| Plan Review Notes For Permit 17120220 |
| Permit Number |
17120220 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-01-08 13:33:25 | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | FAC 61G20.3.001 FOR: | | | A) METAL ROOF PANELS THAT MEET THE DESIGN PRESSURES | | | CALCULATED BY THE ENGINEER OF RECORD ON SHEET S-4 FOR | | | ALL ROOF ZONES. THE DESIGN PRESSURES OF THE FLORIDA | | | PRODUCT APPROVAL FL21383.1 SUBMITTED DON'T MEET THOSE | | | DESIGN PRESSURES. NOTE: COORDINATE WITH ITEM #5(A) | | | ABOVE. | | | IF USING FLORIDA PRODUCT APPROVALS, THEN PROVIDE THE | | | FLORIDA PRODUCT APPROVAL COVER PAGE ALSO NOT JUST THE | | | INSTALLATION INSTRUCTIONS. | | | | | | B) LOW SLOPED ROOF. COORDINATE WITH ITEM #5(A) ABOVE | | | AND #15(B) ABOVE. NOTE: CLEARLY IDENTIFY APPROVED | | | ASSEMBLY TO BE INSTALLED. IF SELECTED ASSEMBLY DOESN'T | | | MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN | | | SIGNED AND SEALED RAS 117 CALCULATIONS MAY BE REQUIRED. | | | | | | C) BALCONY UNDERLAYMENT THAT IS DESIGNED TO BE | | | INSTALLED WITH FINISH FLOOR SPECIFIED ON PLANS. | | | DESIGNER OF RECORD TO PROVIDE SPECIFICATIONS FOR FINISH | | | FLOORING. NOTE: CLEARLY IDENTIFY SPECIFIC ASSEMBLY TO | | | BE INSTALLED AND RAS 117 CALCULATIONS MAY BE REQUIRED | | | IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES | | | FOR ALL ZONES. | | | | | | 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | |
|