| 2017-12-29 15:54:47 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| | FBC EC R404.1 |
| | 2. PROVIDE GFCI PROTECTION FOR ALL OUTLETS IN GARAGE, |
| | INCLUDING GARAGE DOOR OPENER. NEC 210.8; FBC RE3902.2 |
| | 3. RECEPTACLES IN KITCHEN REQUIRE GFCI PROTECTION. |
| | PROVIDE CORRECTION. NEC 210.8; FBC RE 3902.6 |
| | 4. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF |
| | EACH ROOM USED FOR SLEEPING PURPOSES. FBC R315.1 |
| | 5. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| | NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14 |
| | 6. PROVIDE AFCI PROTECTION: ALL 120-VOLT, SINGLE PHASE, |
| | 15 AND 20 AMPERE BRANCH CIRCUITS SUPPLYING OUTLETS IN |
| | DWELLING UNIT FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| | PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS, |
| | RECREATION ROOMS, CLOSETS, HALLWAYS, OR SIMILAR AREAS |
| | OR ROOMS, SHALL HAVE AFCI PROTECTION. A NOTE WILL |
| | SUFFICE. NEC 210.12; FBC RE3902.12 |
| | 7. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED |
| | GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL |
| | SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON |
| | THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE |
| | LEVEL ACCESS. PROVIDE CORRECTION. NEC 210.70(A)(2)(B), |
| | FBC RE3903.3 |
| | 8. PER CODE: "LIGHTING WITH OPEN OR PARTIALLY ENCLOSED |
| | LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT |
| | BE PERMITTED IN CLOTHES CLOSETS". PROVIDE CORRECTION. |
| | NEC 410.16; FBC RE4003.12 |
| | 9. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| | LOADS. I DO NOT SEE ANY LOAD FOR WATER HEATER. NEC 220; |
| | FBC RE3602.3 |
| | 10. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| | LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| | SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS |
| | (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF |
| | THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE |
| | REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| | SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1, |
| | 107.2.1 |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |