| Date |
Text |
| 2018-01-11 08:39:17 | 2ND REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION, |
| | EXISTING BUILDING CODES |
| | PERMIT #17120197 |
| | 1/11/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | NEW PLAN SHEETS 3.2M AND 3.3M REVIEWED AND NOT |
| | APPROVED. |
| | |
| | 1) SHEET 3.2M: SEE COMMENT #2 FROM THE 1ST REVIEW- |
| | SMOKE DETECTORS REQUIRED FOR AHU- 1, 4 & 5. AN |
| | EXEMPTION CAN BE APPLIED IF MANUFACTURER'S |
| | SPECIFICATIONS INDICATE THE UNITS DO NOT HAVE THE |
| | CAPACITIES TO EXCEED 2000 CFMS OF SUPPLY AIR. PLEASE |
| | SUBMIT THE SPECS TO VERIFY THE CFMS OR PROVIDE THE |
| | DETECTORS. |
| | |
| | 2) 3.2M: SEE COMMENT #6 FROM THE 1ST REVIEW- PROVIDE |
| | THE DIMENSIONS OF THE RETUN AIR OPENING ABOVE THE AHU- |
| | 2 & 3 CLOSET WALL. |
| | |
| | 3) 3.2M & 3.3M: SEE COMMENTS #4, 7, & 8 FROM THE 1ST |
| | REVIEW- INSUFFICIENT OUTDOOR AIR PROVIDED. THE |
| | VENTILATION SCHEDULE IS INCORRECTLY SHOWING 5 CFMS PER |
| | PERSON REQUIRED FOR THE DINING ROOM AND BAR AREA- TABLE |
| | 403.3 REQUIRES 7.5 CFM PER PERSON. TOTAL O/A REQUIRED |
| | IS 1388 CFMS + 642 CFMS = 2030. PLEASE CORRECT THE |
| | VENTILATION SCHEDULE AND THE AIR BALANCE SCHEDULE. |
| | REFER |
| | |
| | TO SECTION C403.2.5.1 AND PROVIDE DEMAND CONTROLLED |
| | VENTILATION FOR THE DINING ROOM AND BAR AREA. |
| | |
| | 4) 3.3M: SEE COMMENT #8 FROM THE 1ST REVIEW- WIND LOAD |
| | DESIGN CRITERIA NOT PROVIDED. |
| | |
| | 5) 3.2M & 3.3M: SEE COMMENT #10 FROM THE 1ST REVIEW- |
| | SHOW THE CONDENSATE PIPING RUNS, SUBMIT SPECS FOR THE |
| | CONDENSATE PUMPS, AND ADD THE PUMPS TO THE ELECTRICAL |
| | SCOPE OF WORK. |
| | |
| | 6) 3.2M & 3.3M: SEE COMMENT #11 FROM THE 1ST REVIEW- |
| | REQUESTED COMBUSTION AIR CALCULATIONS NOT PROVIDED. |
| | |
| | 7) SEE COMMENT #12 FROM THE 1ST REVIEW- REQUESTED FL. |
| | PRODUCT APPROVALS AND/OR MIAMI-DADE NOA'S FOR THE |
| | CONDENSER STANDS AND LOUVERS NOT PROVIDED. |
| | |
| | 8) SEE COMMENT #13 FROM THE 1ST REVIEW- CUT SHEETS FOR |
| | THE GAS-FIRED COOKING APPLIANCES AND MOTORIZED DAMPERS |
| | NOT PROVIDED. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |