Plan Review Notes
Plan Review Notes For Permit 17120224
Permit Number 17120224
Review Stop B
Sequence Number 2
Notes
Date Text
2020-10-14 07:45:302014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17120224 ROOF-SUB
 W. P. B. PERMIT: 16020490 PRIME/ BUILDING
 ADD: 1009 BANYAN BLVD.
 CONT: POOLE & KENT
 TEL: 561-223-2096
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: WED. OCT. 14TH/ 2020
 ACTION: DENIED
  
 1) COMPLIED. THE DESIGNER OF RECORD WILL NEED TO REVIEW
 ALL ROOFING SUBMITTALS, APPROVE AND APPLY THEIR SHOP
 DRAWING STAMP OF APPROVAL ON THEM.
 W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2) 2ND REQUEST. THE RESPONSE INDICATES SEE THE NOA
 16-0125.09 FOR THE THICKNESS OF THE PLYWOOD DECK FOR
 FASTENING OF THE ROOFING MATERIAL. THAT IS NOT THE
 ISSUE. THE ISSUE IS NEITHER THE ARCHITECTURAL SHEETS
 NOR STRUCTURAL SHEETS STATE THERE IS ANY PLYWOOD
 SHEATHING ON THE CLEARSTORY FOR A ROOF DECK. THE
 STRUCTURAL SHEET GS-13 DETAILS S917, S918 & S-557 ALL
 SHOW METAL DECKING, NOTE INDICATES SEE ARCHITECTURAL
 SHEETS FOR INSULATION AND ROOFING DETAILS. ARCH.
 SHEETS. A REVISION NEEDS TO BE MADE TO BOTH THE
 ARCHITECTURAL AND STRUCTURAL SHEETS ADDING PLYWOOD
 DECKING WITH THICKNESS TO MATCH THAT OF THE ROOFING
 PRODUCT APPROVAL.
  
 1ST ROUND OF COMMENTS. SUBMITTED FROM FORENSIC
 ENGINEERING FASTENING FOR ? INCH THICK PLYWOOD
 SHEATHING ATTACHMENT CALCULATIONS FOR THE CLERESTORY
 ROOF. THE STRUCTURAL SHEET GS-13 DETAILS S917, S918 &
 S-557 ALL SHOW METAL DECKING, NOTE INDICATES SEE
 ARCHITECTURAL SHEETS FOR INSULATION AND ROOFING
 DETAILS. ARCH. SHEETS.
 17A-11 DETAILS B-D SHOW SLOPED ROOF SYSTEMS WITH METAL
 BARREL TILE, BATT INSULATION AND PRE-ENGINEERED TRUSS
 SYSTEM. THE ARCHITECTURAL PLANS DOES NOT ADDRESS THE
 PLYWOOD DECKING FOR THE ANCHORING OF THE METAL BARREL
 TILE.
  
 3) COMPLIED. THE SLOPED ROOFS WITH METAL BARREL TILE
 FLORIDA APPROVAL FL16317-R1 THE CONTRACTOR HAS NOT
 IDENTIFIED WHICH TILE SYSTEM IS TO BE INSTALLED, SLOPE,
 EXPOSURE, BASIC WIND SPEED NOR HAVE THEY INDICATED FOR
 ZONE 3 IF EVEN ALLOWED. PLEASE READ NOTES AND
 LIMITATIONS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  