| 2017-12-18 17:06:45 | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17120197 |
| | 12/18/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET 4.0M: LABEL THE (2) 5TON SYSTEMS AND SHOW HOW |
| | AIR IS BEING RETURNED TO THE SYSTEM IN THE CLOSET BY |
| | THE RECTANGULAR BAR. |
| | |
| | 2) 4.0M: SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR |
| | SYSTEMS OF EACH 5-TON AC SYSTEM PER SECTION 606.2.1. |
| | PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED IF THE |
| | MANUFACTURER'S SPECIFICATIONS INDICATE SYSTEMS ARE NOT |
| | CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR. |
| | |
| | 3) 4.0M: A SMOKE DETECTOR IS REQUIRED IN THE MECHANICAL |
| | CLOSET HOUSING THE (2) 10-TON AIR HANDLERS- SECTION |
| | 606.2.2. |
| | |
| | 4) 4.0M: SHOW THE OUTSIDE DUCT AND INLET LOCATION FOR |
| | THE 5-TON AIR HANDLER IN THE CLOSET- TABLE 403.3. |
| | |
| | 5) 4.0M: PROVIDE AN AUTOMATICALLY CONTROLLED SHUT OFF |
| | DAMPER FOR THE 16"X12" O/A DUCT TO THE 5-TON AIR |
| | HANDLER BY THE FRONT ENTRANCE- SECTION C403.2.4.4 |
| | FBC-14 ENERGY CONSERVATION. |
| | |
| | 6) 4.0M: THE 24"X24" RETURN GRILLS FOR THE (2) 10-TON |
| | AIR HANDLERS ARE UNDERSIZED. GENERALLY RETURN GRILLS |
| | ARE SIZED AT 200 SQ, INCHES PER TON, OR 50 SQ. INCHES |
| | PER 100 CFMS. USING THESE CALCULATIONS THE GRILLS WOULD |
| | HAVE TO BE 2000 SQ. INCHES EACH |
| | |
| | 7) 4.1M: THE VENTILATION SCHEDULE IS NOT IN COMPLIANCE |
| | WITH TABLE 403.3 WHICH INDICATES O/A FOR DINING ROOMS |
| | TO BE CALCULATED AT 70 PERSONS PER 1000 SQ.FT AT 7.5 |
| | CFMS PER PERSON AND 0.18 CFMS. BASED ON THE SQUARE |
| | FOOTAGES SHOWN IN THE SCHEDULE THE TOTAL O/A REQUIRED |
| | FOR THE DINING AREAS IS 2588 CFMS. THIS TOTAL DOES NOT |
| | INCLUDE THE BARS WHICH ARE CALCULATED AT 100 |
| | |
| | PERSONS PER 1000 SQ. FT. REVISE THE SCHEDULE TO SHOW |
| | THE REQUIRED CFMS FOR THE BARS AND THE DINING AREAS. |
| | PLEASE NOTE THAT THE BUILDING REVIEWER IS REQUIRING |
| | MORE INFORMATION IN ORDER TO DETERMINE AN ACCURATE |
| | OCCUPANT LOAD. |
| | |
| | 8) 4.1M: BASED ON COMMENT #5 PRINTED ABOVE, THE AIR |
| | BALANCE SCHEDULE WILL HAVE TO BE REVISED TO SHOW THE |
| | ACCURATE CFMS TOTALS. |
| | |
| | 9) 4.1M: PROVIDE THE WIND LOAD DESIGN CRITERIA FOR |
| | INSTALLATION OF THE ROOF TOP CONDENSERS AND STANDS- |
| | SECTION 1609 FBC-14 BUILDING. |
| | |
| | 10) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE AIR |
| | HANDLERS- SECTION 307. |
| | |
| | 11) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE |
| | GAS-FIRED COOKING APPLIANCES- SECTION 304 FBC-14 FUEL |
| | GAS. |
| | |
| | 12) PROVIDE FL. PRODUCT APPROVALS AND/OR MIAMI-DADE |
| | NOA'S FOR THE CONDENSER STANDS AND O/A LOUVERS. |
| | |
| | 13) PROVIDE CUT SHEETS FOR THE GAS-FIRED COOKING |
| | APPLIANCES AND THE MOTORIZED SHUTOFF DAMPERS. |
| | |
| | 14) ADVISORY: SEPARATE PERMITS ARE REQUIRED FOR |
| | ALTERATIONS TO, OR REPLACEMENT OF, THE KITCHEN EXHAUST |
| | HOOD, THE FIRE SUPPRESSION SYSTEM, AND THE WALK-IN |
| | COOLER AND FREEZER. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |