| Plan Review Notes For Permit 17120255 |
| Permit Number |
17120255 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-12-27 11:05:05 | 1) SUBMIT TWO COPIES OF MANUFACTURER'S SPECIFICATIONS | | | FOR THE GAS REGULATOR TO BE INSTALLED. REGULATORS | | | INSTALLED ON THE EXTERIOR SHALL BE APPROVED FOR OUTDOOR | | | USE. 2014 FGC SEC.410.1. | | | 2) THE GENERATOR SHALL MEET THE REQUIREMENTS OF UL 2200 | | | PER THE FGC SEC. 616.1. THIS IS SHOWN AS AN OPTION IN | | | THE GENERATOR SPECIFICATIONS. CLARIFY. | | | 3) SHT.P0.1- NOTE #7 - THE TRACER WIRE SHALL BE IN | | | CONTACT WITH THE PE PIPE. FGC SEC.404.17.3. | | | 4) SHOW THE DISTANCE FROM THE OUTLET OF THE METER TO | | | THE MOST REMOTE LINE PRESSURE REGULATOR ON THE 2 PSI | | | SYSTEM.2014 FGC SEC.402.4.3. | | | 5) THE BTU LOAD OF THE GENERATOR AT 60HZ IS 757,000 | | | BTU'S AT 100% LOAD ACCORDING TO THE MANUFACTURER'S | | | SPECIFICATIONS BUT THE GAS DRAWING SHOWS THE BTU LOAD | | | AS 699,000 BTU'S. CLARIFY. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|