Plan Review Notes
Plan Review Notes For Permit 17120220
Permit Number 17120220
Review Stop R
Sequence Number 1
Notes
Date Text
2018-01-08 13:33:251- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20.3.001 FOR:
 A) METAL ROOF PANELS THAT MEET THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER OF RECORD ON SHEET S-4 FOR
 ALL ROOF ZONES. THE DESIGN PRESSURES OF THE FLORIDA
 PRODUCT APPROVAL FL21383.1 SUBMITTED DON'T MEET THOSE
 DESIGN PRESSURES. NOTE: COORDINATE WITH ITEM #5(A)
 ABOVE.
 IF USING FLORIDA PRODUCT APPROVALS, THEN PROVIDE THE
 FLORIDA PRODUCT APPROVAL COVER PAGE ALSO NOT JUST THE
 INSTALLATION INSTRUCTIONS.
  
 B) LOW SLOPED ROOF. COORDINATE WITH ITEM #5(A) ABOVE
 AND #15(B) ABOVE. NOTE: CLEARLY IDENTIFY APPROVED
 ASSEMBLY TO BE INSTALLED. IF SELECTED ASSEMBLY DOESN'T
 MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN
 SIGNED AND SEALED RAS 117 CALCULATIONS MAY BE REQUIRED.
  
 C) BALCONY UNDERLAYMENT THAT IS DESIGNED TO BE
 INSTALLED WITH FINISH FLOOR SPECIFIED ON PLANS.
 DESIGNER OF RECORD TO PROVIDE SPECIFICATIONS FOR FINISH
 FLOORING. NOTE: CLEARLY IDENTIFY SPECIFIC ASSEMBLY TO
 BE INSTALLED AND RAS 117 CALCULATIONS MAY BE REQUIRED
 IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES
 FOR ALL ZONES.
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  