2017-12-18 17:06:451ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17120197
 12/18/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 4.0M: LABEL THE (2) 5TON SYSTEMS AND SHOW HOW
 AIR IS BEING RETURNED TO THE SYSTEM IN THE CLOSET BY
 THE RECTANGULAR BAR.
  
 2) 4.0M: SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR
 SYSTEMS OF EACH 5-TON AC SYSTEM PER SECTION 606.2.1.
 PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED IF THE
 MANUFACTURER'S SPECIFICATIONS INDICATE SYSTEMS ARE NOT
 CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR.
  
 3) 4.0M: A SMOKE DETECTOR IS REQUIRED IN THE MECHANICAL
 CLOSET HOUSING THE (2) 10-TON AIR HANDLERS- SECTION
 606.2.2.
  
 4) 4.0M: SHOW THE OUTSIDE DUCT AND INLET LOCATION FOR
 THE 5-TON AIR HANDLER IN THE CLOSET- TABLE 403.3.
  
 5) 4.0M: PROVIDE AN AUTOMATICALLY CONTROLLED SHUT OFF
 DAMPER FOR THE 16"X12" O/A DUCT TO THE 5-TON AIR
 HANDLER BY THE FRONT ENTRANCE- SECTION C403.2.4.4
 FBC-14 ENERGY CONSERVATION.
  
 6) 4.0M: THE 24"X24" RETURN GRILLS FOR THE (2) 10-TON
 AIR HANDLERS ARE UNDERSIZED. GENERALLY RETURN GRILLS
 ARE SIZED AT 200 SQ, INCHES PER TON, OR 50 SQ. INCHES
 PER 100 CFMS. USING THESE CALCULATIONS THE GRILLS WOULD
 HAVE TO BE 2000 SQ. INCHES EACH
  
 7) 4.1M: THE VENTILATION SCHEDULE IS NOT IN COMPLIANCE
 WITH TABLE 403.3 WHICH INDICATES O/A FOR DINING ROOMS
 TO BE CALCULATED AT 70 PERSONS PER 1000 SQ.FT AT 7.5
 CFMS PER PERSON AND 0.18 CFMS. BASED ON THE SQUARE
 FOOTAGES SHOWN IN THE SCHEDULE THE TOTAL O/A REQUIRED
 FOR THE DINING AREAS IS 2588 CFMS. THIS TOTAL DOES NOT
 INCLUDE THE BARS WHICH ARE CALCULATED AT 100
  
 PERSONS PER 1000 SQ. FT. REVISE THE SCHEDULE TO SHOW
 THE REQUIRED CFMS FOR THE BARS AND THE DINING AREAS.
 PLEASE NOTE THAT THE BUILDING REVIEWER IS REQUIRING
 MORE INFORMATION IN ORDER TO DETERMINE AN ACCURATE
 OCCUPANT LOAD.
  
 8) 4.1M: BASED ON COMMENT #5 PRINTED ABOVE, THE AIR
 BALANCE SCHEDULE WILL HAVE TO BE REVISED TO SHOW THE
 ACCURATE CFMS TOTALS.
  
 9) 4.1M: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR
 INSTALLATION OF THE ROOF TOP CONDENSERS AND STANDS-
 SECTION 1609 FBC-14 BUILDING.
  
 10) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE AIR
 HANDLERS- SECTION 307.
  
 11) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 GAS-FIRED COOKING APPLIANCES- SECTION 304 FBC-14 FUEL
 GAS.
  
 12) PROVIDE FL. PRODUCT APPROVALS AND/OR MIAMI-DADE
 NOA'S FOR THE CONDENSER STANDS AND O/A LOUVERS.
  
 13) PROVIDE CUT SHEETS FOR THE GAS-FIRED COOKING
 APPLIANCES AND THE MOTORIZED SHUTOFF DAMPERS.
  
 14) ADVISORY: SEPARATE PERMITS ARE REQUIRED FOR
 ALTERATIONS TO, OR REPLACEMENT OF, THE KITCHEN EXHAUST
 HOOD, THE FIRE SUPPRESSION SYSTEM, AND THE WALK-IN
 COOLER AND FREEZER.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  