Plan Review Notes
Plan Review Notes For Permit 17120197
Permit Number 17120197
Review Stop M
Sequence Number 2
Notes
Date Text
2018-01-11 08:39:172ND REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION,
 EXISTING BUILDING CODES
 PERMIT #17120197
 1/11/18
  
 PLAN REVIEW RESULTS: DENIED.
 NEW PLAN SHEETS 3.2M AND 3.3M REVIEWED AND NOT
 APPROVED.
  
 1) SHEET 3.2M: SEE COMMENT #2 FROM THE 1ST REVIEW-
 SMOKE DETECTORS REQUIRED FOR AHU- 1, 4 & 5. AN
 EXEMPTION CAN BE APPLIED IF MANUFACTURER'S
 SPECIFICATIONS INDICATE THE UNITS DO NOT HAVE THE
 CAPACITIES TO EXCEED 2000 CFMS OF SUPPLY AIR. PLEASE
 SUBMIT THE SPECS TO VERIFY THE CFMS OR PROVIDE THE
 DETECTORS.
  
 2) 3.2M: SEE COMMENT #6 FROM THE 1ST REVIEW- PROVIDE
 THE DIMENSIONS OF THE RETUN AIR OPENING ABOVE THE AHU-
 2 & 3 CLOSET WALL.
  
 3) 3.2M & 3.3M: SEE COMMENTS #4, 7, & 8 FROM THE 1ST
 REVIEW- INSUFFICIENT OUTDOOR AIR PROVIDED. THE
 VENTILATION SCHEDULE IS INCORRECTLY SHOWING 5 CFMS PER
 PERSON REQUIRED FOR THE DINING ROOM AND BAR AREA- TABLE
 403.3 REQUIRES 7.5 CFM PER PERSON. TOTAL O/A REQUIRED
 IS 1388 CFMS + 642 CFMS = 2030. PLEASE CORRECT THE
 VENTILATION SCHEDULE AND THE AIR BALANCE SCHEDULE.
 REFER
  
 TO SECTION C403.2.5.1 AND PROVIDE DEMAND CONTROLLED
 VENTILATION FOR THE DINING ROOM AND BAR AREA.
  
 4) 3.3M: SEE COMMENT #8 FROM THE 1ST REVIEW- WIND LOAD
 DESIGN CRITERIA NOT PROVIDED.
  
 5) 3.2M & 3.3M: SEE COMMENT #10 FROM THE 1ST REVIEW-
 SHOW THE CONDENSATE PIPING RUNS, SUBMIT SPECS FOR THE
 CONDENSATE PUMPS, AND ADD THE PUMPS TO THE ELECTRICAL
 SCOPE OF WORK.
  
 6) 3.2M & 3.3M: SEE COMMENT #11 FROM THE 1ST REVIEW-
 REQUESTED COMBUSTION AIR CALCULATIONS NOT PROVIDED.
  
 7) SEE COMMENT #12 FROM THE 1ST REVIEW- REQUESTED FL.
 PRODUCT APPROVALS AND/OR MIAMI-DADE NOA'S FOR THE
 CONDENSER STANDS AND LOUVERS NOT PROVIDED.
  
 8) SEE COMMENT #13 FROM THE 1ST REVIEW- CUT SHEETS FOR
 THE GAS-FIRED COOKING APPLIANCES AND MOTORIZED DAMPERS
 NOT PROVIDED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved