| Plan Review Notes For Permit 17120219 |
| Permit Number |
17120219 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-12-08 11:00:50 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THE PROPOSED FIRE ALARM APPEARS TO BE A STAND ALONE | | | SEPARATE SYSTEM. THIS IS NOT A STAND ALONE BUILDING. IT | | | IS A PART OF A PLAZA AND SERIES OF STORES. A FIRE ALARM | | | IN THIS SPACE SHALL ALERT ADJACENT SPACES. | | | | | | ACCORDING TO A PREVIOUSLY APPROVED PERMIT AND INSTALLED | | | SYSTEM,16110614, THIS SYSTEM IS TO BE TIED INTO THE | | | PLAZA FIRE ALARM. | | | | | | PLEASE CORRECT PROVIDE REVISIONS CONSISTENT WITH | | | PREVIOUS FIRE ALARM PERMITTING AND FUNCTION. | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|