Plan Review Notes
Plan Review Notes For Permit 17120220
Permit Number 17120220
Review Stop R
Sequence Number 2
Notes
Date Text
2018-03-22 18:11:581- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20.3.001 FOR:
 A) METAL ROOF PANELS THAT MEET THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER OF RECORD ON SHEET S-4 FOR
 ALL ROOF ZONES. THE DESIGN PRESSURES OF THE FLORIDA
 PRODUCT APPROVAL FL21383.1 SUBMITTED DON'T MEET THOSE
 DESIGN PRESSURES.
 RESPONSE: NOT PRODUCT APPROVAL WAS SUBMITTED THIS TIME.
  
 B) LOW SLOPED ROOF. NOTE: CLEARLY IDENTIFY APPROVED
 ASSEMBLY TO BE INSTALLED. IF SELECTED ASSEMBLY DOESN'T
 MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN
 SIGNED AND SEALED RAS 117 CALCULATIONS MAY BE REQUIRED.
 RESPONSE: NOT PRODUCT APPROVAL WAS SUBMITTED THIS TIME.
  
 C) BALCONY UNDERLAYMENT THAT IS DESIGNED TO BE
 INSTALLED WITH FINISH FLOOR SPECIFIED ON PLANS.
 DESIGNER OF RECORD TO PROVIDE SPECIFICATIONS FOR FINISH
 FLOORING. NOTE: CLEARLY IDENTIFY SPECIFIC ASSEMBLY TO
 BE INSTALLED AND RAS 117 CALCULATIONS MAY BE REQUIRED
 IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES
 FOR ALL ZONES.
 RESPONSE: NOT PRODUCT APPROVAL WAS SUBMITTED THIS TIME.
  