATION BROCHURE PROVIDING |
| | COMPLIANCE WITH 2014 FBC-B SECTIONS; |
| | 1408.2 PERFORMANCE CHARACTERISTICS. |
| | 1408.2 PERFORMANCE CHARACTERISTICS. |
| | 1408.3 STRUCTURAL DESIGN. |
| | 1408.4 WEATHER RESISTANCE. |
| | 1408.4.1 EIFS WITH DRAINAGE. |
| | 408.4.1.1 WATER-RESISTIVE BARRIER. |
| | 1408.5 INSTALLATION. |
| | |
| | 23) LATERAL FORCE-RESISTING SYSTEM FOR ALL ROOF TOP |
| | EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS, |
| | DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL |
| | AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. |
| | |
| | 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| | LOADS. |
| | |
| | 24) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| | ONE SET OF PLANS WILL HAVE TO BE TAKEN (BY THE |
| | CONTRACTOR OR REPRESENTATIVE) TO THE PALM BEACH COUNTY |
| | IMPACT FEE OFFICE LOCATED AT 2300 N. JOG RD. ROOMS |
| | 2W01-2W14 WEST PALM BEACH, FL. THE ACTUAL PERMIT SET OF |
| | PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE |
| | PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE |
| | CALL (561)233-5025 FOR MORE INFORMATION. |
| | |
| | 25) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |