| 2018-01-04 07:40:23 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. NOTE STATES THAT RECEPTACLES SHALL BE TAMPER |
| | RESISTANT PER NEC 406.11. THIS CODE SECTION DOES NOT |
| | APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE |
| | CORRECTION. NEC 406.12; FBC RE4002.14 |
| | 2. SERVICE GROUNDING ELECTRODE TO BE AUGMENTED BY AN |
| | ADDITIONAL ELECTRODE 6 FEET AWAY OR PROVIDE EVIDENCE OF |
| | RESISTANCE TO GROUND OF 25 OHMS OR LESS. PROVIDE |
| | INTERSYSTEM BONDING TERMINATION POINT AT SERVICE (SHOW |
| | ON RISER DIAGRAM). NEC 250.6, 250.94; FBC RE3609.3 |
| | 3. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| | LOADS. NEC 220; FBC RE3602.3 |
| | 4. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| | FBC EC R404.1 |
| | 5. A GFCI PROTECTED OUTLET ON A 20 AMP CIRCUIT IS |
| | REQUIRED WITHIN 3 FEET OF EACH BASIN. PROVIDE |
| | CORRECTION FOR BATH 2. NEC 210.11(C)(3), 210.52(D); FBC |
| | RE 3703.4, 3901.6 |
| | 6. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF |
| | EACH ROOM USED FOR SLEEPING PURPOSES. FBC R315.1 |
| | 7. PROVIDE GFCI PROTECTION FOR ALL OUTLETS IN GARAGE, |
| | INCLUDING THE GARAGE DOOR OPENER. NEC 210.8; FBC |
| | RE3902.2 |
| | 8. PROVIDE SPEC SHEET FOR TANKLESS WATER HEATER. THE |
| | PANEL SCHEDULE SHOWS A LOAD OF 8000 WATTS, WHICH IS A |
| | LOAD OF APPROXIMATELY 33.33 AMPS. HOWEVER, THE BREAKER |
| | IS FOR THIS IS SHOWN AS AN 80 AMP BREAKER. NEED |
| | CLARIFICATION OF SIZE REQUIRED. NEC 110.3 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |