| 2020-10-14 07:45:30 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17120224 ROOF-SUB |
| | W. P. B. PERMIT: 16020490 PRIME/ BUILDING |
| | ADD: 1009 BANYAN BLVD. |
| | CONT: POOLE & KENT |
| | TEL: 561-223-2096 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2ND REVIEW |
| | DATE: WED. OCT. 14TH/ 2020 |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. THE DESIGNER OF RECORD WILL NEED TO REVIEW |
| | ALL ROOFING SUBMITTALS, APPROVE AND APPLY THEIR SHOP |
| | DRAWING STAMP OF APPROVAL ON THEM. |
| | W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 2) 2ND REQUEST. THE RESPONSE INDICATES SEE THE NOA |
| | 16-0125.09 FOR THE THICKNESS OF THE PLYWOOD DECK FOR |
| | FASTENING OF THE ROOFING MATERIAL. THAT IS NOT THE |
| | ISSUE. THE ISSUE IS NEITHER THE ARCHITECTURAL SHEETS |
| | NOR STRUCTURAL SHEETS STATE THERE IS ANY PLYWOOD |
| | SHEATHING ON THE CLEARSTORY FOR A ROOF DECK. THE |
| | STRUCTURAL SHEET GS-13 DETAILS S917, S918 & S-557 ALL |
| | SHOW METAL DECKING, NOTE INDICATES SEE ARCHITECTURAL |
| | SHEETS FOR INSULATION AND ROOFING DETAILS. ARCH. |
| | SHEETS. A REVISION NEEDS TO BE MADE TO BOTH THE |
| | ARCHITECTURAL AND STRUCTURAL SHEETS ADDING PLYWOOD |
| | DECKING WITH THICKNESS TO MATCH THAT OF THE ROOFING |
| | PRODUCT APPROVAL. |
| | |
| | 1ST ROUND OF COMMENTS. SUBMITTED FROM FORENSIC |
| | ENGINEERING FASTENING FOR ? INCH THICK PLYWOOD |
| | SHEATHING ATTACHMENT CALCULATIONS FOR THE CLERESTORY |
| | ROOF. THE STRUCTURAL SHEET GS-13 DETAILS S917, S918 & |
| | S-557 ALL SHOW METAL DECKING, NOTE INDICATES SEE |
| | ARCHITECTURAL SHEETS FOR INSULATION AND ROOFING |
| | DETAILS. ARCH. SHEETS. |
| | 17A-11 DETAILS B-D SHOW SLOPED ROOF SYSTEMS WITH METAL |
| | BARREL TILE, BATT INSULATION AND PRE-ENGINEERED TRUSS |
| | SYSTEM. THE ARCHITECTURAL PLANS DOES NOT ADDRESS THE |
| | PLYWOOD DECKING FOR THE ANCHORING OF THE METAL BARREL |
| | TILE. |
| | |
| | 3) COMPLIED. THE SLOPED ROOFS WITH METAL BARREL TILE |
| | FLORIDA APPROVAL FL16317-R1 THE CONTRACTOR HAS NOT |
| | IDENTIFIED WHICH TILE SYSTEM IS TO BE INSTALLED, SLOPE, |
| | EXPOSURE, BASIC WIND SPEED NOR HAVE THEY INDICATED FOR |
| | ZONE 3 IF EVEN ALLOWED. PLEASE READ NOTES AND |
| | LIMITATIONS. |
| | |