2018-01-04 09:35:01****NOTE:
 FOR CITY RECORDS: COMPLETE ALL THE INFORMATION ON THE
 FRONT SCREEN ONCE THE TOTAL BUILDING SQUARE FOOTAGES
 ARE CLARIFIED.
  
  
  
  
 NEW SINGLE FAMILY RESIDENCE (R3), BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEE ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- BEDROOM #3 DOESN'T COMPLY WITH THE EMERGENCY ESCAPE
 REQUIREMENTS OF SEC. R310.1 FBC-RESIDENTIAL, 5TH
 EDITION (2014). ALL THE WINDOWS ARE FIXED WINDOWS.
 REVISE PLANS AS REQUIRED. NEED TO PROVIDE EMERGENCY
 ESCAPE. NOTE: MAKE SURE EMERGENCY ESCAPE MEETS ALL THE
 MINIMUM CLEAR OPENINGS REQUIREMENTS. CLEAR WIDTH (20"),
 CLEAR HEIGHT (24") AND TOTAL CLEAR OPENING (5.7S.F.).
  
 3- SHEET A-1:
 A) AT LEAST ONE BATHROOM ON THE FIRST FLOOR NEEDS TO
 HAVE A DOOR THAT HAS A MINIMUM OF 29" CLEAR OPENING AS
 REQUIRED BY SEC. R320 FBC-RESIDENTIAL. REVISE PLANS AS
 REQUIRED.
  
 B) LANDING IS REQUIRED ON THE OUTSIDE OF THE SCREEN
 DOORS OF THE SCREENED PORCH. SEC. R311.3
 FBC-RESIDENTIAL.
  
 C) THE SQUARE FOOTAGE AREAS SPECIFIED ON THE ROOM
 LEGEND DOESN'T MATCH AREA ON PLANS. REVISE/CLARIFY AS
 REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS. NOTE:
 THIS COMMENT APPLIES TO SHEET A-2 ALSO.
  
 D) PROVIDE FIRE RATING SPECIFICATIONS FOR THE SWING
 DOOR LEADING FROM THE GARAGE TO THE MAIN HOUSE AS
 REQUIRED BY SEC. R302. 5.1 FBC-RESIDENTIAL. NOTE:
 INCLUDE THE SELF CLOSING DEVICE.
  
 E) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION AND INSTALLATION OF THE SCREEN ENCLOSURE.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 F) CLARIFY TYPE OF KITCHEN WINDOW "D". WINDOW SCHEDULE
 SPECIFIES "TRANSOM ALUM", WHILE WINDOW TYPE SHOWS A
 HORIZONTAL SLIDING WINDOW AND KITCHEN FLOOR PLAN SHOWS
 A CASEMENT WINDOW. REVISE AS REQUIRED TO CLARIFY. SEC.
 107.2.1 CITY AMENDMENTS.
  
 G) CLARIFY TYPE AND SIZE OF DOOR #8 SPECIFIED FOR THE
 FLORIDA ROOM. FLOOR PLAN SHOWS SINGLE FOLDING DOOR,
 WHILE DOOR SCHEDULE ON SHEET A-2 SPECIFIES PAIR OF
 FOLDING DOORS. ALSO, COORDINATE WITH PRODUCT APPROVAL.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 H) SPECIFY INSULATION BETWEEN GARAGE AND A/C AREA. SEC.
 R103.2 FBC-ENERGY CONSERVATION. 5TH EDITION (2014).
 NOTE: COORDINATE WITH THE ENERGY CALCULATIONS.
  
 4- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CHIMNEY SHOWN IN THE EXTERIOR ELEVATIONS FOR THE SUMMER
 KITCHEN". SEC. R301.1 FBC-RESIDENTIAL.
  
 5- SHEET A-2:
 A) SPECIFY THE ROOF SLOPE FOR THE SCREENED PORCH AS
 REQUIRED BY SEC. R905.11.1 FBC RESIDENTIAL. NOTE:
 ACCORDING TO BUILDING ELEVATIONS AND WALL SECTIONS
 SUBMITTED, IT LOOKS LIKE THIS IS A LOW SLOPED ROOF.
 COORDINATE WITH SLOPE SHOWN ON THE SITE PLAN ON SHEET
 SP-1 AND SHEET S-2 . ALSO, COORDINATE WITH TYPE OF
 ROOFING MATERIAL SPECIFIED ON PLANS. METAL ROOFING MAY
 NOT BE ALLOWED. SEE SEC. R905.10 FBC-RESIDENTIAL.
  
 B) SPECIFY SECOND FLOOR ATTIC ACCESS SIZE AND LOCATION
 SHOWING COMPLIANCE WITH SEC. R807 FBC-RESIDENTIAL.
  
 6- SHEET SP-1:
 A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE "WOOD TRELLIS ARBOR" AND "WOOD
 TRELLIS AT ORCHID GARDEN". SEC. R301.1 FBC-RESIDENTIAL.
 (NOTE: STRUCTURAL DRAWINGS DON'T PROVIDE ANY
 CONSTRUCTION DETAILS). OR PROVIDE COMPLETE INFORMATION
 UNDER A SEPARATE PERMIT. IF SEPARATE PERMIT, THEN
 SPECIFY ON PLANS THAT CONSTRUCTION BY OTHERS UNDER
 SEPARATE PERMIT.
  
 B) REVISE THE CODE SUMMARY NOTES AND GENERAL NOTES.
 THIS IS NOT ALTERATION LEVEL 2 AND THERE IS NOT
 DEMOLITION. REVISE ALL NOTES TO REFLECT THE ACTUAL
 SCOPE OF WORK TO BE DONE. THIS IS A NEW SINGLE FAMILY
 RESIDENCE. ALSO, CLARIFY WHY THE TOTAL AREA (BUILDING
 COVERAGE) IS 3,388 S.F.? SEC. 107.2.1 CITY AMENDMENTS.
  
 C) REVISE THE NEW BUILDING DESIGN INFORMATION SHOWN AT
 THE BOTTOM LEFT OF THE SHEET. THE MEAN ROOF HEIGHT
 INFORMATION IS INCORRECT. REVISE AS REQUIRED AND
 INCLUDE THE STAIRWAY TOWER. SEE EXTERIOR BUILDING
 ELEVATIONS AND REVISE AS REQUIRED. SEC. R301.1
 FBC-RESIDENTIAL. ALSO, CLARIFY WHAT IS BUILDING
 CATEGORY R-3T?. SEC. 107.2.1 CITY AMENDMENTS.
  
 D) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF PRIVACY WALLS/FENCES. SEC. R301.1
 FBC-RESIDENTIAL. NOTE: FENCES REQUIRE SEPARATE PERMITS.
  
 E) GENERAL NOTES: CLARIFY THE SQUARE FOOTAGES SHOWN ON
 THE SITE ANALYSIS. WHERE IS THE TOTAL AREA (BUILDING
 COVERAGE) AREA TAKEN FROM. IT DOESN'T ADD UP THE
 BUILDING AREAS SHOWN. PROVIDE THE SQUARE FOOTAGE OF THE
 ENTRY AREA. SEC. 107.2.1 CITY AMENDMENTS.
  
 7- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC.
 R401.3 FBC-RESIDENTIAL.
  
 8- SHEET A-3:
 A) SOUTH EXTERIOR ELEVATION SPECIFIES BEDROOM #3 WINDOW
 "B" TO HAVE A WINDOW SILL ELEVATION OF 12"-6" AND THE
 SECOND FLOOR AT 11'-0". THIS BEDROOM NEEDS AN EMERGENCY
 ESCAPE WINDOW. SEE ITEM #2 ABOVE. THE WINDOW SIZE AND
 TYPE NEEDS TO BE REVISED TO COMPLY WITH THE EGRESS
 REQUIREMENTS. IT LOOKS LIKE THIS WINDOW WILL NEED TO
 COMPLY WITH THE WINDOW FALL PROTECTION OF SEC. R312.2
 FBC-RESIDENTIAL. PROVIDE COMPLETE INFORMATION SHOWING
 COMPLIANCE WITH THE WINDOW FALL PROTECTION.
  
 B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ALL
 DECORATIVE BRACKETS AND CORBELS. SPECIFY ALL FASTENERS.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 9-PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 MASTER BATHROOM SKYLIGHT FRAMING. SPECIFY ALL FRAMING
 MEMBERS AND CONNECTORS. SEC. R301.1 FBC-RESIDENTIAL.
  
 10- SPECIFY CARBON MONOXIDE ALARMS BY ALL BEDROOMS AS
 REQUIRED BY SEC. R315.1 FBC-RESIDENTIAL.
  
 11- PROVIDE COMPLETE DETAIL AND SPECIFICATIONS SHOWING
 HOW THE R-19 INSULATION WILL BE PROVIDED ON THE
 CONCRETE BLOCK WALL AS SPECIFIED ON THE TYPICAL WALL
 SECTION 1 ON SHEET A-5 AND TYPICAL WALL SECTION 2 ON
 SHEET A-6. NOTE: COORDINATE INFORMATION WITH THE
 ENGINEER WHO PREPARED THE ENERGY CALCULATIONS TO AVOID
 CONFLICTS/DELAYS.
 SEC. R103.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 12- HOUSE IS DESIGNED WITH UNVENTED ATTIC. ARCHITECT IS
 SPECIFYING R-30 ICYNENE SPRAY INSULATION. PROVIDE ICC
 EVALUATION REPORT (2 COPIES) FOR THE ICYNENE R-30
 INSULATION TO VERIFY COMPLIANCE WITH SEC. R316
 FBC-RESIDENTIAL.
 NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 13- SHEET A-10:
 A) THE FLORIDA BUILDING CODE DESIGN PARAMETERS SHOWN ON
 SHEET A-10 DOESN'T MATCH INFORMATION SHOWN ON SHEET
 S-4. ALSO, CLARIFY WHAT'S BUILDING CATEGORY "B". REVISE
 THE WIND SPEED. REVISE THE MEAN ROOF HEIGHT AND REVISE
 THE DESIGN PRESSURES TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 B) THE PLYWOOD SHEATHING NAILING PATTERNS DON'T MATCH
 INFORMATION SHOWN ON SHEET S-4. REVISE AS REQUIRED TO
 MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 C) REVISE THE SPECIFICATIONS AND STRUCTURAL NOTES: THE
 CODE EDITION IS OLD. CLARIFY WHAT'S BUILDING CATEGORY
 "B". UPDATE THE EDITION YEAR OF ALL THE REFERENCED
 STANDARDS. SEE CHAPTER 46 OF FBC-RESIDENTIAL FOR THE
 ADOPTED EDITION OF THE STANDARDS. ALSO, THE SOIL
 BEARING CAPACITY SPECIFIED UNDER THE FOUNDATION
 INFORMATION DOESN'T MATCH INFORMATION SHOWN ON SHEET
 S-4. REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 D) THE TYPICAL WOOD BUCK TO CONCRETE CONNECTION DETAIL
 DOESN'T MATCH STRUCTURAL BUCK DETAILS SHOWN ON SHEET
 S-4. REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 14- SHEET S-2: CLARIFY SPACING OF THE 2X10 CEILING
 JOIST AT THE REAR PORCH. JOISTS ARE DRAWN AT 12" O.C.
 BUT SPECIFICATIONS CALL FOR 16" O.C. REVISE AS REQUIRED
 TO CLARIFY. SEC. 107.2.1 CITY AMENDMENTS.
  
 15- SHEET S-4:
 A) SPECIFY THE ATTIC LIVE LOAD AS REQUIRED BY TABLE
 R301.4 FBC-RESIDENTIAL.
  
 B) SPECIFY THE ROOF DESIGN PRESSURES FOR THE LOW SLOPED
 ROOF AREA ABOVE THE SCREENED PORCH. SEC. R301.1
 FBC-RESIDENTIAL.
  
 16- REVISE TYPICAL STEP FOOTING DETAIL ON SHEET S-5.
 THE RISER HEIGHT EXCEEDS THE MAXIMUM HEIGHT REQUIRED BY
 SEC. R311.7.5.1 FBC-RESIDENTIAL.
  
 17- ENERGY CALCULATIONS SUBMITTED:
 A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING CORRECT PROPERTY ADDRESS, BUILDER'S NAME.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 B) PROVIDE WINDOWS AND DOORS MANUFACTURER'S
 SPECIFICATIONS SHOWING THE U-FACTOR AND SHGC FACTOR
 SPECIFIED ON THE ENERGY CALCULATIONS ON ITEM #7 AS
 REQUIRED BY SEC. R405.4.3 FBC-ENERGY CONSERVATION.
 NOTE: COORDINATE WITH PLANS AND PRODUCT APPROVALS
 SUBMITTED TO AVOID CONFLICTS/DELAYS.
  
 C) INSULATION R-VALUE SPECIFIED ON ITEM #9 FOR THE
 CONCRETE BLOCK WALLS DOESN'T MATCH INSULATION R VALUED
 SPECIFIED BY THE ARCHITECT. REVISE AS REQUIRED TO
 MATCH. NOTE: COORDINATE WITH ARCHITECT TO AVOID
 CONFLICTS/DELAYS. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 D) ITEM #10 SPECIFIES A VENTED ATTIC. ARCHITECT OF
 RECORD DESIGNED THE HOUSE WITH AN UNVENTED ATTIC. SEE
 PLANS AND REVISE AS REQUIRED. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 E) REVISE TYPE OF ROOF SPECIFIED ON PAGE 2 OF 5 TO
 MATCH PLANS. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 F) REVISE THE ATTIC INFORMATION SPECIFIED ON PAGE 2 OF
 5. ACCORDING TO PLANS, ARCHITECT DESIGNED AN UNVENTED
 ATTIC. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G) REVISE THE WINDOWS INFORMATION SHOWN ON PAGE 3 OF 5
 TO MATCH PLANS. REVISE ORIENTATION AND OVERHANG DEPTH
 AND SEPARATION TO MATCH PLANS. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 H) CLARIFY WHY THE GARAGE FLOOR AREA AND CEILING AREA
 SHOWN ON PAGE 4 OF 5 DOESN'T MATCH. REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 I) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 FBC-ENERGY
 CONSERVATION.
  
 18- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20.3.001 FOR:
 A) METAL ROOF PANELS THAT MEET THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER OF RECORD ON SHEET S-4 FOR
 ALL ROOF ZONES. THE DESIGN PRESSURES OF THE FLORIDA
 PRODUCT APPROVAL FL21383.1 SUBMITTED DON'T MEET THOSE
 DESIGN PRESSURES. NOTE: COORDINATE WITH ITEM #5(A)
 ABOVE.
 IF USING FLORIDA PRODUCT APPROVALS, THEN PROVIDE THE
 FLORIDA PRODUCT APPROVAL COVER PAGE ALSO NOT JUST THE
 INSTALLATION INSTRUCTIONS.
  
 B) GARAGE DOOR THAT MEETS THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER OF RECORD ON SHEET S-4. THE
 DESIGN PRESSURES OF NOA 15-0922.07 SUBMITTED DON'T MEET
 THOSE DESIGN PRESSURES.
  
 C) ENTRY DOOR WITH TRANSOM AS SHOWN ON PLANS.
  
 D) FIXED WINDOWS AS SHOWN ON PLANS.
  
 E) OPERABLE WINDOWS AS SPECIFIED ON PLANS . NOTE:
 COORDINATE WITH EGRESS WINDOWS REQUIREMENTS. SEE ITEM
 #2 ABOVE.
  
 F) GARAGE EXTERIOR SWING DOOR AS SHOWN ON PLANS.
  
 G) UTILITY EXTERIOR SWING DOOR WITH DOGGIE DOOR AS
 SHOWN ON PLANS.
  
 H) SKYLIGHT AS SHOWN ON PLANS.
  
 I) PRECAST LINTELS AS SPECIFIED ON PLANS. NOTE: NOA
 12-0209.13 SPECIFIED ON SHEET S-5 IS EXPIRED.
  
 J) FOLDING DOOR AS SHOWN ON PLANS BY THE FLORIDA ROOM.
  
 K) EXTERIOR FRENCH DOORS AS SHOWN ON PLANS.
  
 L) KITCHEN WINDOW TYPE AS SPECIFIED ON PLANS.
  
 M) WINDOW MULLIONS AS SHOWN ON PLANS. NOTE: CLEARLY
 SPECIFY MULLION SIZE TO BE USED TO VERIFY COMPLIANCE
 WITH THE CALCULATED DESIGN PRESSURES.
  
 N) LOW SLOPED ROOF. COORDINATE WITH ITEM #5(A) ABOVE
 AND #15(B) ABOVE. NOTE: CLEARLY IDENTIFY APPROVED
 ASSEMBLY TO BE INSTALLED. IF SELECTED ASSEMBLY DOESN'T
 MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN
 SIGNED AND SEALED RAS 117 CALCULATIONS MAY BE REQUIRED.
  
 O) BALCONY UNDERLAYMENT THAT IS DESIGNED TO BE
 INSTALLED WITH FINISH FLOOR SPECIFIED ON PLANS.
 DESIGNER OF RECORD TO PROVIDE SPECIFICATIONS FOR FINISH
 FLOORING. NOTE: CLEARLY IDENTIFY SPECIFIC ASSEMBLY TO
 BE INSTALLED AND RAS 117 CALCULATIONS MAY BE REQUIRED
 IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES
 FOR ALL ZONES.
  
 P) CEMENTITIOUS BOARD SOFFIT AS SHOWN ON SHEET A-5.
  
 Q) ALL SIMPSON AND USP STRUCTURAL CONNECTORS SPECIFIED
 ON PLANS AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR OR DESIGNER OF RECORD TO LIST THE FLORIDA
 PRODUCT APPROVAL NEXT TO THE SPECIFIED CONNECTOR.
  
 19- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 20- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONALS FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $491,776. THE
 PERMIT FEE BALANCE IS $8,247.27.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWINGS. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD
 DRAWINGS FOR REFERENCE.
  